|
•
<br /> SER
<br /> PERI ANENTE
<br /> Project
<br /> Kaiser Permanente Everett
<br /> BASEMENT TER-VRF SYSTEM HOT WATER CABINET UNIT HEATERS Medical Clinic Expansion
<br /> NOTES: FAN UNIT SIZE WATERSIDE MOTOR
<br /> 1.MULTIPLE MODULE UNITS HAVE MULTIPLE ELECTRICAL CONNECTIONS. OPER 2929 PINE STREET
<br /> 2.REFER TO ELECTRICAL DRAWINGS FOR DISCONNECTS. SYMBOL LOCATION FLOW EXTSP' INLET..'IN OUTLET. FILTER MBH GPM EWT("F) MAXPD HP VOLT/ WEIGHT DESIGN BASIS/REMARKS EVERETT,WA 98201
<br /> 3.PROVIDE WITH BACNET GATEWAY CONTROLLER. (CFM) IN IN VEL:FPM (FT) PH (LBS)
<br /> 4.PROVIDE FACTORY CONDENSATE PUMP WITH POWER PROVIDED BY INDOOR UNIT. CUH-1 NOT USED Prepared for
<br /> 5.PROVIDE MANUFACTURER RECOMMENDED FILTER BOX. CUH-2 SOUTH STAIR 410 0.2 24x6 - 310 9.4 1.5 115 3 1/20 120/1 125 TRANE FORCE-FLO 040[1,2,3]
<br /> 6.EQUIVALENT PIPE LENGTH IS AN ASSUMED VALUE INCLUDING PIPE FITTING CORRECTIONS USED TO DETERMINE UNIT CAPACITY.IT DOES NOT REPRESENT ACTUAL PIPE LENGTHS. CUH-3 NORTH STAIR 410 0.2 24x6 310 9.4 1.5 115 3 U20 12011 125 TRANE FORCE-FLO 040 1,2,3
<br /> KAISER FOUNDATION
<br /> 7.TWO IDU OPERATE SIMULTANEOUSLY,AND TWO IDU ARE REDUNDANT. CUH-4 VESTIBULE 430 0.4 24x6 24x6 325 15.7 2.5 115 10 1/16 120/1 125 TRANE FORCE-FLO 04011 2,41 HEALTH PLAN, INC.
<br /> 8.ONE ODU OPERATES AND ONE ODU IS REDUNDANT.
<br /> 9.PROVIDE DSD ON SUPPLY DUCT FOR IDU SHUTOFF.
<br /> NOTES:
<br /> COOLING HEATING FAN CONNECTIONS MAX ELECTRICAL BASIS OF DESIGN 1.PROVIDE 3/4"HEATING WATER SUPPLY AND RETURN BRANCH PIPING.
<br /> DESIGN DESIGN SOUND 2.PROVIDE FAN SPEED CONTROLLER.
<br /> 3.HORIZONTAL CONCEALED CONFIGURATION,3-ROW COIL,70 DEG F ENTERING AIR TEMPERATURE.
<br /> NOMINAL TOTAL SENS EAT EAT OSA EFF: HEAT EAT OSA GAS LIQUID PRESS 4.VERTICAL CABINET SLOPE TOP,2-ROW COIL,70 DEG F ENTERING AIR TEMPERATURE.
<br /> CLG: CLG: CLG: DB: WB: DB: EERI CAP: DB: DB: AIRFLOW: PIPE: PIPE: DRAIN: OUTDOOR (HIMIL) WEIGHT:TIP.A.EMCA
<br /> MARK TYPE LOCATION MBH MBH MBH F F F IEER MBH F F CFM INCH INCH INCH UNIT REFRIG dB(A) LBS MOCP MANUFACTURER MODEL NOTES
<br /> IDU1-TER INDOOR CEILING CONCEALED TER/STORAGE-BASEMENT 72.0 67.0 54.0 74 1 67 1 NIA WA 2,500 ODU-1.2 R410A 220 2081230/11 7.7 15 CITYMULTI PEFY-P72NMHSU-E 1-7,9 3/512021
<br /> IDU2-TER INDOOR CEILING CONCEALED TERISTORAGE-BASEMENT 72.0 67.0 54.0 74 1 67 1 NIA WA 2,500 ODU-1.2 R410A 220 208/230111 7.7 15 CITYMULTI PEFY-P72NMHSU-E 1-7,9
<br /> IDU3-TER INDOOR CEILING CONCEALED TER/STORAGE-BASEMENT 72.0 67.0 54.0 74 67 N/A WA 2,500 ODU-1.2 R410A 220 208/230/1 7.7 15 CITYMULTI PEFY-P72NMHSU-E 1-7,9
<br /> IDU4-TER INDOORCEILING CONCEALED TER/STORAGE-BASEMENT 72.1 67.0 54.0 74 67 N/A WA 2,500 ODU-1.2 R410A 220 208230/1 7.7 15 CITYMULTI PEFY-P72NMHSU-E 1-7,1
<br /> ODU-1 OUTDOOR VRF UNIT ROOF 144.0 120.0 108.0 89 13.8.130.1 NIA 540 R410A 6030 660 460/3 19 30 CITYMULTI PUHY-EP144YNU 13,6,8 kil
<br /> ODU-2 OUTDOOR VRF UNIT ROOF 144.0 120.0 108.0 89 13.8.I30.1 NIA 540 R410A 60-00 660 460/3 19 30 CITYMULTI PURY-EP144YNU 13.6,8
<br /> VARIABLE REFRIGERANT FLOW INDOOR UNITS GLYCOL FILL UNIT
<br /> NOTES: VOLUME MAX OP ELECTRICAL OPER Hellmuth,Obata&Kassabaum,Inc.
<br /> 1.PROVIDE FACTORY CONDENSATE PUMP WITH POWER PROVIDED BY INDOOR UNIT. SYMBOL SYSTEM SERVED LOCATION (GAL) PRESSURE WEIGHT DESIGN BASIS/REMARKS 1218 Third Avenue,Suite 1315
<br /> 2.PROVIDE MANUFACTURER RECOMMENDED FILTER BOX. (PSIG) V/PH/HZ MOTOR HP (LBS) Seattle,WA 98101 USA
<br /> 3.EQUIVALENT PIPE LENGTH IS AN ASSUMED VALUE INCLUDING PIPE FITTING CORRECTIONS USED TO DETERMINE UNIT CAPACITY.IT DOES NOT REPRESENT ACTUAL PIPE LENGTHS. t+1 206 493 1771 If+1 206 493 1778
<br /> 4.SEE DETAIL. GF-1 HEATING WATER BASEMENT 53 125 120/1/60 1 610 ARMSTRONG GLA-S-HP-1
<br /> 5.4-WAY AIRFLOW TYPE CF-1 HEAT RECOVERY ROOF 5 200 NIA N/A 80 WESSELS CPFTA-5 All recotror,s Intellectual oroaen right.reserved
<br /> 201e
<br /> NOTES: In Association with
<br /> HEAT FAN CONNECTIONS MAX ELECTRICAL BASIS OF DESIGN 3/1/2021
<br /> DESIGN DESIGN [3]EQUIV SOUND Mortenson
<br /> NOMINAL TOTAL SENS EAT EAT OSA OSA PIPE HEAT EAT OSA OSA GAS LIQUID PRESS General Contractor
<br /> CLG: CLG: CLG: DB: WB: DB: WB: LENGTH: CAP: DB: DB: WB: AIRFLOW: PIPE: PIPE: DRAIN: OUTDOOR (H/MIL) WEIGHT: VOLT SCCR: 10230 NE Points Drive,Suite 300
<br /> MARK LOCATION MBH MBH MBH F F F F FT MBH F F F CFM INCH INCH INCH UNIT REFRIG dB(A) LBS IPHASE MCA MOCP AMPS MANU MODEL NOTES Kirkland,WA 98033
<br /> IDU-1 WALL-MOUNTED UNIT Equipment Mechanical 24.0 24.0 19.6 80 67 80 67 21.8 70 920 518 318 314 ODU-3 R410A 39/49 46 208/230/1 0.63 15 5KA TRANE/MITSUBISHI PKFYP024W142A 1-0 ConXteCh,IncIDU-2 WALL-MOUNTED UNIT Equipment Mechanical 24.0 24.0 19.6 80 67 21.8 70 920 5/8 3/8 3/4 ODU-3 R410A 39/49 46 208/230/1 0.63 15 5KA TRANE/MITSUBISHI PKFYP024KM142A 1-0
<br /> Structuralch,FabricatorIn
<br /> IDU-3 CEILING SUSPENDED UNIT A-6005 Equipment Room,Electrical 30.0 30.0 22.0 80 67 27.5 70 850 518 3/8 314 ODU-3 R410A 43/49 46 2081230/1 0.63 15 5KA TRANE/MITSUBISHI PKFYP030KMI42A 1-4 6701 Koll Center Parkway,Suite 150
<br /> IDUA WALL-MOUNTED UNIT A-B002 Electrical 30.0 30.0 22.0 80 67 27.5 70 850 518 318 3/4 ODU-3 R410A 43/49 46 208/230/1 0.63 15 5KA TRANE/MITSUBISHI PKFYP0301OM142A 1-0 SUPPLY FANS Pleasanton,CA 94566
<br /> IDU-5 WALL-MOUNTED UNIT Compressor Room 24.0 24.0 19.6 80 67 21.6 70 920 5/8 3/8 3/4 ODU-3 R410A 39/49 46 208230/1 0.63 15 5KA TRANE/MITSUBISHI PKFYPO24KM142A 1-0
<br /> IDU-6 WALL-MOUNTED UNIT Compressor Room 24.0 24.0 19.6 80 67 21.8 70 920 518 3/8 3/4 ODU-3 R410A 39/49 46 208230/1 0.63 15 5KA TRANE/MITSUBISHI PKFYP024KM142A 1-
<br /> IDU-7 CEILING CASSETTE UNIT Eqcmp-MRI-Levels 36.0 36.0 50' 80 67 45 70 1,236 5/8 3/8 3/4 ODU-3 R410A 36/42/45 66 20823011 1.27 15 5KA TRANE/MITSUBISHI PLFYPO EM140A 1-0 KPFF Consulting Engineers
<br /> IDU-8 NOT USED DIS CASING OPER Civil a Structural Engineering
<br /> IDU-9 WALL-MOUNTED UNIT TR A-3356-Level 3 18.0 18.0 8.5 80 67 11.3 70 413 1/2 1/4 3/4 ODUA R410A 34139/43 29 208/230/1 0.38 15 5KA TRANE/MITSUBISHI PKFYPO18HM142A 1-0 SYMBOL SYSTEM SERVED TYPE CFM MIN FAN SIZE V/PH/HZ WEIGHT DESIGN BASIS/REMARKS 1601 Fif[h Avenue,Sui[a 1600
<br /> IDU-10 WALL-MOUNTED UNIT TR A-3004-Level 3 18.0 18.0 8.5 80 67 11.3 70 413 1/2 1/4 3/4 ODUA R410A 34139/43 29 208/230/1 0.38 15 5KA TRANE/MITSUBISHI PKFYPO18HM142A 1-0 CHARGE SP(IN)(RPM) WxH(IN) HP RPM (LBS) Seattle,WA 98101
<br /> IDU-11 WALL-MOUNTED UNIT Med Prep A-3343-Level 3 12.0 11.5 8.5 80 67 11.3 70 413 1/2 1/4 3/4 ODU-0 R410A 34/39/43 29 20823011 0.38 15 5KA TRANE/MITSUBISHI PKFYPO12HM142A 1-0
<br /> IDU-12 WALL-MOUNTED UNIT TR A-4456-Level 4 18.0 18.0 8.5 80 67 11.3 70 413 1/2 1/4 314 ODU-4 R410A 34/39/43 29 208230/1 0.38 15 5KA TRANE/MITSUBISHI PKFYPO18HM142A 1-0 SF-1 TRANSFORMER ROOM CENTRIFUGAL INLINE 3200 1 1534 25X25...1 1.5 11534 46013 150 COOK SON165 Mazzetti
<br /> IDU-13 WALL-MOUNTED UNIT TR A-4003-Level 4 18.0 18.0 8.5 80 67 11.3 70 413 1/2 1/4 3/4 ODU-4 R410A 34/39/43 29 208/230/1 0.38 15 5KA TRANE/MITSUBISHI PKFYPO18HM142A 1-4 NOTES:1.PROVIDE MERV-8 FILTER BOX AND MOTOR GUARD. MEP+FP Engineering
<br /> IDU-14 I WALL-MOUNTED UNIT Med Prep A-506-Level 4 12.0 11.5 8.5 80 67 11.3 70 413 1/2 1/4 3/4 ODUA R410A 34139/43 29 208230/1 0.38 15 5KA TRANE/MITSUBISHI PKFYPO12HM142A 1-0 20134th Avenue,Suite 200
<br /> IDU-15 I WALL-MOUNTED UNIT Med Prep A-4443-Level 4 12.0 11.5 8.5 80 67 11.3 70 413 1/2 1/4 3/4 ODUA R410A 34139/43 29 208230/1 0.38 15 5KA TRANE/MITSUBISHI PKFYPO12HM142A 1-0 3/112021 Seattle,WA 98121
<br /> IDU-16 WALL-MOUNTED UNIT Elevator Machine Room-Level 5 24.0 23.0 18.0 80 67 16.8 70 775 5/8 318 3/4 ODU-5 R410A 39/42/45 46 208/230/1 0.63 15 5KA TRANE/MITSUBISHI PKA-A24KA7.TH 1-4
<br /> Key Plan
<br /> VRF OUTDOOR UNITS PUMPS
<br /> NOTES:
<br /> 1.MULTIPLE MODULE UNITS HAVE MULTIPLE ELECTRICAL CONNECTIONS. MOTOR VIBRATION ISOLATION
<br /> 2.REFER TO ELECTRICAL DRAWINGS FOR DISCONNECTS. TOTAL DESIGN DESIGN OPER
<br /> SYMBOL SYSTEMSERVED TYPE GPM HEAD TEMP PRESS BASE ISOLATOR MIN V/PWHZ WEIGHT DESIGN BASIS/REMARKS
<br /> 3.PROVIDE WITH BACNET GATEWAY CONTROLLER. (FT) ('F) (PSIG) BHP HP RPM TYPE TYPE STATIC (LBS)
<br /> 4.SEE DETAILS. DEFL(IN)
<br /> 5.NOMINAL COOLING CAPACITIES ARE BASED ON INDOOR COIL EAT 80/67"F(DBMB)AND OUTDOOR 95"F(DB). HWP-1 HEATING WATER V INLINE 90 50 115 2.5 3 1770 - ISOL PAD 0.11 460/3/60 200 ARMSTRONG 4380-1.5xl.5x6(PONY PUMP) Professional Seals
<br /> 6.FOMINALHMS,WITH
<br /> H PACITIESMULTIPLE ARE MODULES, EF IGERA TPIPE T 70-F DIMENSION INDICATE
<br /> TOTAL SF(WB) HWP-2 HEATINGWATER VINLINE 200 100 120 7.4 15 3266 - ISOL PAD 0.11 460/3/60 400 ARMSTRONG 4380-3x3x6
<br /> 7.FOR SYSTEMS,WITH MULTIPLE MODULES,REFRIGERANT PIPE DIMENSIONS INDICATE TOTAL SYSTEM COMBINED PIPING
<br /> HWP.3 HEATING WATER V INLINE 200 100 120 7.4 15 3266 - ISOL PAD 0.11 460/3/60 400 ARMSTRONG 4380-3x3x6 W.
<br /> COOLING HEATING CONNECTIONS ELECTRICAL BASIS OF DESIGN HRP-1 HEAT RECOVERY V INLINE 100 45 60 1.6 2 3266 - ISOL PAD 0.11 277/1/60 200 ARMSTRONG 4380-2x2x6 t,Q4'DF w,1s
<br /> DESIGN DESIGNdOMINAL DESIGN EFF::CO
<br /> MAX
<br /> NOMINAL TOTAL OSA HEAT HEAT OSA @47FGAS LIQUID REFRIG SOUND NOTES:(HSPF)CLG: DE: CAP: CAP: WB: PIPE: PIPE: CHARGE PRESS WEIGHT: VOLT SCCR: MANUFACTU
<br /> MARK TYPE LOCATION MBH MBH FMBH MBH F INCH INCH REFRIG LBS dB(A) LBS IPHASE MCA MOCP AMPS RER MODEL NOTES 3/15/2021 2467E ,o
<br /> ODU3 OUTDOOR CONDENSING UNIT ROOF 192 170.6 85 215 193.1 20.2 332 1-1/8 7/8 R410A 110.5 65.1/63 1,300 480/3 14,14 20,20 5KA MITSUBISHI URYE1923BN40AN SCROLUONODU-0 OUTDOOR CONDENSING UNIT ROOF 120 109.0 85 135 116.7 20.2 337 1-1/8 3/4 R410A 53.6 60/62 625 208/3 41 60 5KA MITSUBISHI URYE1203AN40AN SCROLUIODU5 OUTDOOR CONDENSING UNIT ROOF 24 229 85 26 26 16.6 (10.8) 5/8 3/8 R410A 9 47/48 155 20811 19 26 5KA MITSUBISHI PUZ-A24NHA7
<br /> No. Description Data
<br /> BG7 BRANCH CIRCUIT CONTROLLER SEE FLOOR PLANS 192 R410A 110 208/1 0.83 15 MITSUBISHI CMBM0108JA11N4 FORODU3 SCHEMATIC DESIGN 2020/01/24
<br /> DESIGN DEVELOPMENT 2 02 010 511 5
<br /> DESIGN DEVELOPMENT ADDENDUM 2020/06/08
<br /> 50%CONTRACT DOCUMENTS 2020/07/31
<br /> 75%CONTRACT DOCUMENTS 2020/09/25
<br /> PERMIT SET 2020/11/13
<br /> ISSUED FOR CONSTRUCTION 2021/03/19
<br /> HOT WATER UNIT HEATERS HUMIDIFIERS
<br /> AIR SIDE WATERSIDE MOTOR D/SPERTION TUBES OUTDOOR ENCLOSURE
<br /> OPER OPER
<br /> SYMBOL LOCATION CAPACITY FLOW MAXPD VOLT/ WEIGHT DESIGN BASIS/REMARKS SYSTEM CAPACITY
<br /> EAT(-F) LAT("F) GPM EWT ff) W RPM LB SYMBOL MANUFACTURER MODEL CFM MAX AIR DUCT WEIGHT WATER KW V/PH/HZ REMARKS
<br /> (MBH) (CFM) (FT) PH (LBS) SERVED (LBS/HR) ABSORB DIST DUCT SIZE LBS WEIGHT
<br /> MODEL (IN) PD (IN) VELOCITY ( ) MAKEUP DRAIN(IN) (LBS)
<br /> UH-1 A-B100 5.5 380 60 98.0 2.0 115 1 16 1,350 120/1 50 TRANE UHSBO24 (IN WC) (FPM) (IN)
<br /> UH-2 A-B004 5.5 380 60 98.0 2.0 115 1 16 1,350 120/1 50 TRANE UHSBO24 H RTU-1 RTU-1 DRISTEEM VAPORSTREAM VLC 75-3 41,000 197 ULTRASORB LV 6 0.30 84 x 36 1,950 864 1/4 3/4 1,090 56 480/3/60 SEE NOTE 1,2,3,4,8
<br /> H RTU-2 RTU-2 DRISTEEM VAPORSTREAM VLC 50-2 28,000 131 ULTRASORB LV 6 0.30 84 x 36 1.340 740 1/4 3/4 690 37 480/3/60 SEE NOTE 1,2,3,4,8
<br /> H RTU-3 RTU-3 DRISTEEM VAPORSTREAM VLC 42-4 20,000 119 ULTRASORB LV 18 0.30 650 1/4 3/4 1,090 42 1 480/3/60 SEE NOTE 1,2,3,4,8
<br /> H RTU-7 RTU-7 DRISTEEM VAPORSTREAM VLC 24-2 5,500 68 ULTRASORB LV 18 0.30 237 1/4 3/4 690 24 480/3/60 1 SEE NOTE 1,2,3,4,5,8
<br /> NOTES:
<br /> 1.PROVIDE 3/4"HEATING WATER SUPPLY AND RETURN BRANCH PIPING. H 4-3-03 VAV 4-3-03 DRISTEEM VAPORMIST VM-2 815 2.3 SINGLE 6 0.30 12.5 x 14 670 95 - - - 2 277/1/60 SEE NOTE 6,7,9
<br /> H 4-3-08 VAV 4-3-08 DRISTEEM VAPORMIST VM-2 295 0.9 SINGLE 6 0.30 8 x 12 442 95 - - - 2 277/1/60 SEE NOTE 6,7,9
<br /> 3A/2021 H 4-4-20 VAV 44-20 DRISTEEM VAPORMIST VM-2 385 1.1 SINGLE 6 0.30 10 x 12 462 95 - - - 2 277/1/60 SEE NOTE 6,7,9
<br /> H 5-3-13 VAV 5-3-13 DRISTEEM VAPORMIST VM-2 560 1.6 SINGLE 6 0.30 10 x 12 672 95 2 277/1/60 SEE NOTE 6,7,9
<br /> H 5-4-05 VAV 54-05 DRISTEEM VAPORMIST VM-2 560 1.6 SINGLE 6 0.30 10 x 12 672 95 2 277/1/60 SEE NOTE 6,7,9
<br /> H 6-3-12 VAV 6-3-12 DRISTEEM VAPORMIST VM-2 515 1.5 SINGLE 6 0.30 10 x 12 618 95 - - - 2 277/1/60 SEE NOTE 6,7,9
<br /> H 6A-08 VAV 6-4-08 DRISTEEM VAPORMIST VM-2 525 1.6 SINGLE 6 0.30 10 x 12 630 95 - - - 2 277/1/60 SEE NOTE 6,7,9
<br /> NOTES:
<br /> 1.PROVIDE EXTERIOR ENCLOSURE,WITH VENTILATION FAN,PIPING KNOCKOUTS,AND 120V/1P POWER AT 15 AMPS FOR ENCLOSURE HEAT.
<br /> 2.CAPACITY INCLUDES CONDENSATE LOSS FOR SYSTEM OPERATION AT STARTUP. KP Project No: CAP020407
<br /> :
<br /> 3.PROVIDE EVAPORATING CHAMBER INSULATION,FACTORY FLOOR MOUNT SUPPORT ASSEMBLY,CABINET MOUNTED CONTROL PANEL; HOK Project No 19.05002.03
<br /> WITH INTEGRAL AUTOMATED WATER LEVEL CONTROLS,AUTOMATED PERIODIC DRAIN AND FLUSH INCLUDING FACTORY ELECTRONIC DRAIN VALVE. Sheet Title:
<br /> 4.PROVIDE INTERMEDIATE CHANNEL PIPING SUPPORT MIDWAY BETWEEN TUBES TO PREVENT TUBE VIBRATION. QU I PIVI ENT
<br /> MECHANICALLY FASTEN SUPPORT TO BASE AND CEILING OF DUCTWORK,AND TO INDIVIDUAL DISPERSION TUBES. DO NOT BLOCK TUBE DISCHARGE. E
<br /> 5.PROVIDE EQUIPMENT ON EMERGENCY POWER. SCHEDULES
<br /> 6.PROVIDE WITH DRISTEEM HIGH TEMPERATURE CONDENSATE PUMP MODEL A2-SA,115V/1 P,3.5 A.
<br /> a 7.PROVIDE WITH DRISTEEM DRANE-KOOLER.
<br /> 8.SEE DETAIL 1 ON SHEET M712.
<br /> 9.SEE DETAIL 2 ON SHEET M712. or�elnal Ia ao x a2.oo no,scale conaenta or u�a a.aw�ng.
<br /> 2/9/2021 Sheet Number
<br /> M012
<br />
|