Laserfiche WebLink
MECHANICAL ENERGY CODE NOTES GENERAL NOTES GENERAL SYMBOLS ABBREVIATIONS BOGARD I PASCUA <br /> ENGINEERS,PS <br /> ADA AMERICANS WITH DISABILITIES ACT KW KILOWATTS CONSULTING ENGINEERS <br /> 1. MECHANICAL SYSTEMS HAVE BEEN DESIGNED PER THE REQUIREMENTS OF THE FOLLOWING CODES: 1. THE FOLLOWING NOTES APPLY TO ALL MECHANICAL DRAWINGS. M-1 MECHANICAL zz+z+nthA anus sE,&bll+ <br /> ADDITIONAL MECHANICAL NOTES MAY BE INDICATED ON EACH EQUIPMENT <br /> • 2018 WASHINGTON STATE ENERGY CODE(WASHINGTON ADMINISTRATIVE CODE(WAC)CHAPTER 51-11C) AFF ABOVE FINISHED FLOOR LAT LEAVING AIR TEMPERATURE Bung+.wale ao seoz+ <br /> azsa+ss+w <br /> MECHANICAL,PLUMBING AND FIRE PROTECTION DRAWING.REFER IDENTIFICATION AHJ AUTHORITY HAVING JURISDICTION LBS POUNDS <br /> • 2018 INTERNATIONAL BUILDING CODE WITH WASHINGTON STATE AMENDMENTS(WAC CHAPTER 51-50) TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL DETAILS. ARCH ARCHITECT/ARCHITECTURAL LF LINEAR FOOT <br /> • 2018 INTERNATIONAL MECHANICAL CODE WITH WASHINGTON STATE AMENDMENTS(WAC CHAPTER 51-52) PLUMBING FIXTURE BDD BACKDRAFT DAMPER LV,LAV LAVATORY <br /> 2018 UNIFORM PLUMBING CODE WITH WASHINGTON STATE AMENDMENTS(WAC CHAPTER 51-56) 2. INSTALL ALL PIPING ON ROOM SIDE OF BUILDING INSULATION. K"1 IDENTIFICATION BTU BRITISH THERMAL UNITS MA MIXED AIR <br /> • 2018 INTERNATIONAL FUEL GAS CODE WITH WASHINGTON STATE AMENDMENTS(WAC CHAPTER 51-52) 3. ENGINEERED DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO CD CEILING DIFFUSER MAX MAXIMUM W gOC <br /> • 2009 ICGA117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES NOT NECESSARILY REFLECT EVERY REQUIRED OFFSET,FITTING AIR TERMINAL MARK CFM CUBIC FEET PER MINUTE MBH 1,000 BTUS <br /> OR ACCESSORY.REFER TO SYSTEM SCHEMATIC DIAGRAMS FOR s� <br /> ADDITIONAL DESIGN INFORMATION INCLUDING VALVE SIZES AND TYPE CG CEILING GRILLE MCA MINIMUM CIRCUIT AMPS <br /> 2. HEATING AND COOLING SYSTEMS HAVE BEEN SIZED IN ACCORDANCE WITH STANDARD ENGINEERING LOCATIONS. �(SEE SCHEDULE) CL CENTER LINE MD MOTORIZED DAMPER <br /> PRACTICES AND AS REQUIRED BY 2018 WSEC SECTIONS C403.1.2. HVAC SYSTEMS HAVE BEEN DESIGNED PO CO CLEANOUT MECH MECHANICAL ,. <br /> TO COMPLY WITH 2O18 WSEC SECTION C302.1 AND TO MAINTAIN 72 DEGREES F MAX IN HEATING MODE AND 4. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO �DESIGN CFM CONT CONTINUATION MIN MINUTES OR MINIMUM P e 3736 <br /> 75 DEGREES F MIN IN COOLING MODE.HEATING AND COOLING LOAD CALCULATIONS USE THE FOLLOWING BEGINNING WORK IN ORDER TO OBSERVE EXISTING CONDITIONS. COP COEFFICIENT OF MOCP MINIMUM OVER CURRENT °F FG'm <br /> BUILDING THERMAL INSULATION VALUES AND DESIGN TEMPERATURES IN ACCORDANCE WITH THE ASHRAE VERIFY EXACT SIZE,LOCATION AND CONDITION OF ALL EXISTING SS ONAL EN <br /> RECOMMENDED OUTDOOR DESIGN TEMPERATURES FOR EVERETT IN WASHINGTON STATE: SYSTEMS,DUCTS,PIPES,UTILITIES AND BUILDING STRUCTURE. DETAIL REFERENCE PERFORMANCE PROTECTION <br /> • SUMMER OSA:81°F DBI66°F WB ROOF: U=0.037 BTU/HRISFI°F VERIFY VOLTAGES AT THE SITE PRIOR TO ORDERING ANY DETAIL NUMBER CW DOMESTIC COLD WATER N/A NOT APPLICABLE <br /> • SA HEATING:95°F MAX WALLS: U=0.14 BTU/HR SF/°F EQUIPMENT. 1 0 DIAMETER NG NATURAL GAS <br /> • SA COOLING:55°F MIN WINDOWS:U=0.65 BTU/HRISFI°F 5. ALL DISCONNECTS AND LINE VOLTAGE WORK SHALL BE PROVIDED M2 DEG F DEGREES IN HEIT NP NON POTABLE <br /> BY DIVISION 26 DRAWING ON WHICH DELTA T TEMPERATUREE RISE <br /> ISE OR DROP OSA OUTSIDE AIR <br /> . <br /> • WINTER OSA:23°F SHGC=0.70 DETAIL IS LOCATED DFU DRAINAGE FIXTURE UNITS POC POINT OF CONNECTION <br /> 6. ALL SMOKE DETECTORS SHALL BE SUPPLIED BY DIVISION 23. DN DOWN PRV PRESSURE REDUCING VALVE <br /> 3. OUTSIDE AIR VENTILATION AND EXHAUST SHALL BE PROVIDED IN ACCORDANCE WITH 2O18 IMC TABLE SECTION REFERENCE DWG DRAWING PSI POUNDS PER SQUARE INCH <br /> C403.3.1.1 FOR MINIMUM REQUIRED RATES AND NO MORE THAN 150%OF THE MINIMUM RATES PER 2018 7. SMOKE DETECTOR POWER SHALL BE PROVIDED BY DIVISION 26; <br /> WSEC SECTION C403.2.2. SIGNAL SHALL BE RECEIVED BY DIVISION 28.SMOKE DETECTION SECTION NUMBER DWH DOMESTIC WATER HEATER RA RETURN AIR <br /> SHALL SHUT DOWN ASSOCIATED EQUIPMENT AND ALARM TO THE A DWV DOMESTIC WASTE AND VENT RG RETURN I RELIEF GRILLE <br /> FIRE ALARM CONTROL PANEL. (E) EXISTING ITEMS RL RAIN LEADER OR REFRIGERANT <br /> 4. HEAT PUMP CONTROLS SHALL BE CONFIGURED TO PROVIDE A MINIMUM 5 DEGREE DEAD BAND AS M"2 DRAWING ON WHICH EA EXHAUST AIR LIQUID <br /> REQUIRED BY 2018 WSEC SECTION C403.4.1.2. 8. ARRANGE MECHANICAL EQUIPMENT SO THAT NO LESS THAN THE SECTION IS LOCATED EAT ENTERING AIR TEMPERATURE RPBP REDUCED PRESSURE BACKFLOW <br /> MINIMUM OPERATING AND SERVICE CLEARANCES ARE PROVIDED EER ENERGY EFFICIENCY RATING PREVENTER <br /> AS REQUIRED BY CODE ANDIOR THE EQUIPMENT REVISION <br /> 5. CONTROLS FOR SYSTEMS THAT DO NOT OPERATE CONTINUOUSLY SHALL BE CAPABLE OF PROVIDING MANUFACTURER'S INSTALLATION INSTRUCTIONS. 0 IDENTFICATION EFF EFFICIENCY/EFFICIENT IRS REFRIGERANT SUCTION <br /> SEVEN DAY PROGRAMMABLE TEMPERATURE SETTINGS,AUTOMATIC SETBACK AND SHUTOFF AND OPTIMUM ELECT ELECTRICAL SA SUPPLY AIR <br /> START AS REQUIRED BY 2018 WSEC SECTION C403.4.2. 9. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED M>- FLAG NOTE ESP EXTERNAL STATIC PRESSURE SD SMOKE DETECTOR <br /> FITTINGS,VALVES,ETC.FLOOR PLANS AND SECTIONS INDICATE <br /> EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY. FACP FIRE ALARM CONTROL PANEL SENS SENSOR OR SENSIBLE <br /> 6. DUCT WORK SHALL BE SEALED,INSULATED AND PROVIDED WITH A VAPOR BARRIER AS REQUIRED BY 2018 PROVIDE PIPING SHOP DRAWINGS COORDINATED WITH OTHER FCO FLOOR CLEANOUT SFD COMBINATION SMOKE/FIRE DAMPER N <br /> WSEC SECTION C403.10. TRADES.REFER TO SPECIFICATIONS FOR ADDITIONAL SHOP <br /> FD FIRE DAMPER E M <br /> FLOOR DRAIN SG SUPPLY GRILLE <br /> DRAWING REQUIREMENTS. FD FIRE DEPARTMENT <br /> 7. MECHANICAL PIPING,IF EXPOSED TO THE ENVIRONMENT,SHALL BE PROTECTED AND ALL PIPING SHALL BE NT SK SINK �j <br /> INSULATED AS REQUIRED BY 2018 WSEC SECTION C403.10.3. 10. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 8'-0". FDC FIRE DEPARTMENT CONNECTION TSTAT THERMOSTAT <br /> FT FOOT OR FEET TD TRENCH DRAIN U Q N <br /> 11. EXISTING BUILDING MANAGEMENT SYSTEM(BMS)IS ALERTON BY FT WG FEET OF WATER GAGE PRESSURE TP TRAP PRIMER ^ <br /> 8. HVAC DISTRIBUTION SYSTEMS SHALL BE AIR AND WATER BALANCED TO MINIMIZE THROTTLING LOSSES AS ATS.SYSTEM SHALL BE EXPANDED TO INCLUDE NEW MONITORING FU FIXTURE UNITS TYP TYPICAL Ia- Q <br /> REQUIRED BY 2018 WSEC SECTION C408.2.2. POINTS FOR THE NEW FLUID COOLER AND ITS ASSOCIATED HEAT FV FLUSH VALVE LINO UNLESS NOTED OTHERWISE <11 <br /> TRACE.IN ADDITION,INFORMATION ON DESIGN AIR AND WATER GA GAUGE V VENT <br /> 9. PROVIDE NEW MECHANICAL EQUIPMENT WITH CODE REQUIRED MINIMUM EFFICIENCIES,OR BETTER,PER FLOW RATES SHALL BE ADDED TO THE BMS,TO BE DISPLAYED O <br /> 2018 WSEC TABLES 403.3.2(1)THROUGH 403.3.2(12). WHERE APPLICABLE WITHIN THE SYSTEM AND/OR TO BE EASILY GAL GALLONS VA VALVE I"1 <br /> ACCESSIBLE FOR THE MAINTENANCE TEAM TO USE IN IDENTIFYING DUCTWORK SYMBOLS GPF GALLONS PER FLUSH VD VOLUME DAMPER Q a <br /> EQUIPMENT THAT MAY BE OUT OF BALANCE OR OPERATING GPH GALLONS PER HOUR VTR VENT THROUGH ROOF 1 O <br /> 10. PROVIDE WITH AT LEAST 70%EFFICIENT OR ELECTRONICALLY COMMUTATED MOTOR AS REQUIRED BY 2018 IMPROPERLY.IN ADDITION,DEMAND CONTROLLED VENTILATION WSEC SECTION C405.8 FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE 1/12 HORSEPOWER AND PARAMETERS SHALL NOT BE DISPLAYED IN THE ZONES,ONLY AT DUCT SECTION-SUPPLY GPM GALLONS PER MINUTE VFD VARIABLE FREQUENCY® 1-y 0 <br /> DRIVE <br /> LARGER AND ARE NOT OTHERWISE SPECIFIED BY THE CODE. THE BMS. GV GATE VALVE W WASTE O I-OI-�II <br /> DUCTSECTION-RETURN HP HORSEPOWER WC WATER CLOSET Q Z x <br /> C HOT WATER WCO WALL CLEANOUT I �- <br /> 11. A PRELIMINARY COMMISSIONING PLAN INCLUDING INFORMATION REGARDING EQUIPMENT TO BE RECTANGULAR DUCT HAG DOMEST I HW DOMEST C HOT WATER RETURN WG WATER GAUGE <br /> COMMISSIONED,FUNCTIONS TO BE TESTED,CONDITIONS OF TESTING AND MEASURABLE CRITERIA SHALL 20x12 (INSIDE DIMENSION) U <br /> BE PROVIDED TO THE OWNER'S APPOINTED CERTIFIED COMMISSIONING PROFESSIONAL PRIOR TO THE IE INVERT ELEVATION WHA WATER HAMMER ARRESTOR UICI <br /> AHJ'S FIRST MECHANICAL INSPECTION AS REQUIRED BY 2018 WSEC SECTION C408.1.2. 20"o ROUND DUCT IN INCHES <br /> 12. FUNCTIONAL TESTING OF MECHANICAL SYSTEMS SHALL BE PROVIDED TO ENSURE PROPER OPERATION IN FLEX CONNECTION E- 1--1 <br /> ALL SEQUENCES OF OPERATIONS INCLUDING POWER FAILURE AS REQUIRED BY 2018 WSEC SECTION PIPING SYMBOLS <br /> C408.1.2.2. Iw=J <br /> L20x12 LINED DUCT(INSIDE DIMENSION) <br /> x6� BALL VALVE h HEAT TRACE <br /> 13. COPIES OF ALL APPLICABLE SERVICE AND EQUIPMENT DATA,AND PROJECT DOCUMENTATION THAT W Q <br /> RELATES,SHALL BE PROVIDED TO THE OWNER AND MADE AVAILABLE TO THE AUTHORITIES HAVING __L12x10__ LINED DUCT(INSIDE DIMENSION) tlrG BALANCING VALVE HWS HEATING WATER SUPPLY 00 W <br /> JURISDICTION(AHSS)WITHIN 180 DAYS OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY AS REQUIRED BY F _ <br /> C �!� BUTTERFLY VALVE --HWR--- HEATING WATER RETURN <br /> 2018 WSEC SE TION C103.6 INCLUDING: A 90°CONICAL SPIN-IN FITTING t� CHECK VALVE CA COMPRESSED AIR W W <br /> • RECORD DRAWINGS DEPICTING FINAL INSTALLATION CONFIGURATIONS OF SYSTEMS AND EQUIPMENT �,�µ <br /> • OPERATION AND MAINTENANCE EQUIPMENT MANUALS INCLUDING:MANUFACTURER'S INFORMATION ON "' FLEXIBLE DUCT i�i CLEAN OUT -CWS- CONDENSER WATER SUPPLY <br /> SPECIFIC MODEL NUMBERS AND OPTIONS INSTALLED,CONTROLS DATA INCLUDING CALIBRATION AND c� CONTROL VALVE-2 WAY ---CWR--- CONDENSER WATER RETURN U <br /> DESIGN SETPOINT INFORMATION,AND RECOMMENDED MAINTENANCE SCHEDULE WITH A REPUTABLE ', TURNING VANE <br /> SERVICE CONTRACTOR'S CONTACT INFORMATION. t� CONTROL VALVE-3 WAY _ID- INDIRECT OR CONDENSATE DRAIN <br /> • ENERGY CODE COMPLIANCE FORMS AND OTHER RELATED REPORTS SUCH AS AIR AND WATER BALANCING, �-� CEILING DIFFUSER --- DEMOLISHED ITEM F FIRE SPRINKLER PIPE <br /> START-UP AND/OR PRESSURE TESTING DATA AS APPLICABLE. <br /> • TRAINING OF THE MAINTENANCE STAFF SHALL BE PROVIDED,INCLUDING REVIEW OF DOCUMENTATION, RETURN/EXHAUST/ FLOW METER G NATURAL GAS <br /> HANDS-ON DEMONSTRATION OF OPERATION AND START-UP PROCEDURES AS WELL AS A TRAINING ©COMPLETION REPORT. TRANSFER GRILLE OR REGISTER FLEX CONNECTION RL RAIN LEADER <br /> VOLUME DAMPER tea- GATE VALVE -ORL- OVERFLOW RAIN LEADER <br /> MOTORIZED DAMPER PRESSURE REDUCING VALVE PIPE DOWN <br /> PRESSURE RELIEF VALVE PIPE UP <br /> ADDITIONAL CODE NOTES COMBINATION SMOKE/FIRE DAMPER RPBP B REDUCED <br /> PRESSURE <br /> -PREVENTE HOSE BIBB/WALL HYDRANT <br /> DUCT SMOKE DAMPER �cu HOSE DRAIN VALVE <br /> AMERICANS WITH DISABILITIES ACT __o BACKDRAFT DAMPER THERMOMETER 0 VENT THROUGH ROOF <br /> • ROOM SENSORS AND SWITCHES SHALL BE MOUNTED ON WALLS NO MORE THAN 48"ABOVE FINISHED Imo- UNION ® FLOOR DRAIN <br /> T THERMOSTAT VENT <br /> FLOOR FOR ADA ACCESSIBILITY. � -------- ® FLOOR SINK <br /> �S SENSOR WASTE SPRINKLER HEAD-PENDANT <br /> INTERNATIONAL BUILDING CODE _ COLD WATER(DOMESTIC) ® SPRINKLER HEAD-UPRIGHT <br /> OCCUPANCY OR CO2 SENSOR RRa.No: 21015.00 <br /> 0 <br /> • PROVIDE SEISMIC BRACING AND SUPPORTS IN ACCORDANCE WITH THE 2018 IBC FOR SEISMIC DESIGN � HOT WATER(DOMESTIC) <br /> CATEGORY D AND BASED ON A SEISMIC IMPORTANCE FACTOR OF 1.0 FOR ALL SYSTEMS,EXCEPT THE GAS OMM BY: - <br /> PIPING SHALL USE AN IMPORTANCE FACTOR OF 1.5. © CO AND NO2 TOXIC GAS SENSOR --- HOT WATER RECIRCULATED <br /> • PROTECT ALL DUCT OPENINGS OF FIRE RATED ASSEMBLIES PER IBC 716. cuEcxeo BY:LWB <br /> DATE: FEB 3,2023 <br /> INTERNATIONAL FUEL GAS CODE REVISIONS REVISION I ISSUE DATE <br /> • PROVIDE WITH A SEDIMENT TRAP AND A TEST PORT REQUIRED BY 2018 IFGC SECTION 410.2 FOR NATURAL MINIMUM PIPE INSULATION THICKNESS PER 2018 WSEC TABLE C403.10.3. A BID SET <br /> GAS PRVS. <br /> FLUID OPERATING INSULATION REQUIREMENTS NOMINAL PIPE OR TUBE SIZE INCHES <br /> UNIFORM PLUMBING CODE TEMPERATURE CONDUCTIVITY MEAN RATING <1 1 TO<1-1 PL 1-1/2 TO<4 4 TO<8 8 OR LARGER <br /> • SANITARY WASTE PIPING SHALL BE INSTALLED AT 114"PER FOOT SLOPE AWAY FROM FIXTURES UNLESS BTU'IN/HR"SF'DEG F TEMPERATURE <br /> NOTED OTHERWISE ON THE FLOOR PLANS. 141 TO 200 <br /> • PIPING IN CONNECTION WITH A PLUMBING SYSTEM SHALL BE SO INSTALLED THAT PIPING OR CONNECTIONS DEGREES F 0.25 TO0.29 125 DEGREES F 1.5 1.5 2.0 2.0 2.0 <br /> WILL NOT BE SUBJECT TO UNDUE STRAINS OR STRESSES,AND PROVISIONS SHALL BE MADE FOR <br /> EXPANSION,CONTRACTION,AND STRUCTURAL SETTLEMENT.VOIDS AROUND PIPING PASSING THROUGH <br /> CONCRETE FLOORS ON THE GROUND SHALL BE SEALED PER UPC 312.1. 105 TO 140 <br /> DEGREES F 0.21 T00.28 100 DEGREES F 1.0 1.0 1.5 1.5 1.5 <br /> 64 TO 104 0.21 TO0.28 100 DEGREES F 1.0 1.0 1.5 1.5 1.5 <br /> DEGREESF <br /> aoroso DRAWING INDEX <br /> DEGREES F 0.21 TO0.27 75 DEGREES F 0.5 0.5 1.0 1.0 1.0 DWG. DESCRIPTION <br /> <40 DEGREES F 0.20 TO0.26 75 DEGREES F 0.5 1.0 1.0 1.0 1.5 M0.0 COVER SHEET <br /> M0.1 MECHANICAL LEGEND,NOTES,AND ABBREVIATIONS <br /> M0.2 EQUIPMENT SCHEDULES <br /> MINIMUM DUCT INSULATION REQUIREMENTS PER 2018 WSEC SECTION C403.10.1 M0.3 EQUIPMENT SCHEDULES <br /> DUCT TYPE DUCT LOCATION INSULATION MINIMUM VAPOR BARRIER OTHER NOTES M1.1 BUILDING 5 OVERALL PLAN <br /> R-VALUE <br /> FOR M1.2 ATTIC DEMOLITION PLAN <br /> SUPPLYAND UNCONDITIONED 6 MECHANICALLY M1.3 ENLARGED ATTIC DEMOLITION PLANS <br /> RETURN SPACE SHEET TITLE <br /> COOLED <br /> M1.4 ENLARGED ATTIC DEMOLITION PLANS <br /> U M1.5 FLOOR PLAN MECHANICAL <br /> OTSIDEAIR TSIDEAI CONDITIONED SPACE 7 YES LEGEND, NOTES, <br /> M1.6 ATTIC PLAN <br /> AND ABBREVIATIONS <br /> FOR M2.1 ENLARGED PLANS <br /> SUPPLYAND OUTDOORS 8 MECHANICALLY SHEET NUMBER <br /> RETURN AIR M2.2 ENLARGED PLANS <br /> COOLED <br /> M2.3 ENLARGED PLANS <br /> o_ SUPPLYAIR<55 FOR 0 . <br /> CONDITIONED SPACE 3.3 MECHANICALLY M3.1 SCHEMATIC DIAGRAMS <br /> OR>105 DEG F COOLED M3.2 DETAILS AND DIAGRAMS <br /> E6.PRaEc.N° SHEET 2 OF 15 <br /> N <br /> O <br /> f� <br />