Laserfiche WebLink
Seatronics, Inc. Boeing 40-81/82 Yard Tunnel Section 1 <br /> Job: Fire Alarm System Submittal Manual Page 2 <br /> SYSTEM SEQUENCE OF OPERATION <br /> 1. ALARM CONDITIONS: <br /> 1.1 ACTIVATION OF ANY SPOT TYPE SMOKE DETECTOR, MANUAL PULL STATION OR WATER <br /> FLOW SHALL: <br /> a. CAUSE THE ALARM INDICATOR LAMP ON THE FACP TO ILLUMINATE. <br /> b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br /> c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH ALARM POINT LOCATION <br /> INFORMATION. <br /> d. DISPLAY ALARM POINT LOCATION ON THE REMOTE ANNUNCIATORS. <br /> e. CAUSE BUILDING FIRE ALARM STROBES AND HORN/STROBES TO ACTIVATE. <br /> f. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMIT AN ALARM <br /> SIGNAL TO THE TYCO CENTRAL STATION MONITORING COMPANY. <br /> 2. SUPERVISORY CONDITIONS: <br /> 2.1 ACTIVATION OF ANY FIRE SPRINKLER TAMPERS SHALL: <br /> a. CAUSE THE SUPERVISORY INDICATOR LAMP ON FACP TO ILLUMINATE. <br /> b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br /> c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH SUPERVISORY POINT <br /> LOCATION INFORMATION. <br /> d. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMIT A <br /> SUPERVISORY SIGNAL TO THE TYCO CENTRAL STATION MONITORING COMPANY. <br /> 3. FAULT/TROUBLE CONDITIONS: <br /> 3.1 CONDITIONS IN THE SYSTEM THAT MAY CAUSE FAILURE, OR IMPAIR OPERATION OF THE <br /> SYSTEM SHALL CAUSE THE FOLLOWING: <br /> a. CAUSE THE TROUBLE INDICATOR LAMP ON THE FACP TO ILLUMINATE. <br /> b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br /> c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH TROUBLE LOCATION <br /> INFORMATION. <br /> d. DISPLAY TROUBLE POINT LOCATION ON THE REMOTE ANNUNCIATORS <br /> e. TRANSMIT A TROUBLE SIGNAL TO CENTURYLINK'S REMOTE MONITORING STATION. <br /> f. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMIT A TROUBLE <br /> SIGNAL TO THE CENTRAL STATION MONITORING COMPANY. <br /> THE FOLLOWING IS AN ABBREVIATED LIST OF THE TYPES OF FAULTS THAT WILL CAUSE <br /> A TROUBLE CONDITION TO REPORT TO THE FACP. <br /> a. OPEN, SHORTED OR GROUNDED WIRING ON ANY DETECTION CIRCUIT. <br /> b. OPEN, SHORTED OR GROUNDED WIRING ON ANY MANUAL CIRCUIT. <br /> c. ANY MISSING OR REMOVED ADDRESSABLE DEVICE SUCH AS SMOKE DETECTORS, <br /> POINT MONITORING MODULES OR MANUAL STATIONS. <br /> d. OPEN, SHORTED OR GROUNDED WIRING ON ANY NAC (HORN/STROBE) CIRCUIT. <br /> e. ACTIVATION OF ANY PANEL "BYPASS" OR "OVERRIDE" FUNCTION. <br /> f. CONTROL PANEL STAND-BY BATTERY FAULT. <br /> g. LOSS OF PRIMARY 120 VAC POWER TO PANEL FOR MORE THAN 90 SECONDS. <br /> In. LOSS OF 24VDC POWER. <br /> i. FAILURE OF THE SYSTEM DIALER/COMMUNICATOR TO PROPERLY "CHECK-IN" TO THE <br /> CENTRAL STATION MONITORING COMPANY ONCE EVERY 24 HOURS OR LOSS OF <br /> EITHER OR BOTH PHONE LINES CONNECTED TO THE DIALER. <br /> Seatronics, Inc. PO BOX 1138 Auburn, WA 98001 253-939-6060 <br />