Section 11. Electrical - Low Voltage <br /> 11.1 Low Voltage Maximum Wire Length <br /> Table 11.1 defines the maximum total length of Table 11.1 <br /> low voltage wiring from the outdoor unit, to the 24 VOLTS <br /> indoor unit, and to the thermostat. <br /> WIRE SIZE MAX.WIRE LENGTH <br /> 18 AWG 150 Ft. <br /> 16 AWG 225 Ft. <br /> 14 AWG 300 Ft. <br /> 11.2 Low Voltage Hook-up Diagrams <br /> With TEM 3, 4, 6, 8 With TAM 4, 5, 7, 9 <br /> Thermostat Air Handler Outdoor Thermostat Air Handler Outdoor <br /> Unit Unit <br /> 24 VAC HOT IKI - - - ED - - - � 24 VAC HOT - - - -� - - - � <br /> FAN - - - -❑ FAN - - - -❑ <br /> 24VAC24 VAC <br /> Common ��9 - - - -IN - - - - p I Common <br /> SOV - - - -� - - - � SOV ID - - - -10 T <br /> COOL/HEATCOOL/HEAT <br /> 1s STAGE Y Y <br /> 1st STAGE - - - - Y* - - - -❑ I - - - - <br /> HEATING <br /> 2ndSTAGE I Y� I - - -/ White- <br /> LJ <br /> HEAT <br /> V� - - HEATING - <br /> /\� - - - �/� 2nd STAGE <br /> EW2 X2 Black <br /> HEATGENCY BW2 <br /> - - - Black <br /> • Units with pigtails require wirenuts for connections. <br /> • In AC systems for multiple stages of electric heat,jumper W1 and W2 together if comfort control has only one stage of heat. <br /> * Y2 for TEM6 <br /> 18-BC108D1-1 B-EN 13 <br />