Laserfiche WebLink
Operation 2) Total current for nonresettable power, resettable power and <br /> Activation of a compatible smoke detector or any normally-open two NACs must not exceed 6.0 A for the MS-4(required optional <br /> fire alarm initiating device activates audible and visual signaling second transformer). <br /> devices, illuminates an indicating LED, sounds the piezo CABINET DIMENSIONS <br /> sounder at the FACP, activates the FACP alarm relay and oper- Door: 15.342" (38.97 cm) high x 14.667" (37.28 cm) wide x <br /> ates an optional module used to notify a remote station or initi- 0.375'(0.95 cm)deep. <br /> ate an auxiliary control function. Backbox: 15.0" (38.10 cm) high x 14.5" (36.83 cm)wide x 3.0" <br /> (7.62 cm)deep. <br /> Specifications 13ACKBOX MOUNTING <br /> AC POWER-T63 The cabinet can be surface mounted. The door is removable <br /> • MS-4: 120 VAC,50/60 Hz,2.3 A. during installation by opening and lifting it off the hinges. The <br /> • MS-4E:240 VAC,50 Hz, 1.15 A. cabinet mounts using two key slots at the top of the backbox and <br /> • Wire Size: Minimum 14 AWG(2.0 mm2)with 600 V insulation. two additional 0.25"diameter holes at the bottom. <br /> BATTERY(SEALED LEAD-ACID ONLY)-JS <br /> • Maximum charging circuit: normal flat charge 27.6 VCD @ Listings and Approvals <br /> 0.8 A. • UL Listed: S624 <br /> • Maximum battery charger capacity: 18.0 AH battery (two • MEA:297-01-E <br /> 7.0 AH batteries can be housed in the FACP cabinet. Larger • CSFM:7165-0075:200 <br /> batteries require a separate battery box such as the Fire-Lite <br /> BB-17F). Ordering Information <br /> INITIATING DEVICE CIRCUITS-T63 MS-4: Four-zone conventional FACP; 120 VAC,50/60 Hz,2.3 A. <br /> • Alarm zones 1 -4. MS-4E: Same as above,but 240 VAC,50 Hz, 1.15 A operation. <br /> • Power-limited circuitry. CAC-4: Class A converter module. Used to convert Style B <br /> • Operation:all zones Style B(Class B). (Class B) IDC to Style D(Class A)and Style Y(Class B)NAC to <br /> • Normal operating voltage:nominal 20 VDC. Style Z(Class A). The module connects to J1 on the MS-4 cir- <br /> • Alarm current: 15 mA minimum. cuit board. <br /> • Short-circuit current:40 mA maximum. 4XTMF:Transmitter module. <br /> • Maximum loop resistance: 100 ohms. 4XLMF: LED interface module. <br /> • End-of-line resistor:4.7K ohm,1/2 watt(P/N 71252). 4XZMF:Zone relay module,4 form C relay. <br /> • Standby current:4 mA. RZA:-4XF: Remote Annunciator. <br /> • Compatible devices: refer to the Fire-Lite Device Compatibil- BB-17F: Battery box, required to house two batteries greater <br /> ity Document PN 15384 for a complete list of compatible than 7 AH to a maximum of 18 AH. <br /> devices. 411/411UD: Three-input (channels) model 411, and four-input <br /> model 411UD, dual-line Digital Alarm Communicator/Transmit- <br /> NOTIFICATION APPLIANCE CIRCUITS-T132 ters (DACTs). Can be used as slave communicators with the <br /> • Two NACs. FACP. <br /> • Power-limited circuitry. DP-MS2/4:Optional dress panel. <br /> • Normal operating voltage:nominal 24 VDC. MS-4RB: Replacement board. <br /> • Maximum signalling current: 2.5 A total with standard trans- T13-1-11:Optional trim ring for semi-flush mounting. <br /> former 5.0 A total (2.5 A maximum per NAC) with optional A 2-zone version of this panel is also available.See DF-52211. <br /> transformer. <br /> • End-of-line resistor:4.7K ohm,1/2 watt(P/N 71252). <br /> • Compatible devices: refer to the Fire•Lite Device Compatibil- <br /> ity Document PN 15384 for a complete list of compatible <br /> devices. <br /> FORM-C RELAYS <br /> • Trouble Relay TB5(fail-safe). <br /> • Alarm Relay TB6. <br /> • Supervisory relay TB7. <br /> • Relay contact ratings:2.0 A @ 30 VDC(resistive). <br /> AUXILIARY OUTPUT: RESETTABLE POWER-T131 <br /> • Operating voltage: nominal 24 VDC. <br /> • Maximum available current: 500 mA-appropriate for pow- <br /> ering four-wire smoke detectors(see notes). <br /> • Power-limited circuitry. Fire-Lite®Alarms is a registered trademark of Honeywell International Inc. <br /> y @2011 by Honeywell International Inc.All rights reserved.Unauthorized use <br /> Notes: 1) Refer to the Fire•Lite Device Compatibility Document of this document is strictly prohibited. <br /> for a complete list of compatible devices. <br /> This document is not intended to be used for installation purposes. <br /> ISO 9001 <br /> We try to keep our product information up-to-date and accurate. <br /> We cannot cover all specific applications or anticipate all requirements. <br /> ENGINEERING&MANUFACTURING All specifications are subject to change without notice. <br /> QUALITY SYSTEMS Made in the U.S.A. <br /> For more information,contact Fire-Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. <br /> www.firelite.com <br /> Page 2 of 2-DF-52266:132•12/21/2012 <br />