Laserfiche WebLink
BOGARD I PASCUA <br /> ENGINEERS,PS <br /> EXHAUST FAN DEMOLITION SCHEDULE <br /> `' CONSULTING ENGINEERS <br /> 22121 t]ih Avanua SE,S"Xe tit <br /> Bdhal,WasFinAlon 90021 <br /> PERFORMANCE ELECTRICAL BACKDRAFT WEIGHT CONTROLS/ ROOF CAP NOTES zsalsBlw <br /> TAG APPLICATION MANUFACTURER MODEL TYPE AIRFLOW STATIC PRESSURE <br /> CFM IN WG RPM WATTS/HP VOLTAGE PHASES DAMPER (POUNDS) INTERLOCK <br /> EF-1 RESTROOMS 113,114,115 PENN Z14 INLINE 1065 0.50 1980 1/2 HP 120 1 YES - EMS SYSTEM CF <br /> EF-2 MEN 1671 WOMEN 168 PENN Z121 INLINE 940 0.375 1150 296 WATTS 120 1 YES 50 EMS SYSTEM SL30wB�C9p <br /> s <br /> EF-3 STORAGE 163 PENN Z12 CEILING 580 0.50 1150 265 WATTS 120 1 YES 50 EMS SYSTEM SL30 z <br /> EF-4 WOMEN 156/MEN 158 PENN Z14 INLINE 945 0.50 980 112 HP 120 1 YES - EMS SYSTEM CF <br /> EF-5 DRESSING 154/155 PENN Z12 CEILING 550 0.40 1150 265 WATTS 120 1 YES 50 EMS SYSTEM SL30 <br /> O FGISTER �1� <br /> EF-6 MECHANICAL 151 PENN Z10 CEILING 345 0.40 1000 130 WATTS 120 1 YES 35 EMS SYSTEM SL20 eSSIONAL eN� <br /> EF-7 STORAGE147 PENN Z10 CEILING 350 0.40 1000 130 WATTS 120 1 YES 36 EMS SYSTEM SL20 <br /> EF-8 INSTRUMENT STORAGE 128 PENN Z12 CEILING 650 0.40 1150 265 WATTS 120 1 YES 50 EMS SYSTEM SL30 <br /> EF-9 JANITOR 136 PENN Z8 CEILING 90 0.375 1035 105 WATTS 120 1 YES 22 EMS SYSTEM SL20 <br /> EF-10 STORAGE 125 PENN Z12 CEILING 550 0.40 1150 265 WATTS 120 1 YES 50 EMS SYSTEM SL30 <br /> EF-11 KITCHEN FRYERS PENN FX16B ROOF 2500 1.33 1140 1-1/2 HP 208 3 YES - INTERLOCK WITH HOOD <br /> EF-12 COOKING LINE PENN FX24B ROOF 5000 1.33 880 2 HP 208 3 YES - INTERLOCK WITH HOOD <br /> EF-13 WORKROOM PENN Z81 CEILING 140 0.50 1115 124 WATTS 120 1 YES 22 EMS SYSTEM SL20 <br /> EF-14 STUDENT STORE PENN Z81 CEILING 140 0.50 1115 124 WATTS 120 1 YES 22 EMS SYSTEM SL20 <br /> TF-1 KITCHEN PENN CENTREX SX275BA TRANSFER 7600 0.75 675 3 HP 208 3 YES 460 INTERLOCK WITH FANS 11 AND 12 <br /> FAN SCHEDULE N <br /> TAG MAKE MODEL SERVICE CONFIGURATION DRIVE FLOW(CFM) ESP(IN FAN RPM ELECTRICAL SOUND WEIGHT rr� <br /> WG) VOLTS/PH MCA MOCP BHP/HP PRESSURE LBS �• rn <br /> EF-1 PENNBARRY Z14 RESTROOMS 113 114 115 INLINE DIRECT 785 0.625 1179 120/1 8.00 15 0.15/l/2 52 65 O <br /> EF-2 PENNBARRY Z121 MEN 167/WOMEN 168 INLINE DIRECT 790 0.625 1438 120/1 4.00 15 0.14/l/4 56 50 U Q N <br /> EF-3 PENNBARRY Z121 STORAGE 163 CEILING DIRECT 580 0.50 1333 120/1 4.10 15 151 WATTS 7.5 SONES 50 a Q ':7, <br /> EF-4 PENNBARRY Z14 WOMEN 156/MEN 158 INLINE DIRECT 945 0.50 1189 120/1 - - 0.15/l/2 6.4 SONES 60 ti <br /> EF-5 PENNBARRY Z121 DRESSING 154/155 CABINET DIRECT 550 0.40 1349 120/1 3.30 15 263 WATTS 1.3 SONES 50 c O <br /> EF-6 PENNBARRY Z10 MECHANICAL 151 CEILING DIRECT 345 0.40 1396 120/1 1.50 15 80 WATTS 6.0 SONES 35 <br /> EF-7 PENNBARRY Z10 STORAGE 147 CEILING DIRECT 350 0.40 1407 120/1 1.50 15 83 WATTS 6.0 SONES 36 Q O <br /> EF-8 PENNBARRY Z121 INSTRUMENT STORAGE 128 CEILING DIRECT 650 0.40 973 120/1 3.30 15 351 WATTS 6.5 SONES 50 <br /> EF-9 PENNBARRY Z8 JANITOR 136 CEILING DIRECT 90 0.375 887 120/1 0.29 15 6 WATTS 1.5 SONES 22 0 0 <br /> EF-10 PENNBARRY Z12 STORAGE 125 CEILING DIRECT 550 0.40 1362 120/1 3.30 15 348 WATTS 5.0 SONES 50 <br /> EF-11 PENNBARRY FX-16B KITCHEN FRYERS ROOFTOP UPBLAST BELT 2500 1.33 1361 208/3 6.50 15 0.93/1-1/2 HP 69 140 U <br /> EF-12 PENNBARRY FX-24B COOKING LINE ROOFTOP UPBLAST BELT 5000 1.33 1043 208/3 7.50 15 1.98/2 70 235 <br /> EF-13 PENNBARRY Z81 WORKROOM CEILING DIRECT 140 0.50 873 120/1 0.46 15 45 WATTS 10 SONES 35 u <br /> EF-14 PENNBARRY Z81 STUDENT STORE CEILING DIRECT 140 0.50 873 120/1 0.46 15 45 WATTS 10 SONES 35 <br /> TF-1 PENNBARRY CENTREXSQX270-0091 KITCHEN INLINE DIRECT 7600 0.75 1770 208/3 - 2.38/3 75 214 E- <br /> Hx wH <br /> HEATING WATER BOILER DEMOLITION SCHEDULE Q o <br /> CAPACITY MIN PERFORMANCE CONNECTION HE SIZES 60 HERTZ ELECTRICAL 0 <br /> W <br /> TAG MANUFACTURER MODEL LOCATION ACCESSORIES/REMARKS <br /> DELTA PFT W W <br /> GALLONS GPM DELTAT TA ( INPUT(MBH) EFFICIENCY(%) CW HW GAS VENT VOLT PH MOCP <br /> B-1 BURNHAM PF-513 MECH ROOM 20 2655 FORCED DRAFT 3 3 1 112 14 208 3 15 CAST IRON SECTIONAL U <br /> HEATING WATER BOILER SCHEDULE <br /> CAPACITY MIN PERFORMANCE CONNECTION SIZES(INCHES) 60 HERTZ ELECTRICAL OPERATING NOTES <br /> TAG MANUFACTURER MODEL LOCATION WEIGHT ACCESSORIES/ COMMENTS <br /> (FT H2O) (MBH) (%) <br /> GALLONS GPM DELTAT DELTA INPUT EFFICIENCY CW HW GAS VENT VOLT PH MCA MOCP (LBS) REMARKS <br /> B-1 LOCHINVAR CREST FBN1251 MECH ROOM 87.0 120 20 10 1250 96 3 3 1 112 6"IN&8"OUT 208 3 <9 15 1975 20 TO l TURNDOWN EXTERIOR DIMS ARE 30x56.5x78H 1 THRU 4 <br /> B-2 LOCHINVAR CREST FBN1251 MECH ROOM 87.0 120 20 10 1250 96 3 3 1 1/2 6"IN&8"OUT 208 3 <9 15 1975 20 TO 1 TURNDOWN EXTERIOR DIMS ARE 30x56.5x78H 1 THRU 4 <br /> NOTES: <br /> 1 PROVIDE WITH RELIEF VALVE SET TO 125 PSI. <br /> 2 REFER TO PIPING SCHEMATICS AND TYPICAL INSTALLATION DETAIL. <br /> 3 PROVIDE WITH NEUTRALIZATION OF THE CONDENSATE DRAIN. <br /> 4 PROVIDE MANIFOLDED BOILERS WITH MANUFACTURER'S REQUIRED CONTROLS FOR SEQUENCING THEIR OPERATIONS,INCLUDING LEAD AND LAG CONTROLS. <br /> PROJ.NO: 21015.00 <br /> ORAWN BY: - <br /> EXPANSION TANK SCHEDULE COOLING TOWER DEMOLITION SCHEDULE CHECKED BY:LWB <br /> MAKE AND CAPACITY ACCEPTANCE CHARGE MAX SIZE(INCHES) MAX WEIGHTS(POUNDS) 60 HERTZ ELECTRICAL DATE: FEB 3,2023 <br /> FAN OPERATING REMSIONs REVISION/ISSUE DATE <br /> TAG MODEL SERVICE TYPE (GALLONS) (GALLONS) (PSIG) DIAMETER LENGTHORHT EMPTY OPERATIONAL NOTES TAG MANUFACTURER MODEL DESCRIPTION PUMP ACCESSORIES/REMARKS <br /> VOLT pH HEATER WITH MOTOR MCA MOCP WEIGHT(CBS) BID SET <br /> XT-1 AMTROL EXTROLAX-80V HYDRONIC IN-LINE 44.4 22.6 12 24 29 167 355 1 AND 2 (KW) VFD <br /> NOTES: (HP) (HP) <br /> CT-1 BALITMORE AIR COIL(BAC) VTL-152-M LOW PROFILE OPEN CIRCUIT COOLING TOWER 460 3 7 20 5 6600 <br /> 1 EXPANSION TANKS SHALL BE PROVIDED ON ALL HOT WATER SYSTEMS WITH A CHECK VALVE AS REQUIRED BY 2018 UPC SECTION 608.3. <br /> 2 ALL TANKS SERVING CLOSED SYSTEMS WITH OPERATING PRESSURES>30 PSI(69.3'WG)SHALL BE ASME TYPE AS REQUIRED BY 2018 IMC SECTION 1009.2. <br /> FLUID COOLER SCHEDULE <br /> ASHRAE MIN PERFORMANCE CONNECTION SIZES(INCHES) 60 HERTZ ELECTRICAL NOTES <br /> TAG MANUFACTURER MODEL DESCRIPTION CENTRIFUGAL FAN NOISE AT OPERATING ACCESSORIES/REMARKS <br /> AIRFLOW(CFM) 5'(DBA) 90.1RATING HEAT REJECTION MIN DESIGN EWT LWT WB PRESSURE CWS/C MAKEUP OVERFLOW DRAIN VOLT PH HEATER FAN WITH VFD PUMP MCA MOCP WEIGHT(LBS) <br /> (MBH) GPM GPM (°F) (°F) (°F) DROP(PSI) WR WATER (KW) (HP) MO TOR <br /> FC-1 BALITMORE AIR COIL(BAC) VXF-0812A-20D-M CLOSED CIRCUIT COOLING TOWER 64,110 84 25.4 1,454 125 300 85 75 68 16.0 4 1 1/2 3 2 460 3 8 20 5 15,762 UNIT DIM:8'-6"Wx 12'-O'L x 1Z-6"H 1TO4 <br /> NOTES: <br /> 1 PROVIDED WITH THE MANUFACTURER'S STANDARD ALL G235 GALVANIZED STEEL CONSTRUCTION. <br /> 2 PROVIDE WITH MECHANICAL VIBRATION SWITCH,FLOAT WATER LEVEL CONTROLLER,ELECTRIC BASIN HEATER WITH CONTROLLER AND VARIABLE SPEED DRIVE ON FAN. <br /> 3 THERMAL PERFORMANCE PER CTI TEST PROCEDURE=14.9 GPM/HP.(BASED ON EWT=102,LWT=90 AND WB=75.) <br /> 4 REFER TO PIPING SCHEMATICS FOR ADDITIONAL DETAIL. <br /> NON-POTABLE AND SANITARY WASTE AND VENT PIPE MATERIALS SCHEDULE <br /> NOTES: 1. INSULATE PIPES PER 2018 STATE ENERGY CODE. SHEET TITLE <br /> 2 HEAT TRACE PIPES IN UNCONDITIONED SPACES. EQUIPMENT <br /> 3. ALL PIPING SHALL BE NSF-61 CERTIFIED. <br /> SCHEDULES <br /> PIPE ID SERVES PIPE SIZE PIPE MATERIAL NOTES <br /> SHEET NUMBER <br /> CW,NP ABOVE GROUND 2"&SMALLER COPPER TUBE TYPE L ASTM B88 <br /> SANITARY VENT ABOVEGROUND ALL SIZES ASS PIPE:ASTM D2751,SDR35,BELL AND SPIGOT,SOLVENT SEALED ENDS. M0 . 3 <br /> SANITARYWASTE ABOVEGROUND ALL SIZES ABS PIPE:ASTM D2751,SDR35,BELL AND SPIGOT,SOLVENT SEALED ENDS. <br /> N SANITARY WASTE UNDERGROUND ALL SIZES ABS PIPE:ASTM D2751,SDR35,BELL AND SPIGOT,SOLVENT SEALED ENDS. <br /> EATaRaECTN" SHEET 4 OF 15 <br /> N <br /> O <br /> f� <br />