control options
<br /> propeller and blower (horizontal delivery unit heaters)—PA/PAE and BA/BAE models 1) 20 03
<br /> Control Service Thermostat Type of
<br /> Control Sy
<br /> stem Description Code
<br /> No Voltage Voltage os
<br /> (Intermittent-duty pilot ignition without lodkout).Includes e combination automatic gas valve and spark 08 116V 25V naturaloy 23ov 26V natural
<br /> ignition controller,overheat control,low voltage transformer,fan timer,and an intermittent pilot without
<br /> lockout.Ignition system is energized bythermostat.Pilot isestablished onlyon callfor heat. 1p®03
<br /> (Low voltage control system).Includes a combination automatic gas valve,overheat control,low voltage 116V 26V natural
<br /> 12 transformer,fan timer,and a standing pilot with 100%safety shut-off.gas valve is energized by thermostat 116V V 265V 2 propane
<br /> 81
<br /> (or manual switch). 1Q©® 82 230 230V propane
<br /> V 26V propane
<br /> ! 26 116V 25V natural
<br /> (Two-stage control).Includes two-stage automatic gas valve,overheat control,low voltage transformer, 26 230V 25V natural
<br /> fan timer,pressure regulator,manual shut-off valve,and a standing pilot with 100%safety shut-off.Gas 83 115V 26V propane
<br /> valve is energized by control thermostat.First stage 50%fire,second stage 100%fire.
<br /> 84 230V 25V propane
<br /> (Intermittent-duty pilot ignition with lockout).Incipcies a combination automatic gas valve and spark 28 116V 26V natural
<br /> ignition controller,overheat control,low voltage transformer,fan timer,and intermittent pilot with lockout. 29 230V 26V natural
<br /> Ignition system is energized by thermostat.Pilot is established only on call for heat. D OO 03 ® 78 116V 25V propane
<br /> 79 230V 25V -propane
<br /> (Mechanical modulation with Intermittent-duty ignition without lockout).includes a combination 51 116V 26V natural
<br /> automatic gas valve and spark ignition controller,overheat control,low voltage transformer,mechanical 52 230V 25V natural
<br /> modulating gas valve,pressure regulator,manual shut-off valve,and an intermittent pilot without lockout.
<br /> Designed for 100%make-up air.System is non-override type and is assembled and pre-wired to the unit.
<br /> Valve modulates rated input from 100%to 40%and shuts off gas below 40%.Temperature range 60OF to
<br /> 900F. 1p p @ (Available on blower units only.)
<br /> (Two stage control with Intermittent-duty pilot ignition without lockout).Includes two-stage automatic 55 116V 25V natural
<br /> gas valve and spark ignition controller,overheat control,low voltage transformer,fan timer,and an 66 230v 25V natural
<br /> intermittent pilot without lockout.Ignition system is energized by thermostat.Pilot is established only on
<br /> call for heat.First stage 50%fire,second stage 100%fire. 1D© 30
<br /> (Mechanical modulation with Intermittent-duty pilot ignition,with lockout).Includes a combination 61 115V 26V natural
<br /> automatic gas valve and spark ignition controller,overheat control,low voltage transformer,mechanical 62 230V 25V natural
<br /> modulating gas valve,pressure regulator,manual shut-off valve and an intermittent pilot with lockout. 76 116V 25V propane
<br /> Designed for 100%make-up air.System is non-override type and is assembled and pre-wired to the unit. 77 230V 25V propane
<br /> Valve modulates rated input from 100%to 40%and shuts off gas below 40%fire.Temperature range 50OF
<br /> to 90oF.01 03 ® (Available on blower units only.)
<br /> (Two-stage control with Intermittent-duty pilot ignition with lockout).Includes two-stage automatic 65 116V 25V natural
<br /> gas valve, and spark ignition controller,overheat control, low voltage transformer,fan timer,and an 66 230V 25V natural
<br /> intermittent pilot with lockout.Ignition system is energized by thermostat.Pilot is established only on call 95 115v 25V propane
<br /> for heat. First stage
<br /> 50% fire, second stage 100% fire.O O 10® 1 96 230V 25V propane
<br /> t1) All single stage units require a Category I vent system.Models PAE 30 and PAE/BAE 50 thru PAE/BAE 100 with two-stage or modulating gas controls require a Category II vent system.
<br /> p For units with control systems having fan timer.Fan starts 30 seconds(max.)after ignition and shuts down approximately 60 seconds after main burner shuts down.Available on units with up to ^"
<br /> 1 H.P.motors or 14 amps @ 115V A.C.Contact Factory for applications with units having motors with horsepower ratings above 1 H.P.or 14 amps @ 115V A.C.
<br /> © Nuisance lockout or ignition malfunction may result if ignition controller is exposed to rain,sprinklers,water from gas pipe leak testing,condensation,and accidental exposure to cleaning
<br /> solutions.
<br /> 40 Whenever 230v/1 0 or 230v/30 power is used,it is necessary to specify 230v/25v controls.Whenever 460v/30 power is used,it is necessary to specify 230v/25v controls and in addition,a
<br /> 460v/230v step-down transformer(by others)is required.This transformer should be 75 VA for units without power venters,and 250VA for units with power venters.On all 30 systems,the
<br /> motor starter coil voltage(motor starter by others)must be 230v.
<br /> Page 26