Laserfiche WebLink
HYDRAULIC CALCULATIONS <br /> for <br /> Job Information <br /> Project Name : K&H Printing <br /> Contract No. : City: <br /> Project Location: 7720 Hardison Road Date: 12/17/2023 <br /> Contractor Information <br /> Name of Contractor: Burns Fire Protection Systems, Inc <br /> Address: P.O.B. 1110 City: Granite Falls, Wa 98252 <br /> Phone Number: 425-388=0124 E-mail: <br /> Name of Designer: D.Yates <br /> Authority Having Jurisdiction: City of Everett <br /> Design <br /> Remote Area Name 2 <br /> Remote Area Location spark system <br /> Occupancy Classification <br /> Density(gpm/ft2) 0.1 <br /> Area of Application (ft2) 0.8 <br /> Coverage per Sprinkler(ft2) 80 <br /> Number of Calculated Sprinklers 4 <br /> In-Rack Demand(gpm) 0 <br /> Special Heads <br /> Hose Streams(gpm) 0 <br /> Total Water Required(incl. Hose Streams)(gpm) 32.2 <br /> Required Pressure at Source(psi) 72.2 <br /> Type of System Wet <br /> Volume-Entire System (gal) 804.1 gal <br /> Water Supply Information <br /> Date 12/17/23 <br /> Location main drain test <br /> Source W 1 <br /> Notes <br /> File:C:\Users\yates\Documents\dwg2\burns\K&H Printing Everett\k&h Printing.dwg <br /> Date 12/18/2023 Copyright©2002-2012 Tyco Fire Protection Products Page 2 <br />