M <br /> GENERAL NOTES: <br /> o <br /> FIRE ALARM SYMBOL LEGEND 1. SCOPE OF WORK: THIS PROJECT SHALL INCLUDE THE REPLACEMENT OF AN <br /> NOTE a SYMBOLS ar NOT BE USED M THIS MWEDT EXISTING DMP XR550 PANEL FOR A NEW XR150DNFC-R PANEL. ALL FIELD DEVICES <br /> SYMBOL DESCRIPTION MANUF. & PART # MOUNTING MOUNT IN QTY SHALL REMAIN THE SAME. <br /> 2. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS <br /> FACP FIRE ALARM CONTROL PANEL DMP—XR150DNFC—R WALL—TOP 066° CABINET INCLUDED 1 FOR EXACT DIMENSIONS. Z <br /> ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION <br /> ® rDm" s © 3. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE a x <br /> E EXISTING AWG AMERICAN WIRE GAUGE L1 S001 OR M01 - v <br /> G WITH GUARD TWP TWISTED PAIR (L—DENOTES LWP!1 - - - CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. <br /> P PENDENT MOUNT TWSP TWISTED SHIELDED PAIR (s or u-DrNOTrs sENsaB olS,uoout��) - W �, <br /> R RESIDENTIAL 110 FPLP FIRE POWER LIMITED PLENUM 1- 16 2 TWP - 4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY c <br /> =�. DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING o <br /> S SOUNDER BASE FPLR FIRE POWER LIMITED RISER wlu-E ASBRVTm CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA W WP WEATHERPROOF OON.0 COUM <br /> EOL END OF LINE RESISTOR ®15j "�30� �w!lBrsrze _� _ _ SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS N <br /> bNOF 1CAM(lIFi OMITT D � LONG AS NO 11 OV OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. ti <br /> ED, END OF LINE RELAY z <br /> a gip, 5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE-RATED y <br /> CONSTRUCTION. w <br /> o4 rc <br /> s 6. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE <br /> PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH <br /> CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT, Z co <br /> co <br /> MECHANICALLY PROTECTED, ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND O <br /> LL Q SHALL BE RED AND LABELED FIRE ALARM CIRCUIT CONTROL' IN ACCORDANCE <br /> o < 5z o 3 WITH NFPA 72. ELECTRICAL CONTRACTOR SHALL PERFORM LOAD CALCULATIONS TO � <br /> a z o N x S 1 f DETERMINE SIZE OF WIRING AND BREAKERS FOR ALL FIRE ALARM AC BRANCH � <br /> OPERATIONS W CIRCUITS BASED ON THE INFORMATION PROVIDED IN THE BATTERY CALCULATIONS I <br /> FOR THE FIRE ALARM EQUIPMENT. o <br /> MATRIX <br /> 7. POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED <br /> ExIsrlNc SYSTEM OPERATIONS SHALL y x IN CABINET. ALL POWER-LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" Zig <br /> REMAIN,FIELD VERIFY ACTUAL SYSTEM o y z o y o o T,., 4 AWAY FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL <br /> OPERATIONS z rn .y w . <br /> 0 o w m w m , POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT28 <br /> — w <br /> M IN W a N a ' 3 ��' a<a fA THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. E <br /> E �^ 8. WHEN UTILIZING CLASS "A" CIRCUITS, SEPARATE OUTGOING AND RETURN Q w <br /> 'g 000-0, <br /> CONDUCTORS OF CLASS "A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN (n nFIRE ALARM INPUT c a a N s z VERTICALLY AND 48" WHERE RUN HORIZONTALLY. J <br /> SMOKE DETECTORS • • • • j•j•j•j• • y` - 9. WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH Q <br /> HEAT DETECTORS • • • • • • • • JUNCTION BOX. INSULATE AND TAPE BACK AT END. <br /> KITCHEN HOOD • • • • • • • • 10. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT E- <br /> PULL STATIONS • • • • • • • • MANUFACTURER FOR THE INTENDED PURPOSE. CABLES USED IN VERTICAL RUNS <br /> BE TYPE FPP OR FPLR. CABLEBE <br /> WATERA OW SWITCHES • • • • • • • • N VICINITY MAP NHALL LISTED FITTINGS, BOXES, ENCLOSURES,P FIRE SALARMEDEVICES,NORSHALL UTILIZATIONADE <br /> EQUIPMENT. WHERE INSTALLED EXPOSED, CABLES SHALL BE ADEQUATELY <br /> VALVE SUPERVISORY SWITCHES • • • • SCHEMATIC:NOT ro SCALE SUPPORTED AND INSTALLED IN SUCH A WAY THAT MAXIMUM PROTECTION AGAINST <br /> DUCT DETECTORS • • • • • • PHYSICAL DAMAGE IS AFFORDED BY BUILDING CONSTRUCTION. WHERE LOCATED <br /> FIRE ALARM AC POWER FAIL • • • • WITHIN 7 FT OF THE FLOOR, CABLES SHALL BE SECURELY FASTENED IN AN <br /> FIRE ALARM LOW BATTERY • • • • APPROVED MANNER AT INTERVALS OF NOT MORE THAN 18 IN. <br /> OPEN CIRCUIT • • • • 11. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION <br /> CLEAN-UP IS COMPLETED AND FINAL. <br /> GROUND FAULT • • • • <br /> NAC SHORT CIRCUIT • • • • 12. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL <br /> DIFFUSERS. WALL-MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MAXIMUM OF <br /> LOSS OF AC TO BUILDING • • • • • 12" FROM CEILING. <br /> 13. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. <br /> PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI-SYNC MODE SLAVE <br /> CONNECTION BETWEEN ALL SYNC MODULES. <br /> 14. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES Z <br /> WITH FIRE ALARM CONTRACTOR. W <br /> 15. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, W <br /> A/C SUPPLY OR THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE <br /> RETURN DIFFUSER PENDANT MOUNTED, NOTE:MEASUREMENTS SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A 0 T_ <br /> CEILING—MOUNTED J� AUDIBLE/VISUAL SHOWN ARE TO THE FINAL FIRE ALARM SYSTEM INSPECTION. Q W p Z <br /> a"MIN HEAT DETECTOR VWWNP APPLIANCES DLOSEST ETECTORPOINT OF 16. PROVIDE OFF-SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, Z > cm <br /> FACP 7770���� 00 <br /> � <br /> 36"MIN. SECTION 907.6.6 AND THE LOCAL AUTHORITY HAVING JURISDICTION. Q Q J <br /> 4"MIN 6"MIN. <br /> DMP 12"MAX AUDIBLE/VISUAL AUDIBLE—ONLY REMOTE ALARM <br /> CEILING MOUNTED CEILING MOUNTED 12"MAX 17. INSTALLING CONTRACTOR SHALL, PHYSICALLY, LABEL ALL INITIATING DEVICES AND a <br /> NEVER AND/OR VISUAL APPLIANCES INDICATOR SMOKE/HEAT AUDIBLE/VISUAL NOTIFICATION APPLIANCE CIRCUIT END OF LINE WHEN WIRING CLASS "B". THESE W Q <br /> XR150DNFCR HERE ONLY APPLIANCE DETECTOR APPLIANCES ( ) �y <br /> ZONE 1 ��UU �f SMOKE OUNTEDR LABELS SHALL BE IN PLACE PRIOR TO START-UP AND TESTING. Y LL <br /> W WALL—MOUNTED DOOR WIDTH 18. ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS a/ V Q <br /> o HEAT DETECTOR LESS 3 AND VALVES OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS J <br /> ZONE#2 �" SHALL BE IDENTIFIED WITH PERMANENTLY MOUNTED SIGNS WITH LETTERING NOT W <br /> W MAGNETIC 0 30'MAX LESS THAN 2 INCHES TALL WITH A PRINCIPAL STROKE OF NOT LESS THAN 3/8 a. W Q <br /> ZONE 3 EXISTING INITIATING:REMAINING THE SAME DOOR ' INCH. LETTERS SHALL CONTRAST WITH BACKGROUND. Q Cfl W <br /> o FACP SYSTEM HOLDER <br /> ® RECORDS. 80"-96" 90"MIN. 10'MAX 30'MAX SIDE WALL N p W <br /> ZONE 4 DOCUMENTS Permit#: FA2305-015 LL \\ _ <br /> TO LOWEST WHERE CEILING AFF AFF a / LL <br /> PART OF LENS � Site Address: 3706 Rucker Ave (� <br /> HEIGHT ALLOWSLU <br /> 5'MAX. Applicant: Washington Alarm Inc. L <br /> 66"TO 66"TO 66"TO FROM EXIT ��rFF'gppgg�TTII�� "-WNNIISHED Application Date:5/12/2023 <br /> TOP OF TOP OF TOP OF It�l I Description: Panel Replacement V <br /> FACP-1 FSA FACP CABINET —T <br /> MANUAL 42—48" Review Status: 1st Review by City&Peer Reviewers <br /> PULL Review Date: 5/17/2023 <br /> FINISHED STATION <br /> FLOOR <br /> FACP-2 EXISTING NOTIFICATION:REMAINING THE SAME <br /> EVERETT rvrBBTT <br /> FACP-3 FIRE ALARM DEVICE MOUNTING HEIGHTS Everett Fire Dept.Permit Review <br /> 120 VAC SCALE:NOT TO SCALE Status:Approved <br /> (DEDICATED CIRCUIT) ( Reviewed By:KBrown <br /> 05/17/2023 1:48:37 <br /> PM <br /> d4T1ERY <br /> Drawings reviewed by: DRAWN CRL <br /> Brady B.Haws SET UNICAD JOB#23229 <br /> NICET Certification CHECKED BRADY B.HAWS <br /> FIRE ALARM RISER DIAGRAM Fire Protection Engineering Technology NICET IV138751 <br /> Fire Alarm Systems-Level IV DATE 5/5/2023 <br /> SCHEMATIC NOT TO SCALE Cert.No.138751 REVISION 0 <br /> Exp 5/1/2025 <br /> " ' " <br /> UNICARdrnE=F�_ <br /> Noa+pW-S. <br /> °T�315 <br /> .YnlWd.nl1 <br />