Laserfiche WebLink
TOLBraceTM Seismic Bracing Calculations V8.8.124 <br />Contractor: Viking Automatic Sprinkler C <br />Project Address: Boeing 40-36 FSI/MIC Address: 3434 1 st Avenue S <br />* <br />E <br />Seattle, WA, 98314 .y <br />3003 W Casino Rd Phone: 206-622-4656 Powering6uselessWorfdmde <br />Everett, WA Licence: VI-KI-NA-S373NT <br />Job # WSC-3046 Calculations based on 2016 NFPA Pamphlet #13 <br />Brace Information <br />TOLCOTM Brace Components <br />TOLCOTM Component Listed Load Adjusted Load <br />Maximum Brace Length 7' 0" (2.134 m) <br />Diameter of Brace 1 <br />Fig. 1001 Clamp 1640 Ibs (744 kg) 1420 Ibs (644 kg) <br />Fig.980 - 1/2" Universal SWIVE 3750 Ibs (1701 kg) 3247 Ibs (1473 kg) <br />Type of Brace Sch.40 <br />See Fastener Information <br />Angle of Brace 75° Min. <br />*Calculation Based on CONCENTRIC Loading <br />*Please <br />Note: These calculations are for TOLCOTM components only. Use of any <br />other components voids these calculations and the listing of the assembly. <br />Least Rad. of Gyration 0.42" (11 mm) <br />Seismic Brace Assembly Detail <br />L/R Value 200 <br />Max Horizontal Load 1604 Ibs (728 kg) <br />IOLCOFIO 980 <br />YBRACE <br />UwIYER5AI TTAACHMENT <br />Other Requirements - FM Approved Loads <br />BRACE PIPE <br />Fastener Information <br />Orientation to Connecting Surface NFPAType F <br />Fastener <br />Type 1/2in. Unfinished Steel Bolt <br />Diameter 1/2in. <br />Length N/A <br />Maximum Load 2850 Ibs (1293 kg) <br />01GCLAMP F°' <br />PIPE CLAMP FOR <br />SWAY BR ACING <br />Brace Identification on Plans Lat 3" <br />Prying Factor N/A <br />Brace Type Lateral [X] Longitudinal [ ] 4-Way [ ] <br />Sprinkler System Load Calculation (Fpw = CpWp) <br />C = 0.643 <br />Diameter <br />Type <br />Length <br />Total Length Weight Per Unit Length <br />Total Weight <br />3" (80 mm) <br />I Sch. 40 <br />116.563 ft (5 m) <br />116.563 ft (5 m) <br />110.82 lb/ft (16.1 kg/m) <br />179 Ibs (81 kg) <br />2" (50 mm) <br />Sch. 40 <br />199 ft (60.7 m) <br />199 ft (60.7 m) <br />5.13 lb/ft (7.63 kg/m) <br />1021 Ibs (463 kg) <br />• W.ASRINOTON STATE <br />■ <br />■ CERTIFICATE OF COMPETENCY <br />� FIRE PROTECTION SPRINKLER SYSTEMS a <br />Lucia S. Y. Fung 1-7 <br />4MW11-C LwM 3 <br />■ Ming Automatic Sprinkler Con wy ■ <br />i VIKtNAS3 NT <br />i ■ <br />r� <br />rirC ■1.= <br />b�aao�� <br />>30 HiK b. GYI�iACAT �o• a <br />3 GM�22 <br />Subtotal Weight <br />1200 Ibs (544 kg) <br />Wp (incl. 15%) <br />1380 Ibs (626 kg) <br />Main Size <br />Type/Sch. <br />Spacing (ft) <br />Total (Fpw) <br />887 Ibs (402 kg) <br />3" <br />Sch. 40 <br />16.563 <br />Maximum Fpw per 9.3.5.5.2 (if applicable) <br />1597 lb (724 kg) <br />fTOLBraceTM Version 81 Use of TOLBraceTM is subject to terms and conditions per the end user license agreement <br />