Panel DP2A-EXISTING PANEL SCHEDULE PROJECT: CASCADE HIGH SCHOOL Panel DP2A-REVISED PANEL SCHEDULE PROJECT: CASCADE HIGH SCHOOL -BOGARD I PASCUA
<br /> 277/48OV,3Ph,4W. 100A Bus IDEA M.C.B. SURFACE MOUNTED lfeb-23 277/48OV,3Ph,4W. 100A Bus 100A M.C.B. SURFACE MOUNTED lfeb-23 ,3 ENGINEERS,PS
<br /> Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description Ckt. Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description Ckt ` CONSULTING ENGENEERS
<br /> No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No. No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No. 221210NA-SE,Sulb1T1
<br /> '
<br /> 1 HP-23 1,050 M 20 2 A 20 1 200 H UH-1 2 1 HP-23 1,924 M 20 2 A 20 1 200 H UH-1 2 DETAIL NOTES I26♦15541a0
<br /> 3 1,050 M B 20 1 864 M UH,WH IGN&CIRC PUMP 4 3 1,924 M B 20 1 864 M UH,WH IGN&CIRC PUMP 4
<br /> 5 HP-17 450 M 20 2 C 20 1 6DO R REC-ATTIC NE 6 5 HP-17 374 M 20 2 C 20 1 600 R REC-ATTIC NE 6 D
<br /> 1 REPLACE EXISTING CIRCUIT BREAKER WITH NEW.MATCH TYPE AND
<br /> 7 -- 000 M - - A 20 1 1,000 M SS-BOILER
<br /> 8 7 - 374 - - - A 20 1 1,920 M BOILER
<br /> 8 AIC RATING.FIELD VERIFY.
<br /> 9 SPACE 1,000 20 1 B 20 3 1,000 WH BOILER BI 10 9 SPACE 1,000 - 20 1 B 20 3 1,080 WH BOILER BI 10
<br /> 11 DRESS 154,155 600 R 20 1 C - - 1,000 WH - 12 11 DRESS 154,155 600 R 20 1 C - - 1,080 WH - 12 D PROVIDE NEW CIRCUIT BREAKER.MATCH TYPE AND AIC RATING Y A.
<br /> 13 REC-CLASSRM 209 1,200 R 20 1 A - - 1,000 WH - 14 13 1 REC-CLASSRM 209 1,200 R 20 1 A - - 1,080 WH - 14 WITH PANEL.FIELD VERIFY. .v��ypgyTGJ�
<br /> 15 REC-CLASSRM 209 1,200 R 20 1 B 20 1 1,920 G RP-2,RP3 16 15 REC-CLASSRM 209 1,200 R 20 1 B 20 1 1,920 G RP-2,RP3 16 51' • 'It?T
<br /> 17 REC-CLASSRM 209 1,2001 R 20 1 1 C 20 1 - R EMS 18 17 REC-CLASSRM 209 1,200 R 20 1 C 20 1 1 - R lEMS 18
<br /> 19 REC-CLASSRM209 1,200 R 20 1 A 20 1 1,200 R REC-ROOM 212 20 19 REC-CLASSRM209 1,200 R 20 1 A 20 1 1,200 R REC-ROOM 212 20 LQ
<br /> 21 REC-CLASSRM 209,EF-5 1,200 R 20 1 B 20 1 1,200 R REC-ROOM 212 22 21 REC-CLASSRVI 209,EF-5 1,202 R 20 1 B 20 1 1,200 R REC-ROOM 212 22
<br /> 23 BLACKBOX 800 R 20 1 C 20 1 1,2DO R REC-ROOM 212 24 1 23 BLACKBOX 800 R 20 1 C 20 1 1,200 R REC-ROOM 212 24
<br /> 25 BLACKBOX 1,000 R 20 1 A 20 1 1,2DO R REC-ROOM 212 26 25 BLACKBOX 1,000 R 20 1 A 20 1 1,200 R REC-ROOM 212 26
<br /> 27 BLACKBOX 800 R 20 1 B 20 1 1,200 R REC-ROOM 212 28 27 BLACKBOX 800 R 20 1 B 20 1 1,200 R REC-ROOM 212 28 d
<br /> 29 STOR 151,EF-6,UTIL,151A 1,000 R 2D 1 C 2D 1 1,200 R REC-ROOM 212 30 29 STOR 151,EF-6,UTIL,151A 950 R 20 1 C 20 1 1,200 R REC-ROOM 212 30
<br /> 31 CHOIR(WEST),EF-7 1,000 R 2D 1 A 2D 1 1,200 R REC-ROOM 212 32 31 CHOIR(WEST),EF-7 953 R 20 1 A 20 1 1,200 R REC-ROOM 212 32
<br /> 33 CHOIR(EAST) 1 1,200 R 20 1 B 20 1 1,200 R REC-ROOM 212 34 33 ICHOIR(EAST) 1 1,200 R 20 1 1 B 20 1 1,200 R REC-ROOM 212 34
<br /> 35 COOLING TOWER 1,920 R 20 1 C 20 1 1,200 R REC-ROOM 212 38 35 COOLING TOWER 1,920 R 20 1 C 20 1 1,200 R REC-ROOM 212 38
<br /> 37 REC-ROOM 212 1,200 R 20 1 A 20 1 1,200 R REC-ROOM 212 38 37 REC-ROOM 212 1,200 R 20 1 A 20 1 1,200 R REC-ROOM 212 38
<br /> 39 REC-ROOM 212 1 1,2001 R 1 20 1 1 B 1 20 1 1 1 1,200 I R I REC-ROOM 212 40 39 1 REC-ROOM 212 1 ,200 R 1 20 1 B 20 1 1,200 R REC-ROOM 212 40
<br /> 41 REC-ROOM 212 1,200 R 20 1 C 20 1 1,200 R REC-ROOM 212 42 41 REC-ROOM 212 1,200 R 20 1 C 20 1 1,200 R REC-ROOM 212 42
<br /> I
<br /> Total Connected Load: Ph A 15,020 VA 54 A Total Connected Load: Ph A 15,851 VA 57 A
<br /> Total Connected Load: Ph B 16,234 VA 59 A Total Connected Load: Ph B 17,190 VA 62 A Electrical Consultants,Inc
<br /> Total Connected Load: Ph C 13,570 VA 49 A Total Connected Load: Ph C 13,524 VA 49 A LOAD INCREASE: 19015 36th Avenue West,Suite E
<br /> Total Connected Load: 44.8 KVA Total Demand Load: 33.1 KVA Total Connected Load: 46.6 KVA Total Demand Load: 35.0 KVA 1,849 VA Lynnwood,Washington 98036
<br /> 53.9 AMPS 39.8 AMPS 56.0 AMPS 42.1 AMPS 2AMPS
<br /> Phone(425)775-1799 FAX(425)774-98�
<br /> Connected Subfed Total Demand Demand Connected Subfed Total Demand Demand
<br /> Loads Loads(S) Loads Factor Load Loads Loads(S) Loads Factor Load
<br /> G General(Non-Continuous) 1,920 1.920 100% 1.920 G General(Non-Continuous) 1,920 1,920 100% 1.920
<br /> L Lighting 0 0 125% 0 L Lighting 0 0 125% 0
<br /> R Receptacles-to 10 KVA 32,920 10,000 100% 10,000 Accessories: R Receptacles-to 10 KVA 32,825 10,000 100% 10,000 Accessories:
<br /> ver 10 KVA 22,920 50% 11,460 ver 10 KVA 22,825 50% 11,413 N
<br /> K Kitchen 0 0 100% 0 K Kitchen 0 0 100% 0
<br /> H Heating 200 200 100% 200 H Heating 200 200 100% 200
<br /> M Motors 5,784 5,784 100% 5,784 M Motors 7,380 7,380 100% 7,380
<br /> LM Largest Motor 0 0 125% 0 LM Largest Motor 0 0 125% 0
<br /> WA Water Heater 3,000 3,000 125% 3,750 NH Water Heater 3,240 3,240 125% 4,050 ^
<br /> C Continuous General Load 0 0 125% 0 C Continuous General Load 0 0 125% 0 121
<br /> 43,824 VA 0 VA 43,824 VA 33,114 VA 45,565 VA O VA 45,565 VA 34,963 VA 1 W
<br /> Panel LP1 -EXISTING PANEL SCHEDULE PROJECT: CASCADE HIGH SCHOOL Panel LP1 -REVISED I PANEL SCHEDULE PROJECT: CASCADE HIGH SCHOOL Q Q FQL�
<br /> 277/48OV,3Ph,4W. 400A Bus M.L.O. SURFACE WALL MOUNTED 1-Feb-23 277/48OV,3Ph,4W. 400A Bus M.L.O. SURFACE WALL MOUNTED 1feb-23
<br /> Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description/ Ckt. Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description/ Ckt. U
<br /> No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No. No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No.
<br /> 1 LTG-LIBRARY NORTH 2,604 L 20 1 A 20 1 L LTG-EXTERIOR 2 1 LTG-LIBRARY NORTH 2,604 L 20 1 A 20 1 L LTG-EXTERIOR 2
<br /> 3 LTG-LIBRARY SOUTH 2,790 L 20 1 B 20 1 L LTG-EXTERIOR 4 3 LTG-LIBRARY SOUTH 2,790 L 20 1 B 20 1 L LTG-EXTERIOR 4
<br /> 5 LTG-LIBRARY COVE 3,720 L 20 1 C 20 1 SPARE 6 5 LTG-LIBRARY COVE 3,720 L 20 1 C 15 3 1,038 WH BOILERB2 6 2 y�L4 F+i
<br /> 7 LTG-LIBRARY OFFICES 3,348 L 20 1 A 20 1 SPARE 8 7 LTG-LIBRARY OFFICES 3,348 L 20 1 A - - 1,038 WH -- 8
<br /> 9 LTG-CORRIDOR 111,112,159,160 2,822 L 20 1 B 20 1 SPARE 10 9 LTG-CORRIDOR 111,112,159,160 2,822 L 20 1 B - - 1,038 WH -- 10
<br /> 11 SPARE 20 1 C 20 1 SPARE 12 11 SPARE 20 1 C 20 1 SPARE 12 II--I41
<br /> 13 LTG-FACULTY,REST,ELEC 1,953 L 20 1 A 20 1 SPARE 14 13 LTG-FACULTY,REST,ELEC 1,953 L 20 1 A 20 1 SPARE 14
<br /> 15 LTG-KITCHEN 2,556 L 20 1 B 20 1 SPARE 16 15 LTG-KITCHEN 2,556 L 20 1 B 20 1 SPARE 16 W rfl ry
<br /> 17 LTG-CLASSROOM 209,RESTRM 1,736 L 20 1 C 20 1 1 1 SPARE 18 17 LTG-CLASSROOM 153,RESTRM 1,736 L 20 1 1 C 20 1 1 SPARE 18 ^ w Q
<br /> 19 SPARE 20 1 A 20 1 SPARE 20 19 SPARE 20 1 A 20 1 SPARE 20 00
<br /> 21 LTG-CLASS 119,STOR 117 1,767 L 20 1 B 20 1 SPARE 22 21 LTG-CLASS 119,STOR 117 1,767 L 20 1 B 20 1 SPARE 22
<br /> 23 SPARE 20 1 C 20 1 SPARE 24 23 SPARE 20 1 C 20 1 SPARE 24 r
<br /> 25 SPARE 20 1 A 20 1 SPARE 26 25 SPARE 20 1 A 20 1 SPARE 26 �•/
<br /> 27 LTG-ATTIC 1,216 L 20 1 B 20 1 SPARE 28 27 LTG-ATTIC 1,216 L 20 1 B 20 1 SPARE 28
<br /> 29 LTG-VESTIBULE 3,015 L 20 1 C 20 1 SPARE 30 29 LTG-VESTIBULE 3,015 L 20 1 C 20 1 SPARE 30
<br /> 31 LTG-CORRIDOR 1,906 L 20 1 A 50 3 1,560 SL PANEL CP1()FMR 11 32 31 LTG-CORRIDOR 1,906 L 20 1 A 50 3 1,560 SL PANEL CP1()FMR 11 32 r 1
<br /> 33 PANEL DPIA(XFMR TIA) 3,552 SL 100 3 B 1,949 SL - 34 33 PANEL OPIA(FMR T1A) 3,494 SL 100 3 IS 1,949 SL - 34 V
<br /> 35 - 2,123 SL C 1,819 SL - 38 35 - 2,123 SL - - C 1,819 SL - 36
<br /> 37 - 3,899 SL A 200 3 21,949 SL PANELADP(XFMRTI) 38 37 - 3,899 SL A 200 3 20,980 SL PANEL ADP()FMRT1) 38
<br /> 39 SPACE B 25:'9 SL 40 39 SPACE B 22,631 SL 40
<br /> 41 SPACE C 21,939 SL 42 41 SPACE C 21,012 SL 42
<br /> Total Connected Load: Ph A 37,219 VA 134 A Total Connected Load: Ph A 37,287 VA 135 A
<br /> Total Connected Load: Ph B 40,045 VA 145 A Total Connected Load: Ph B 40,253 VA 145 A
<br /> Total Connected Load: Ph C 34,352 VA 124 A Total Connected Load: Ph C 34,463 VA 124 A LOAD INCREASE:
<br /> Total Connected Load: 111.6 KVA Total Demand Load: 36.8 KVA Total Connected Load: 112.0 KVA Total Demand Load: 40.7 KVA 3,893 VA
<br /> 134.3 AMPS 44.3 AMPS 134.7 AMPS 48.9 AMPS 5 AMPS
<br /> Connected Subfed Total Demand Demand Connected Subfed Total Demand Demand
<br /> Loads Loads(S) Loads Factor Load Loads Loads(S) Loads Factor Load
<br /> G General(Non-Continuous) 0 0 0 100% 0 G General(Non-Continuous) 0 0 0 100% 0
<br /> L Lighting 29,433 0 29,433 125% 36,791 L Lighting 29,433 0 29,433 125% 36,791
<br /> R Receptacles-to10KVA 0 0 0 100% 0 Accessories: R Receptacles-to 10 KVA 0 0 0 100% 0 Accessories:
<br /> over 10 KVA 0 0 50% 0 ver 10 KVA 0 0 50% 0
<br /> K Kitchen 0 0 0 100% 0 K Kitchen 0 0 0 100% 0
<br /> H Heating 0 0 0 100% 0 H Healing 0 0 0 100% 0
<br /> M Motors 0 0 0 100% 0 M Motors 0 0 0 100% 0
<br /> LM Largest Motor 0 0 0 125% 0 LM Largest Motor 0 0 0 125% 0
<br /> V%H Water Heater 0 0 0 125% 0 W-1 Water Heater 3,114 0 3,114 125% 3,893 P80ANo. 21015.00
<br /> C Continuous General Load 0 0 0 125% 0 C Continuous General Load 0 0 0 125% 0
<br /> 29,433 VA 0 VA 29,433 VA 36,791 VA 32,547 VA 0 VA 32,547 VA 40,684 VA oRAWN By: LRD
<br /> ciiecm By,BA
<br /> BATE 08-30-2022
<br /> mvlBlo a REVISION I ISSUE DATE
<br /> Panel DP1A-EXISTING PANEL SCHEDULE PROJECT: CASCADE HIGH SCHOOL Panel DP1A-REVISED PANEL SCHEDULE PROJECT: CASCADE HIGH SCHOOL 0
<br /> 120/208V,3Ph,4W. 200A Bus M.L.O. SURFACE WALL MOUNTED 1feb-23 120(208V,3Ph.4W. 200A Bus M.L.O. SURFACE WALL MOUNTED 1feb-23
<br /> Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description/ Ckt. Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description/ Ckt. Q
<br /> No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No. No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No.
<br /> 1 REC-OFFICE 120,121 600 R 20 1 A 20 1 400 R REC-LIB.CIRCULATION 101 2 1 REC-OFFICE 120,121 600 R 20 1 A 20 1 400 R REC-LIB.CIRCULATION 101 2 Q
<br /> 3 REC-CLASSROOM 119 1,000 R 20 1 B 20 1 400 R REC-LIB.CIRCULATION 152 4 3 REC-CLASSROOM 119 1,000 R 20 1 B 20 1 400 R REC-LIB.CIRCULATION 102 4
<br /> 5 REC-CLASSROOM 119 600 R 20 1 C 20 1 400 R REC-LIB.CIRCULATION 103 6 5 REC-CLASSROOM 119 600 R 20 1 C 20 1 400 R REC-LIB.CIRCULATION 103 6
<br /> 7 REC-STORE 116 1,000 R 20 1 A 20 1 600 R REC-LIB.WORK 103 8 7 REC-STORE 116 1,000 R 20 1 A 20 1 600 R REC-LIB.WORK 103 8
<br /> 9 REC-STORE 116,EF-14 1,000 R 20 1 B 20 1 600 R REC-LIB.WORK 104 10 9 REC-STORE 116,EF-14 921 R 20 1 B 20 1 600 R REC-LIB.WORK 104 10
<br /> 11 SPARE 20 1 C 20 1 1400 R REC-PATCH 109,CONTROL 110 12 11 SPARE 20 1 C 20 1 1400 R REC-PATCH 109,CONTROL 110 12
<br /> 13 IREC-RESTROOM,ELEC RM 800 R 1 20 1 1 A 20 1 1200 R REC-CONF 108,PATCH 109 14 13 REC-RESTROOM,ELEC RM 800 R 20 1 A 20 1 12DO R REC-CONF 108,PATCH 109 14
<br /> 15 REC-RESTROOM,ROOM 112 800 R 20 1 B 20 1 600 R REC-VESTIBULE 16 15 REC-RESTROOM,ROOM 112 800 R 20 1 B 20 1 600 R REC-VESTIBULE 16
<br /> 17 RR1 CIRC PUMP 20 1 C 1 20 1 SPARE 18 17 RR1 CIRC PUMP 1 20 1 1 C 20 1 SPARE 18
<br /> 19 REC-MEDIA 105,CONF 106 800 R 20 1 A 20 1 1000 R REC-ATTIC SW 20 19 REC-ME DIA 105,CONF 106 800 R 20 1 A 20 1 1000 R REC-ATTICSW 20
<br /> 21 REC-PER 104,WORK 103,EF-13 800 R 20 1 B 20 1 SPARE 22 21 REC-PER 104,WORK 103,EF-13 721 R 20 1 B 20 1 SPARE 22
<br /> 23 REC-OFFICE 102,MEDIA 105 1,000 R 20 1 C 20 1 SPARE 24 23 REC-OFFICE 102,MEDIA 105 1,000 R 20 1 C 20 1 SPARE 24
<br /> 25 REC-LIBRARY 1,600 R 20 1 A 20 1 EMS CONTROL 26 25 REC-LIBRARY 1,600 R 20 1 A 20 1 EMS CONTROL 26
<br /> 27 REC-FRONT ENTRY 200 R 20 1 B 20 1 SPARE 28 27 REC-FRONT ENTRY 200 R 20 1 B 20 1 SPARE 28
<br /> 29 MISC-INSTA-HOT,STORE 116 750 G 20 1 C 20 1 750 MISC-HANDICAP DOORS 30 29 MISC-INSTA-HOT,STORE 116 750 G 20 1 C 20 1 750 MISC-HANDICAP DOORS 30
<br /> 31 MISC-SECURITY GATE 1,000 G 20 1 A 20 1 SPARE 32 31 MISC-SECURITY GATE 1,000 G 20 1 A 20 1 SPARE 32
<br /> 33 MISC-POP MACH.,STORE 1,000 G 20 1 B 20 1 1800 MISC-MOTORIZED SHADES-CAF. 34 33 MISC-POP MACH.,STORE 1,000 G 20 1 B 20 1 1800 MISC-MOTORIZED SHADES-CAF. 34
<br /> 35 SPARE 20 1 C 20 1 SPACE 36 35 SPARE I 2D 1 C 20 1 SPACE 36
<br /> 37 SPACE A 1 SPACE 38 37 SPACE A 20 1 SPACE 38
<br /> 39 SPACE B 20 SPACE 40 39 SPACE B SPACE 40
<br /> 41 SPACE C I ISPACE 42 41 SPACE C 1 SPACE 42
<br /> Total Connected Load: Ph A 9,000 VA 75 A Total Connected Load: Ph A 9,000 VA 75 A
<br /> Total Connected Load: Ph B 8,200 VA 68 A Total Connected Load: Ph B 8,042 VA 67 A
<br /> Total Connected Load: Ph C 4,900 VA 41 A Total Connected Load: Ph C 4,900 VA 41 A LOAD DECREASE:
<br /> Total Connected Load: 22.1 KVA Total Demand Load: 16.2 KVA Total Connected Load: 21.9 KVA Total Demand Load: 16.1 KVA 79 VA
<br /> 61.4 AMPS 44.9 AMPS 61.0 AMPS 44.6 AMPS 0.22 AMPS
<br /> SHEET TITLE
<br /> Connected Subfed Total Demand Demand Connected Subtad Total Demand Demand
<br /> Loads Loade(S) Loads Factor Load Loads Loads(S) Loads Factor Load PANEL SCHEDULES
<br /> G General(Non-Continuous) 2,750 0 2,750 100% 2,750 G General(Non-Continuous) 2,760 0 2,750 100% 2,750
<br /> L Lighting 0 0 0 125% 0 L Lighting 0 0 0 125% 0
<br /> R Receptacles-to10KVA 16,800 0 10,000 100% 10,000 Accessories: R Receptacles-to 10 KVA 16,642 0 10,000 100% 10,000 Accessories:
<br /> over 10 KVA 0 6,800 50% 3,400 ver 10 KVA 0 6,642 50% 3,321
<br /> K Kitchen 0 0 0 100% 0 K Kitchen o 0 0 100% o SHEET NUMBER
<br /> H Heating 0 0 0 100% 0 H Heating 0 0 0 100% 0
<br /> M Motors 0 0 0 100% 0 M Motors 0 0 0 100% 0
<br /> LM Largest Motor 0 0 0 125% 0 LM Largest Motor 0 0 0 125% 0
<br /> VW Water Heater 0 0 0 125% 0 WH Water Heater 0 0 0 125% 0
<br /> C Continuous General Load 0 0 0 125% 0 C Continuous General Load 0 0 0 125% 0
<br /> 19,550 VA 0 VA 19,550 VA 16,150 VA 19,392 VA O VA 19,392 VA 16,071 VAE21