Seismic Bracing <br /> TOLCOW Fig. 1001 - Sway Brace Attachment (FM Approved) <br /> Size Range: Pipe size to be braced: 1"(25mm)thru 8" (200mm) IPS. OPM FM <br /> Pipe size used for bracing: 1" (25mm)and 11/4"(32mm)Schedule 40 IPS. APPROVED <br /> Material: Steel <br /> Function: For bracing pipe against sway and seismic disturbance. <br /> The pipe attachment component of a sway brace system: <br /> Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and <br /> joined together with bracing pipe per NFPA 13, forming a complete <br /> sway brace assembly. <br /> Features: Can be used to brace schedule 7 through schedule 40 IPS. <br /> Field adjustable, making critical pre-engineering of bracing pipe <br /> length unnecessary. Unique design requires no threading of bracing <br /> pipe. Can be used as a component of a four-way riser brace. <br /> Comes assembled and ready for installation. Fig. 1001 has built-in Set Bolts <br /> visual verification of correct installation. See installation note below. Included <br /> Installation Note: Position Fig. 1001 over the pipe to be braced <br /> and tighten two hex head cone point set bolts until heads bottom <br /> out.A minimum of 1"(25mm) pipe extension is recommended. Brace pipe <br /> can be installed on top or bottom of pipe to be braced. <br /> Approvals: Approved by Factory Mutual Engineering (FM). <br /> Included in our Seismic Engineering Guidelines approved by the State of California <br /> Office of Statewide Health Planning and Development(OSHPD). For additional <br /> load, spacing and placement information relating to OSHPD projects, please refer <br /> to our Seismic Engineering Guidelines, OPM-0052-13. <br /> For UL Listed information refer to UL Listed page 66. <br /> Finish: Plain or Electro-Galvanized. Contact customer service for alternative fin- <br /> ishes and materials. <br /> Order By: Order by figure number, pipe size to be braced, followed by pipe <br /> size used for bracing (1" (25mm)or 11/4"(32mm)) , and finish. <br /> Important Note: Fig. 1001 is precision manufactured to perform its <br /> function as a critical component of a complete bracing assembly.To ensure <br /> performance, the FM Approval requires that Fig. 1001 must be used only with <br /> other TOLCO bracing products. <br /> Designed to meet or exceed requirements of FM IDS 2-8. <br /> Design Load-For Sch.7,Sch.10,&Sch.40 Pipe <br /> Pipe Part Number&Approx.Wt./100 Allowable Horizontal Capacity(Ibf)Per Installation 1.2.3 <br /> Size 1"(24mm)Brace Pipe 11/4"(32mm)Brace Pipe 30°-44° 45°-59° 60°-74° 75°-90° <br /> in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (M) Lbs. (M) Lbs. (M) Lbs. (M) <br /> 1" (25) 1001-1 X 1 100.0 (45.3) 1001-1 X 11/4 118.0 (53.5) 1800 (8.00) 2550 (11.34) 3120 (13.88) 3490 (25.52) <br /> 11/4"(32) 1001-11/4 X 1 100.0 (45.3) 1001-11/4 X 11/4 114.0 (51.7) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58) <br /> 11/2"(40) 1001-11/2 X 1 100.0 (45.3) 11001-11/2 X 11/4 115.0 (52.1) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58) <br /> 2" (50) 1001-2 X 1 108.0 (49.0) 1001-2 X 11/4 121.0 (54.9) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58) <br /> 21/2"(65) 1001-21/2 X 1 138.6 (62.8) 1001-21/2 X 11/4 160.4 (72.7) 800 (3.56) 1130 (5.02) 1380 (6.14) 1540 (6.85) <br /> 3" (80) 1001-3 X 1 147.2 (66.7) 1001-3 X 11/4 168.7 (76,5) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29) <br /> 4" (100) 1001-4 X 1 160.9 (73.0) 1001-4 X 11/4 182.4 (82.7) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29) <br /> 6" (150) 1001-6 X 1 190.0 (86.2) 1001-6 X 11/4 211.4 (95.9) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40) <br /> 8" (200) 1001-8 X 1 217.4 (98.6) 1 1001-8 X 11/4 238.8 (108.3) 1 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40) <br /> 1 FM Approved when used with 1 or 11/4 inch NPS Schedule 40 GB/T 3091,EN 10255H,or JIS G3451 steel pipe as the brace member. <br /> 2 Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as"Schedule 7".These ratings may <br /> also be applied when EN 10220 and GB/T 8163 steel pipe. <br /> 3 Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H,or JIS G3454,FM Approved Thinwall, <br /> or Schedule 40 steel pipes. <br /> Note: See UL load ratings in UL Listed Design Load chart shown under drawing. <br /> Note: Metric sizes are available, contact factory. <br /> 0 O o <br /> Fig.too, <br /> All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. <br /> B-Line series Fire Protection Solutions 67 Eaton <br />