Laserfiche WebLink
BACKFEED BREAKER SIZING <br /> MAX. CONTINUOUS OUTPUT 16.00A @ 240V PV SYSTEM <br /> 16.00 1XI 1.25 1 = 120.00AMPS 120A BREAKER-OK 4.300 kW-DC <br /> SEE 705.12 OF 2020 NEC 3.800 kW-AC <br /> 200 Xj 1.20 1 = 1240 <br /> 240 - 200 1 = 40A ALLOWABLE BACKFEED <br /> CLIENT: <br /> JESUS BARAJAS <br /> 5416 ROCKEFELLER AVE,EVERETT,WA <br /> 98203 <br /> AHJ:CITY OF EVERETT <br /> (E)UTILITY UTILITY:SNOHOMISH PUD <br /> (E)200A RATED METER METER:1000373305 <br /> MAIN SERVICE PANEL APN:004958-006-012-00 <br /> 1 PH,120/240V 60HZ PHONE:(206)513-9680 <br /> (E)200A/2P MAIN EMAIL:JESUSBARAJASB@GMAIL.COM <br /> BREAKER <br /> STRING-1 (TOP FED) <br /> 10 SILFAB SOLAR:SIL-430QD SYSTEM:SYSTEM SIZE(DC):10 X 430=4.300 kW <br /> SYSTEM SIZE(AC):3.800 kW @ 240V <br /> MODULES:10 X SILFAB SOLAR:SIL-430QD <br /> (N)30A RATED OPTIMIZERS:10 X SOLAREDGE S440 <br /> INVERTER:SOLAREDGE SE380OH-USRGM <br /> (N)SOLAREDGE VISIBLE LOCKABLE [SI1] <br /> SE380OH-USRGM[Sill LABELED DISCONNECT TO OTHER LOADS <br /> INVERTER EATON DG221URB(OR <br /> SOLAREDGE S440 POWER OPTIMIZERS AC EQUIVALENT) •� <br /> KNIFEBLADE,LOCKABLE, <br /> DCNEMA 3R,UL LISTED <br /> l� (N)20A/2P PV BREAKER � <br /> n TO UTILITY <br /> JUNCTION I OX o • OVERHEAD-DROP THROUGH <br /> _------------- ---- dl ------ --------_—_----_-----_— <br /> L__ _--_---_ BOX —_--- o ROOF <br /> FEED <br /> RAPID <br /> SHUTDOWN I REVISIONS <br /> 2-#10 AWG,PV WIRE SWITCH L NO. REVISED BY DATE <br /> 1-#6 AWG IN FREE AIR OR 2-#10 AWG,THWN-2 3-#10 AWG,THWN-2 3-#10 AWG,THWN-2 <br /> #10 AWG MUST BE IN EMT 1-#10 EGC,THWN-2 1-#10 EGC,THWN-2 1-#10 EGC,THWN-2 <br /> CONDUIT IN OR IN 3/4"OR LARGER EMT IN 3/4"OR LARGER EMT <br /> LARGER EMT CONDUIT CONDUIT CONDUIT <br /> freedom- <br /> FOREVER <br /> FREEDOM FOREVER LLC <br /> 43445 BUSINESS PARK DR#110,TEMECULA, <br /> CA 92590 <br /> Tel:(800)385-1075 <br /> GREG ALBRIGHT <br /> �� g�N— <br /> CONTRACTOR LICENSE: <br /> ELECTRICAL ADMINISTRATOR ALBRIG*807C1 <br /> NOTE: <br /> CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED <br /> ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT THREE LINE DIAGRAM <br /> TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS JOB NO: DATE: DESIGNED BY: SHEET: <br /> 488990 8/23/2024 G.D. PV-4 <br />