Page 4 of 6
<br />C MICROMATIC°STANDARD
<br />RESPONSE HORIZONTAL
<br />SIDEWALL SPRINKLER
<br />VK104 (K5.6)
<br />The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
<br />Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
<br />Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
<br />Approval Chart 1 (UL)
<br />Temperature
<br />KEY
<br />Micromatic° Viking Standard Response Horizontal Sidewall Sprinkler VK104 � Finish
<br />For Light Hazard Occupancies Only A1X4--Escutcheon(ifapplicable)
<br />Maximum 176 PSI (12 Bar) WWP
<br />Sprinkler
<br />Thread Size
<br />Nominal K-factor
<br />Overall Length
<br />Listings and Approvals3
<br />Base Part
<br />SIN
<br />(Refer also to UL Design Criteria.)
<br />Number'
<br />NPT
<br />BSPT
<br />U.S.
<br />metricz
<br />Inches
<br />mm
<br />cULus°
<br />LPCB
<br />MED
<br />CE8
<br />China
<br />Approval
<br />12995
<br />VK104
<br />1/2"
<br />--
<br />5.6
<br />80.6
<br />2-1/2"
<br />64
<br />A1Z, B1X, B2X, C4Z, E4Y
<br />A1Z, B2Z
<br />C19
<br />C1Z8
<br />12988
<br />VK104
<br />--
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/2"
<br />64
<br />A1Z, B1X, B2X, C4Z, E4Y
<br />A1Z, B2Z
<br />C19
<br />C1Z8
<br />2023010
<br />1 VK104
<br />--
<br />15 mml
<br />5.6
<br />80.6
<br />2-1/2"
<br />64
<br />D3
<br />D3
<br />NOTICE
<br />10224
<br />VK104
<br />1/2"
<br />5.6
<br />80.6
<br />2-1/2"••
<br />64
<br />B2W,•B1W,A1X
<br />A1Z
<br />C19
<br />C1Y8
<br />C1Z9
<br />10171
<br />1 VK104
<br />1 --
<br />115 mml
<br />5.6
<br />1 80.6
<br />1 2-1/2"
<br />1 64
<br />1 132W, B1W,A1X
<br />A1Z
<br />C19
<br />C1Y8
<br />C1Z9
<br />Approved Temperature Rating Codes
<br />A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 °C)
<br />B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
<br />C = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 °C)
<br />D=155°F(68°C)
<br />E = 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
<br />Approved Finish Codes
<br />1 = Brass, Chrome, White Polyester61, and Black Polyester61
<br />2 = Wax -Coated Brass and Wax Over Polyester (corrosion resistant)
<br />3 = Chrome
<br />4 = ENT6
<br />Approved Escutcheon Codes
<br />W = Standard surface -mounted escutcheons or recessed with the Viking Model E-1, E-2, E-3, or Model G-1 Recessed Escutcheons
<br />X = Standard surface -mounted escutcheons or recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheons
<br />Y = Installed with surface -mounted escutcheons or recessed with the Viking Model E-1 Recessed Escutcheons
<br />Z = Installed with surface -mounted escutcheons only
<br />Footnotes
<br />I. Base part number shown. For complete part number, refer to Viking's current price schedule.
<br />2. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
<br />3. This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
<br />a. Listings and Approvals are limited to Light Hazard Occupancies where allowed by the installation standards being applied.
<br />5. Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
<br />s. cULus Listed as corrosion -resistant.
<br />7. Other colors are available on request with the same Listings and Approvals as the standard colors.
<br />e. Certified, Standard EN 12259-1, EC -certificate of conformity 0832-CPD-0021 and 0832-CPD-2003.
<br />9. MED Certified, Standard EN 12259-1, EC -certificate of conformity 0832-MED-1003 and 0832-MED-1008.
<br />10.Approved according to China GB standard.
<br />DESIGN CRITERIA - UL
<br />(Also refer to Approval Chart 1 above.)
<br />cULus Listing Requirements:
<br />The Micromatic° Viking Standard Response Horizontal Sidewall Sprinkler VK104 is cULus Listed as indicated in the Approval Chart for installation in accordance with
<br />the latest edition of NFPA 13 for sidewall standard spray sprinklers.
<br />• For use in Light Hazard occupancies only where allowed by the installation standards being applied.
<br />• Locate the deflector 4" to 12" (102 mm to 305 mm) below the ceiling.
<br />• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.
<br />• Minimum spacing allowed is 6 ft. (1.8 m).
<br />• Align the top of the deflector parallel with the ceiling.
<br />• Locate no less than 4" (102 mm) from end walls.
<br />• Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall.
<br />• The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed.
<br />IMPORTANT: Always refer to Bulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to Bulletin Form No. F 080614 for
<br />general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking
<br />technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of gov-
<br />ernmental codes, ordinances, and standards, whenever applicable.