Laserfiche WebLink
S <br /> YEN DESIGN INC, <br /> PC Comment Response Letter <br /> June 12, 2017 <br /> 5. Specify 5/8" Type "X" GWB on interior side of walls that are less than 5 feet from <br /> property line (In locations where GWB is removed). <br /> Response:A keynote specifying this requirement has been added to the plans. <br /> 6. Provide minimum 100 CFM exhaust fan in the kitchen. Fan shall be vented to the <br /> exterior. <br /> Response:A 110 CFM exhaust fan has been added in the kitchen with a <br /> keynote showing the venting requirements. <br /> 7. Show how the basement is thermally isolated from the main floor, including the walls <br /> adjacent to the stairs,or provide insulation as required by the Washington State Energy <br /> Code in the basement. If basement is heated provide details for the installation of the <br /> insulation at below grade walls. <br /> Response:A key note has been added to the plans to explain the required <br /> insulation method. <br /> 8. The opening between the hall to the bedrooms and the dining room was enlarged. <br /> Provide size, species and grade of beam used for the enlarged opening. <br /> Response:This opening is unchanged.Added dimensions to the proposed and <br /> existing plans to clarify. <br /> 9. Provide "Building Section"specific to this structure.Show the ceiling height for all <br /> levels and the thickness of the floor assembly between the main floor and the <br /> basement. <br /> Response:A building section has been added to the plans on page A4.1. <br /> 7. Smoke Alarms shall be installed not less than 3 feet horizontally from a door or <br /> opening of a bathroom that contains a bathtub or shower unless this would prevent <br /> placement of a smoke alarm required by 704.2.2.1 IPMC. <br /> Response: Positioning of the proposed smoke alarms has been adjusted to <br /> better comply with Section 704.2.2.1. IPMC. A note has been changed to specify <br /> required type of smoke alarm. <br /> 6. Specify how the dwelling is heated. <br /> Response:The home will have a new forced-air furnace system installed in the <br /> basement. A note has been added to call this out. <br /> (425)346-6507I WWW.YENDES.COM <br /> z13 <br />