Laserfiche WebLink
Viking Automatic Sprinkler Co. <br /> 3434 1st Ave S . <br /> Seattle, WA <br /> HYDRAULIC CALCULATIONS FOR <br /> Boeing 40-81 <br /> 1000 WILLAMINA CREEK RD. , <br /> WILLAMINA, OR <br /> DRAWING NUMBER: DATE: MAR 25, 2024 <br /> -DESIGN DATA- <br /> REMOTE AREA NUMBER: REMOTE AREA LOCATION: TUNNEL EXPANSION <br /> OCCUPANCY CLASSIFICATION: LIGHT HAZARD <br /> DENSITY: 0 . 1 gpm/sq. ft . <br /> AREA OF APPLICATION: 1500 sq. ft . <br /> COVERAGE PER SPRINKLER: MAX 225 sq. ft . <br /> TYPE OF SPRINKLERS CALCULATED: SSU, K=5 . 6 <br /> NUMBER OF SPRINKLERS CALCULATED: 10 <br /> HOSE-STREAM DEMAND: 100 gpm <br /> TOTAL WATER REQUIRED (INCLUDING HOSE) : 251 . 4 gpm <br /> FLOW AND PRESSURE (AT BASE OF RISER) : 151 . 4 gpm @ 15 . 6 psi <br /> TYPE OF SYSTEM: WET PIPE SYSTEM <br /> WATER SUPPLY <br /> Source: FIRE PUMP Test Date: 12/23/2014 Test By: CONTRACTOR <br /> Location: BUILDING 40-29 <br /> Static: 67 psi Residual : 57 psi Flow: 3090 gpm <br /> Source Elevation Relative to Finished Floor Level : ft . <br /> INSTALLING CONTRACTOR <br /> Name: VIKING AUTOMATIC SPRINKLER CO. <br /> Address : 3434 1ST AVE S. , SEATTLE, WA <br /> Phone: (206) 622-4656 Certification number: VIKINAS373NT <br /> NAME OF DESIGNER: DONALD KOVAL <br /> AUTHORITY HAVING JURISDICTION: CITY OF EVERETT <br /> NOTES : <br /> Calculations performed by HASS under license # 65689119 , <br /> granted by HRS SYSTEMS, INC. <br /> (Notes continue after pipe calculations results . ) <br /> (Notes continue after pipe calculations results . ) <br /> rrrrrrrrrrrrrrrrrrrwrrrrwrrrrwrrrrrrrrrâ–  <br /> i WASHINGTON STATE <br /> r Ewplrws CERTIFICATE OF COMPETENCY <br /> DEC 31,241 FIRE SPRINKLER SYSTEMS <br /> Daniel McLuen <br /> 6676-0791-C Level3 <br /> Viking Automatic,'prinkler ompany <br /> VIKINAS373NT, <br /> y 3/26/2024 <br /> Date `r <br /> rrrrwwrrrrwrrwrrriwrrrrrrwrrrrrrrrrrwrwi <br />