Laserfiche WebLink
�`•� AIR DISTRIBUTION TEST <br /> Date: 11/3/2022 <br /> Pages: of <br /> Project: Everett Mall Retail TI- Suites D Job # 3596 <br /> System: RTU-4 <br /> Terminal Room Terminal Factor Design Test - FPM or CFM Final <br /> No. No. <br /> Type Size FPM CFM Test 1 Test 2 Test 3 FPM CFM <br /> 1 S A 10" 240 259 286 239 250 <br /> 2 S A 10" 200 257 262 197 204 <br /> 3 S/A 10" 280 283 287 269 289 <br /> 4 S A 10" 280 287 255 1 275 270 <br /> 5 S A 10" 280 235 307 270 291 <br /> 6 S A 10" 280 260 278 290 302 <br /> 1560 1606 <br /> 7 R A 20" -1295 -1469 -1574 -1578 -1354 <br /> Outside Air 250 112 101 252 <br /> REMARKS: Fan speed maxed, balanced supplies to 280 CFM, back rooms were over conditioned- <br /> reduced CFM there. Drawing shows open floor plan. <br /> CamScanner <br />