• <br /> Component Description <br /> 2-2.1.1 SYSTEM NITROGEN CARTRIDGE,P/N B120043 <br /> The UCH Control System uses a nitrogen cartridge for actuating the wet chemical cylinders and is <br /> charged with dry nitrogen(see Figure 2-15).The cartridge is mounted inside the UCH Control System <br /> to protect it from tampering and provides the date of manufacturing and space (gray band) for <br /> recording the installation date. <br /> 5-1/8 in. <br /> (130 mm) <br /> 1-9/16 in. <br /> mm) I/I/h//u <br /> GRAY BAND <br /> Figure 2-15. System Nitrogen Cartridge, P/N B120043 <br /> 2-2.1.2 TEST CARTRIDGE,P/N B120044 <br /> The Test Cartridge is used for testing of the Badger Wet Chemical System. The cartridge has a red <br /> band and labeled"TEST CARTRIDGE"as shown in Figure 2-16. <br /> Note: The System Nitrogen Cartridge P/N B 120043 is required for actuation and full discharge or <br /> "puff'tests. <br /> A The Test Cartridge (P/N B120044) must be removed and the System Nitrogen Cartridge <br /> CAUTION (P/N B120043) must be installed at the completion of any work done on the system. <br /> Failure to do so will result in malfunction of the system. <br /> 4 In. <br /> (102 mm) <br /> 1 in. TEST 11111 <br /> (25 mm) CARTRIDGE <br /> Figure 2-16. Test Cartridge, P/N B120044 <br /> January 2007 2-14 P/N 9127100 <br /> I '2,11 <br />