Laserfiche WebLink
AM <br /> MECHANICOAL TESTING,A nTING AND GLANCING BUREAU <br /> THE IROFE3910-CHOICE- <br /> VA V BOX <br /> PROJECT: EMOP Suite 110 DATE: 12/18/2024 <br /> LOCATION: Everett,WA CONTACT: Trent Scacco <br /> PROJECT#: 24-413 AUTHOR: <br /> SYSTEM/UNIT: VAV-108 Tested By: Trent Scacco <br /> Date: 12/5/2024 <br /> Unit Data Motor Data <br /> Unit Manufacturer Enviro-Tec Nameplate Motor Hertz 60 Hz <br /> Unit Model Number VVFEH <br /> Terminal Type Parallel Fan Powered Term Box Test Data <br /> Box Inlet Size 12 Design Max Airflow 1500 CFM <br /> Actual Max Airflow 1527 CFM <br /> Fan Speed Setting High <br /> Log: VAV-108 12/5/2024 Trent Scacco AHU Static-1.2"W.C. ,VAV Static-.71"W.C. <br /> VAV-108 Supply Outlet Summary <br /> System/Unit Area Served Outlet Size LxW/ Instrument AK Final Design Prelim Final CFM %G Final <br /> Type D Factor FPM CFM CFM <br /> Outlet-01 Open Office CD 12 Rotating Vane 1.00 522 500 518 522 104 <br /> Outlet-02 Open Office CD 12 Rotating Vane 1.00 486 500 454 486 97 <br /> Outlet-03 Open Office CD 12 Rotating Vane 1.00 520 500 545 520 104 <br /> Totals: - - - - - 1500 1517 1528 102 <br /> SYSTEM/UNIT: VAV-109 Tested By: Trent Scacco <br /> Date: 12/11/2024 <br /> Unit Data Motor Data <br /> Unit Manufacturer Enviro-Tec Nameplate Motor Hertz 60 Hz <br /> Unit Model Number VVFEH <br /> Terminal Type Parrallel Fan Powered Term Box Test Data <br /> Box Inlet Size 10 Design Max Airflow 1500 CFM <br /> Actual Max Airflow 1287 CFM <br /> Fan Speed Setting High <br /> Log: VAV-109 12/11/2024 Trent Scacco No flow ring installed <br /> VAV-109 12/11/2024 Trent Scacco AHU Static-1.2"W.C. ,VAV Static-.49"W.C. <br /> VAV-109 Supply Outlet Summary <br /> System/Unit Area Served Outlet Size LxW/ Instrument AK Final Design Prelim Final CFM %G Final <br /> Type D Factor FPM CFM CFM <br /> Outlet-01 Open Office CD 12 Flowhood 1.00 432 500 559 432 86 <br /> Outlet-02 Confernce CD 12 Flowhood 1.00 440 500 275 440 88 <br /> Room <br /> Outlet-03 Confernce CD 12 Flowhood 1.00 415 500 328 415 83 <br /> Room <br /> Totals: - - - - - 1500 1 1162 1 1287 86 <br /> T& S Mechanical Page 2 of 4 <br />