SITTS & HILL ENGINEERS, INC. <br /> TACOMA, WASHINGTON (253)474-9449 JOB: 17659 <br /> DESIGNED: EMF DATE: 03/17/2020 8 <br /> PROJECT: SITE PUMPED INDUSTRIAL WASTE CHECKED: BKL DATE: 03/17/2020 <br /> Precast Concrete Panel Flexural Strength: <br /> The precast concrete panels will be reinforced with #5 reinforcing bars at 6" O.C, each <br /> way at the bottom face of the panel and with #4 reinforcing bars at 6" O.C. each way at <br /> the top face of the panel. Per the attached Enercalc beam analysis of the precast <br /> concrete panel spanning over the width of the trench, the panels can resist half an axle <br /> load in flexure and are found to be OK. <br /> P .":=P=20.8 kip Precast panel design load <br /> Channel Strength: <br /> The channels in the welded steel frames are checked for their ability to resist a single <br /> wheel load in flexure. This load distribution is based on the assumption that the wheel <br /> group dimensions and load transfer within the precast assemblies will ensure that no <br /> single channel sees more than a single wheel load. Per the attached Enercalc analyses, <br /> the channels are OK in flexure. <br /> 10.4 kip Channel design load <br /> Pchalm(i:=0.5 P= , <br /> Trench Lid Support Member ' <br /> W8x24 beams will be provided at unsupported trench lid bearing edges at corners or <br /> turns in the trench alignment. These beams are only required at the 3'-0" x 2'-0" trench, <br /> and are found to be capable of supporting half an axle load per the attached Enercalc <br /> analysis. A 1/2" single shear plate connection with (2) 1" 0 A325 bolts with a capacity of <br /> 37 kips (ASD) per AISC SCM Table 10-10a approximates the beam shear strength and <br /> can withstand the design loads. <br /> P beam:=P=20.8 kip Lid support beam design load , <br /> I <br /> I <br />