IPS CARBON STEEL PIPE—FIRE PROTECTION VALVES 10. 18 <br /> FireLock° Butterfly Valve <br /> SERIES 705W <br /> WITH WEATHERPROOF ACTUATOR <br /> SWITCH AND WIRING 1.The supervisory switch contains two,single pole,double throw, pre-wired switches. <br /> 2.Switches are rated: <br /> 10 amps @ 125 or 250 VAC/60 Hz <br /> 0.50 amps @ 125 VDC <br /> 0.25 amps @ 250 VDC <br /> 3.Switches supervise the valve in the"open" position. <br /> 4.One switch has two#18 MTW wires per terminal,which permit complete supervision of leads <br /> (refer to diagrams and notes below).The second switch has one#18 MTW wire per terminal. <br /> This double circuit provides flexibility to operate two electrical devices at separate locations, <br /> such as an indicating light and an audible alarm, in the area that the valve is installed. <br /> 5.A#14 MTW ground lead (green) is provided. <br /> Switch#1 =S1 For connection to the supervisory circuit of a UL <br /> Listed alarm control panel <br /> Switch#2=S2 Auxiliary switch that may be connected to auxiliary <br /> devices, per the authority having jurisdiction <br /> S1 Normally Closed: (2) Blue <br /> Common: (2)Yellow <br /> Normally Closed: Blue with Orange Stripe <br /> S2 Normally Open: Brown with Orange Stripe <br /> Common:Yellow with Orange Stripe <br /> ULLISTED <br /> JUNCTIONB� FIRE ALARM TO END OF-LINE RESISTOR, <br /> CONTROL NET OR NEXT INDICATOR <br /> CONDUIT SUPERVISORY <br /> CIRCUIT <br /> NC NO. COM. <br /> SWR H <br /> W NPT CONTACT RATING: <br /> I� CONDUIT CONNECTORS l0A AT 125 AND ■ Sl <br /> 250VAC, <br /> 0.5A AT 125 VOC, <br /> 0.25 AT 250 VDC <br /> 52 BE <br /> WIRENUTS ■ <br /> OR <br /> VOLTAGESOURCE HORN <br /> Switch 1:2 leads per terminal <br /> Switch 2:1 lead per terminal <br /> NOTE:The above diagram shows a connection between the common terminal (yellow—S1 and <br /> yellow-with-orange stripe—S2)and the normally closed terminal (blue—S1 and blue-with-orange <br /> stripe—S2). In this example,the indicator light and alarm will stay on until the valve is fully open. <br /> When the valve is fully open,the indicator light and alarm will go out. Cap off any unused wires <br /> (e.g. brown with orange stripe). <br /> Only S1 (two leads per terminal) may be connected to the fire alarm control panel. <br /> The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary <br /> switch per NFPA 70(NEC). <br /> www.victaulic.com <br /> VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2008 VICTAULIC COMPANY.ALL RIGHTS RESERVED. IC_tau I-id <br /> 10.18_6 REV_H <br />