Laserfiche WebLink
• <br /> TERMINAL UNITS - RTU-5 - SUPPLY \III/ KAISER <br /> AIR SIDE WATERSIDE NOISE CRITERIA i PERMANENTE=, <br /> INLET MAX OPER <br /> SYMBOL MAX CFM MIN CFM UNIT PID CAPACI7_T EWT/LWT MIN MAX PD RADIATED SOUND PWL DISCHARGE SOUND PWL NC: WEIGHT DESIGN BASIS Project <br /> SIZE(IN) (IN WC) (MBH) (°F) LAT(°F) GPM (°F) ROWS (FT) NC: RAD.3 4 5 6 7 2 3 4 5 6 7 DISCH. (LBS) Kaiser Permanente Everett <br /> 2 <br /> VAV 5-3-01 9 630 230 0.5 7.5 55 85.0 1.2 135/120 2 4 57 47 43 36 33 29 18 71 61 54 47 43 42 24 39 Titus DESV Medical Clinic Expansion <br /> VAV 5-3-02 6 335 120 0.5 3.9 55 85.0 0.7 135/120 2 4 58 52 42 36 32 28 20 71 64 55 45 41 39 24 29 Titus DESV <br /> VAV 5-3-03 8 475 150 0.5 4.9 55 85.0 0.8 1351120 2 4 56 44 38 32 31 28 17 72 59 50 41 39 37 25 32 Titus DESV <br /> VAV 5-3-04 6 130 50 0.5 1.6 55 85.0 0.5 1351120 2 4 51 40 31 24 23 20 18 63 53 44 34 33 31 18 29 Titus DESV 2929 PINE STREET <br /> VAV 5-3-05 6 245 80 0.5 2.6 55 85.0 0.5 1351120 2 4 56 48 38 32 29 26 17 69 61 51 42 39 37 25 29 Titus DESV EVERETT,WA 98201 <br /> VAV 5-3-06 8 555 170 0.5 5.5 55 85.0 0.9 1351120 2 4 59 50 42 37 35 31 20 74 64 54 45 41 38 28 32 Titus DESV <br /> VAV 5-3-07 6 345 130 0.5 4.2 55 85.0 0.7 135/120 2 4 58 52 42 36 32 28 1 20 71 64 54 1 45 41 38 24 29 Titus DESV Prepared for <br /> VAV 5-3-08 12 1040 320 0.5 10.4 55 85.0 1.7 135/120 2 4 59 49 45 40 34 28 20 73 64 57 49 46 43 24 47 Titus DESV P <br /> VAV 5-3-09 8 375 120 0.5 3.9 55 85.0 0.7 135/120 2 4 57 46 39 33 32 29 18 72 61 51 42 40 37 25 32 Titus DESV KAISER FOUNDATION <br /> VAV 5-3-10 8 420 140 0.5 4.5 55 85.0 0.8 135/120 2 4 58 47 40 35 34 30 19 73 62 52 43 40 38 27 32 Titus DESV <br /> VAV 5-3-11 8 375 120 0.5 3.9 55 85.0 0.7 1351120 2 4 57 46 39 33 32 29 18 72 61 51 42 40 37 25 32 Titus DESV HEALTH PLAN, INC. <br /> VAV 5-3-12 8 375 375 0.5 12.2 55 85.0 2.0 1351120 2 4 56 45 39 33 32 28 17 72 60 51 42 39 37 25 32 Titus DESV <br /> VAV 5-3-13 8 560 225 0.5 7.3 55 85.0 1.2 1351120 2 4 59 50 42 37 35 31 20 74 64 54 45 41 38 28 32 Titus DESV <br /> VAV 5-3-14 6 255 80 0.5 2.6 55 85.0 0.5 1351120 2 4 56 49 39 32 30 26 17 69 61 52 42 39 37 25 29 Titus DESV <br /> VAV 5-3-15 6 310 310 0.5 10.0 55 85.0 1.6 135/120 2 4 57 51 41 34 31 27 18 70 63 53 44 40 38 23 29 Titus DESV <br /> VAV 5-3-16 10 860 260 0.5 8.4 55 85.0 1.4 135/120 2 4 60 51 47 44 40 28 22 74 63 56 49 44 41 25 47 Titus DESV <br /> VAV 5-3-17 14 1590 550 0.5 17.8 55 85.0 2.8 135/120 2 4 58 52 45 43 39 35 20 70 61 57 50 49 45 20 47 Titus DESV <br /> VAV 5-3-18 14 1315 540 0.5 17.5 55 85.0 2.8 135/120 2 4 57 51 44 42 38 34 18 70 60 56 50 49 46 20 47 Titus DESV <br /> VAV 54-01 12 1040 320 0.5 10.4 55 85.0 1.7 1351120 2 4 59 49 45 40 34 28 20 73 64 57 49 46 43 24 47 Titus DESV <br /> VAV 54-02 8 375 120 0.5 1 3.9 55 85.0 0.7 1351120 2 4 57 46 39 33 1 32 29 18 72 61 51 42 40 37 25 32 Titus DESV <br /> VAV 54-03 8 375 120 0.5 3.9 55 85.0 0.7 1351120 2 4 57 46 39 33 1 32 29 18 72 61 51 42 40 37 25 32 Titus DESV <br /> VAV 54-04 8 425 130 0.5 4.2 55 85.0 0.7 1351120 2 4 58 47 41 35 1 34 30 19 73 62 52 43 40 38 27 32 Titus DESV <br /> VAV 5-4-05 8 560 225 0.5 7.3 55 85.0 1.2 135/120 2 4 59 50 42 37 35 31 20 74 64 54 45 41 38 28 32 Titus DESV <br /> VAV 5-4-06 8 375 245 0.5 7.9 55 85.0 1.3 135/120 2 4 56 45 39 33 32 28 17 72 60 51 42 39 37 25 32 Titus DESV <br /> VAV 54-07 6 255 140 0.5 4.5 55 85.0 0.8 135/120 2 4 56 48 39 32 29 26 17 69 61 51 42 39 36 25 29 Titus DESV <br /> VAV 54-08 6 310 310 0.5 10.0 55 85.0 1.6 135/120 2 4 57 51 41 34 31 27 18 70 63 53 44 40 38 23 29 Titus DESV <br /> VAV 54-09 6 340 110 0.5 3.6 55 85.0 0.6 135/120 2 4 59 53 42 36 32 28 21 72 64 55 46 41 39 25 29 Titus DESV , <br /> VAV 54-10 6 330 120 0.5 3.9 55 85.0 0.7 1351120 2 4 58 52 42 35 32 28 20 71 64 54 45 41 39 24 29 Titus DESV <br /> VAV 5-4-11 8 555 1 170 1 0.5 5.5 55 85.0 0.9 1351120 2 1 4 59 50 42 37 35 31 20 1 74 64 54 45 41 38 28 32 Titus DESV <br /> VAV 54-12 8 460 140 0.5 4.5 1 55 85.0 0.8 1351120 2 4 58 48 41 36 34 31 19 73 63 53 44 41 38 27 32 Titus DESV <br /> VAV 54-13 9 630 210 0.5 6.8 55 85.0 1.1 1351120 2 4 57 47 43 36 33 29 18 71 61 54 47 43 42 24 39 Titus DESV <br /> VAV 5-4-14 6 130 40 0.5 1.3 55 85.0 0.5 135/120 2 4 1 51 40 31 24 23 20 10 63 53 44 34 33 31 18 29 Titus DESV <br /> VAV 5-4-15 6 245 80 0.5 2.6 55 85.0 0.5 135/120 2 4 56 48 38 321 29 26 17 69 61 51 42 39 37 25 29 Titus DESV <br /> VAV 54-16 6 150 50 0.5 1.6 55 85.0 0.5 135/120 2 4 52 42 33 26 25 22 11 64 54 45 36 34 33 19 47 Titus DESV <br /> VAV 5-4-17 14 1315 400 0.5 13.0 55 85.0 2.1 135/120 2 4 57 51 45 43 39 35 18 70 61 56 51 50 47 20 47 Titus DESV Hellmuth,Obata&Kassabaum,Inc. <br /> VAV 54-18 14 1240 600 0.5 19.4 55 85.0 3.1 1351120 2 4 56 50 44 42 38 34 17 69 60 55 50 49 46 19 47 Titus DESV 1218 Third Avenue,Suite 1315 <br /> VAV 54-19 14 1310 660 0.5 21.4 55 85.0 3.4 1351120 2 4 57 50 44 42 38 34 18 70 60 56 50 49 46 20 47 Titus DESV <br /> 20610 8160 1 Seattle,WA 98101 USA <br /> NOTES: t+1 206 493 1771 f+1 206 493 1778 <br /> 1.NC RATINGS BASED ON 1.5'INLET STATIC PRESSURE AND 0.5"DOWNSTREAM STATIC PRESSURE. <br /> 2.PROVIDE SINGLE DUCT TERMINAL BOX WITH HOT WATER REHEAT COIL AS INDICATED(20%GLYCOL). zulre roa�otror,s Intellectual oroaeny r�ante raser.ea <br /> 3.PROVIDE 3-WAY VALVES IN THE LOCATIONS INDICATED ON DRAWINGS/OR AT THE MOST REMOTE VAV ON EACH BRANCH.PROVIDE 2-WAY CONTROL VALVES FOR ALL OTHER REHEAT COILS. In Association with <br /> 4.PROVIDE WITH MANUFACTURER 1"EPFI(ENGINEERED POLYMER FOAM INSULATION)"FIBRE-FREE'INSULATION. <br /> 5.SEE DETAIL. <br /> Mortensen <br /> General Contractor <br /> 10230 NE Points Drive,Suite 300 <br /> Kirkland,WA 98033 <br /> TERMINAL UNITS - RTU-6 - SUPPLY ConXtech,Inc <br /> Structural Fabricator <br /> AIR SIDE WATER SIDE NOISE CRITERIA 6701 Koll Center Parkway,Suite 150 <br /> INLET MAX OPER Pleasanton,CA 94566 <br /> SYMBOL MAX CFM MIN CFM UNIT PD C�pACITy EWT/LWT MIN MAX PD RADIATED SOUND PWL DISCHARGE SOUND PWL NC: WEIGHT DESIGN BASIS <br /> SIZE(IN) (IN WC) (°F) LAT(°F) GPM (°F) ROWS (FT) NC: RAD. DISCH. (LBS) <br /> z 3 a 5 s 7 z 3 a 5 s 7 KPFF Consulting Engineers <br /> VAV 6-3-01 10 810 250 0.5 8.1 55 85.0 1.3 135/120 2 4 60 51 47 44 40 28 22 74 63 56 49 44 41 25 32 Titus DESV Civil+Structural Engineering <br /> VAV 6-3-02 8 370 150 0.5 4.9 55 85.0 0.8 135/120 2 4 57 46 39 33 32 29 18 72 61 51 42 40 37 25 32 Titus DESV 1601 Fifth Avenue,Suite 1600 <br /> VAV 6-3-03 6 250 80 0.5 2.6 55 85.0 0.5 135/120 2 4 56 49 39 32 29 26 17 69 61 51 42 39 37 25 29 Titus DESV Seattle,WA 98101 <br /> VAV 6-3-04 8 505 160 0.5 5.2 55 85.0 0.9 135/120 2 4 59 49 41 36 35 30 20 73 63 53 44 41 38 27 32 Titus DESV <br /> VAV 6-3-05 1 6 225 80 0.5 2.6 55 85.0 0.5 135/120 2 4 55 47 37 31 29 25 15 68 59 50 41 38 36 24 29 Titus DESV Mazzetti <br /> VAV 6-3-06 6 220 80 0.5 2.6 55 85.0 0.5 135/120 2 4 55 47 37 30 28 25 15 68 59 50 40 38 36 24 29 Titus DESV MEP+FP Engineering <br /> VAV 6-3-07 10 985 300 0.5 9.7 55 85.0 1.6 135/120 2 4 61 51 47 45 41 29 23 75 64 56 50 44 42 27 47 Titus DESV 2013 4th Avenue,Suite 200 <br /> VAV 6-3-08 10 790 240 0.5 7.8 55 85.0 1.3 135/120 2 4 60 50 47 44 39 28 22 74 62 56 49 44 41 1 25 47 Titus DESV Seattle,WA 98121 <br /> VAV 6-3-09 6 260 80 0.5 2.6 55 85.0 0.5 135/120 2 4 56 49 39 32 1 30 26 17 69 61 52 42 39 37 25 29 Titus DESV <br /> VAV 6-3-10 9 710 220 0.5 7.1 1 55 85.0 1.2 135/120 2 4 58 48 43 37 34 29 19 72 62 55 48 44 42 23 39 Titus DESV <br /> VAV 6-3-11 12 1135 350 0.5 11.3 55 85.0 1.8 135/120 2 4 59 50 46 40 35 29 20 73 65 58 49 46 44 24 47 Titus DESV Key Plan <br /> VAV 6-3-12 8 515 260 0.5 8.4 55 85.0 1.4 135/120 2 4 59 49 42 37 35 31 20 73 64 53 45 41 38 27 32 Titus DESV <br /> VAV 6-3-13 8 375 120 0.5 3.9 55 85.0 0.7 135/120 2 4 57 46 39 33 32 29 18 72 61 51 42 40 37 25 32 Titus DESV <br /> VAV 6-3-14 8 365 110 0.5 3.6 55 85.0 0.6 135/120 2 4 56 45 39 33 32 29 17 72 61 51 42 39 37 25 32 Titus DESV <br /> VAV 6-3-15 6 260 80 0.5 2.6 55 85.0 0.5 135/120 2 4 56 49 39 32 30 26 17 69 61 52 42 39 37 25 29 Titus DESV <br /> VAV 6-3-16 8 465 320 0.5 10.4 55 85.0 1.7 135/120 2 4 58 48 41 35 34 30 19 73 62 52 44 40 38 27 32 Titus DESV <br /> VAV 6-3-17 6 155 50 0.5 1.6 55 85.0 0.5 135/120 2 4 52 42 33 26 25 22 11 64 55 46 36 35 33 19 29 Titus DESV <br /> VAV 6-3-18 10 795 240 0.5 7.8 55 85.0 1.3 135/120 2 4 60 50 47 44 40 28 22 74 62 56 49 44 41 25 47 Titus DESV <br /> VAV 6-3-19 6 290 90 0.5 2.9 55 85.0 0.5 135/120 2 4 57 50 40 1 34 1 31 27 18 70 63 53 44 40 38 27 29 Titus DESV <br /> VAV 6-3-20 6 290 90 0.5 2.9 1 55 85.0 0.5 135/120 2 4 57 50 40 34 31 27 18 70 63 53 44 40 38 27 29 Titus DESV <br /> VAV 6-3-21 6 130 50 0.5 1.6 55 85.0 0.5 135/120 2 4 51 40 31 24 23 20 10 63 53 44 34 33 31 18 29 Titus DESV <br /> VAV 6-3-22 6 150 50 0.5 1.6 55 85.0 0.5 135/120 2 4 52 42 33 26 25 22 11 64 54 45 36 34 33 19 29 Titus DESV <br /> VAV 6-3-23 8 555 170 0.5 5.5 55 85.0 0.9 135/120 2 4 59 50 42 37 35 31 20 74 64 54 45 41 38 28 32 Titus DESV <br /> VAV 64-01 8 460 170 0.5 5.5 55 85.0 0.9 135/120 2 4 58 48 41 35 34 30 19 73 62 52 44 40 38 27 32 Titus DESV <br /> VAV 6-4-02 8 370 150 0.5 4.9 55 85.0 0.8 135/120 2 4 57 46 39 33 32 29 18 72 61 51 42 40 37 25 32 Titus DESV <br /> VAV 6-4-03 6 225 70 0.5 2.3 55 85.0 0.5 135/120 2 4 55 47 37 31 29 25 15 68 59 50 41 38 36 24 29 Titus DESV <br /> VAV 64-04 8 515 160 1 0.5 5.2 55 85.0 0.9 135/120 2 4 59 49 42 37 35 31 20 73 64 1 53 45 41 38 27 32 Titus DESV <br /> VAV 6-4-05 6 215 80 0.5 2.6 55 85.0 0.5 135/120 2 4 55 47 37 30 28 24 15 67 59 50 40 1 37 35 23 29 Titus DESV Professional Seals <br /> VAV 64-06 8 475 315 0.5 10.2 55 85.0 1.7 135/120 2 4 58 48 41 1 36 1 34 30 19 73 63 52 44 40 38 27 32 Titus DESV <br /> VAV 64-07 9 590 180 0.5 5.8 1 55 85.0 1.0 135/120 2 4 56 46 42 36 33 28 17 70 60 54 47 43 42 23 39 Titus DESV <br /> W.VAV 64-08 8 530 530 0.5 17.2 55 85.0 2.7 135/120 2 4 59 49 42 37 35 31 20 73 64 53 45 41 38 27 32 Titus DESV <br /> VAV 64-09 6 260 260 0.5 8.4 55 85.0 1.4 135/120 2 4 56 49 39 32 30 26 17 69 61 51 42 39 36 25 29 Titus DESV ��OF AS <br /> VAV 64-10 9 660 200 0.5 6.5 55 85.0 1.1 135/120 2 4 57 48 43 37 33 29 18 72 62 55 47 44 42 25 39 Titus DESV <br /> VAV 64-11 12 1065 320 0.5 10.4 55 85.0 1.7 135/120 2 4 59 50 46 40 34 28 20 73 64 57 49 46 43 24 47 Titus DESV q z <br /> VAV 64-12 1 8 385 120 0.5 3.9 55 85.0 0.7 135/120 2 4 57 46 40 34 33 29 18 72 61 51 42 40 37 25 32 1 Titus DESV <br /> VAV 64-13 8 515 160 0.5 5.2 55 85.0 0.9 135/120 2 4 1 59 49 42 37 35 31 20 73 64 53 45 41 38 27 32 Titus DESV 24672 <br /> VAV 64-14 8 355 1 110 1 0.5 3.6 55 85.0 0.6 135/120 2 4 56 45 39 33 32 29 17 72 60 50 42 39 37 25 32 Titus DESV <br /> VAV 64-15 8 450 260 0.5 8.4 55 85.0 1.4 135/120 2 1 4 58 47 40 35 34 30 19 73 62 52 43 1 40 38 27 29 Titus DESV LS'r Cs <br /> VAV 64-16 12 1050 320 0.5 10.4 55 85.0 1.7 135/120 2 4 59 50 45 40 34 28 20 73 64 57 49 46 43 24 47 Titus DESV TONAL <br /> VAV 64-17 6 195 100 0.5 3.2 55 85.0 0.6 135/120 2 4 54 45 36 29 27 24 14 67 58 49 39 37 35 23 29 Titus DESV <br /> VAV 64-18 9 685 280 0.5 9.1 55 85.0 1.5 135/120 2 4 57 47 42 36 33 28 18 72 61 54 47 43 41 25 39 Titus DESV No. Description Data <br /> VAV 64-19 6 140 100 0.5 3.2 55 85.0 0.6 135/120 2 4 52 41 32 25 24 21 11 63 54 45 35 34 32 18 29 Titus DESV <br /> VAV 64-20 8 555 170 0.5 5.5 55 85.0 0.9 135-M 20 2 4 59 50 42 37 35 31 20 74 64 54 45 41 38 28 32 Titus DESV SCHEMATIC DESIGN 2020/01/24 <br /> DESIGN DEVELOPMENT 2020105115 <br /> VAV 64-21 5 90 40 0.5 1.3 55 85.0 0.5 135/120 2 4 45 38 31 27 26 22 10 64 49 41 32 33 31 19 29 Titus DESV DESIGN DEVELOPMENT ADDENDUM 202D/D8/08 <br /> 20390 7715 50%CONTRACT DOCUMENTS 2020/07/31 <br /> 75%CONTRACT DOCUMENTS 2020/09/25 <br /> NOTES: PERMIT SET 2020/11/13 <br /> 1.INC RATINGS BASED ON 1.5'INLET STATIC PRESSURE AND 0.5'DOWNSTREAM STATIC PRESSURE. ISSUED FOR CONSTRUCTION 2021/03/19 <br /> 2.PROVIDE SINGLE DUCT TERMINAL BOX WITH HOT WATER REHEAT COIL AS INDICATED(20%GLYCOL). <br /> 3.PROVIDE 3-WAY VALVES IN THE LOCATIONS INDICATED ON DRAWINGS/OR AT THE MOST REMOTE VAV ON EACH BRANCH.PROVIDE 2-WAY CONTROL VALVES FOR ALL OTHER REHEAT COILS. <br /> 4.PROVIDE WITH MANUFACTURER 1"EPFI(ENGINEERED POLYMER FOAM INSULATION)"FIBRE-FREE'INSULATION. <br /> 5.SEE DETAIL. <br /> LEVEL-4 CAV- EAV- RAV SOUND POWER LEVELS PHARMACY - LEVEL 4 <br /> SYMBOL MAX INLET SOUND POWER LEVELS MAX DISCHARGE SOUND POWER LEVELS MAX RADIATED SOUND POWER LEVELS DESIGN BASIS/REMARKS /� <br /> CAV-7-2 57 47 41 44 40 37 57 51 48 49 43 40 44 38 37 30 30 30 CAV - EAV - RAV SCHEDULE <br /> RAV-7-1 56 46 40 42 39 37 56 50 47 48 41 39 43 37 36 29 29 29 <br /> CAV-7-1 50 45 46 51 44 50 55 50 49 54 47 44 45 44 42 39 38 38 MAX PRESSURE COIL MAX FLUID <br /> EAV-7-1 49 42 39 40 40 42 48 43 41 45 38 30 32 31 29 27 25 20 CAV/EAV/RAV VALVE VALVE DROP(IN.)/ HEATING AIR EAT F LAT F FLUID FLUID EWT/LWT PRESSURE COIL COIL COIL WEIGHT <br /> AREASERVED UNITSIZE APPLICATION ACCESSORIES CFM CAPACITY TYPE/ FLOW CAPACITY/ ACCESS REMARKS <br /> EAV-7-2 53 46 43 46 44 46 52 46 45 50 42 33 34 35 32 30 28 23 # MODEL PRESSURE PRESSURE DEG. DEG. F DEG. DROP MOUNTING LBS <br /> EAV-7-3 55 48 46 49 47 48 54 48 47 52 44 35 35 37 35 32 30 25 MODEL RANGE MBH DROP(IN.) GLYCOL% (GPM) (Fr W G) COIL TYPE DOOR <br /> EAV-7-4 58 51 49 53 49 51 56 50 49 55 46 49 37 39 37 34 32 27 <br /> CAV-7-3 47 43 44 48 41 48 53 48 47 51 45 42 43 42 39 36 36 37 CAV-7-1 HD BUFFER 212 VV SAV WHWC 1750 0.4/L 47.5 0.13 55 80.1 PG/20 5.0 135/120 3.70 OSCOR CSL ADDQ 65 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> RAV-7-2 58 48 42 45 41 38 58 52 49 50 44 41 45 39 38 31 31 30 CAV-7-2 ANTE ROOM 114 VV SAV WHWC 1120 0.4/L 30.4 0.12 55 79.8 PG/20 5.0 135/120 2.06 OSC12R CSL ADDQ 40 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> CAV-74 54 47 44 47 45 47 52 47 45 51 43 34 35 36 33 31 29 24 CAV-7-3 NON-HD BUFFER 212 VV SAV WHWC 1480 0.4/L 40.1 0.10 55 80.3 PG/20 4.0 135/120 2.49 OSCOR CSL ADDQ 65 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> RAV-7-3 54 47 44 47 45 47 52 47 45 51 43 34 35 36 33 31 29 24 <br /> CAV-74 PHARM REC,CIRC 112 VV SAV WHWC 800 0.5/L 21.7 0.10 55 80.3 PG/20 3.0 135/120 1.17 OSC12R CSL ADDQ 35 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> 11/11/2020 EAV-7-1 HD BUFFER BSC-1 112 VV OEV - 550 0.4/L WA --- --- --- --- --- - - - - - 22 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> EAV-7-2 HD BUFFER BSC-2 112 VV OEV - 750 0.4/L WA --- --- --- --- --- - - - - - 22 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> EAV-7-3 HD BUFFER 112 VV GEV - 3501900 0.4/L WA --- --- --- --- --- - - - - - 22 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> EAV-74 HD BUFFER 112 VV GEV - 350/1100 0.4/L NIA --- --- --- --- --- - - - - - 22 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> RAV-7-1 ANTE ROOM 114 VV GEV - 1020 0.4/L N/A --- --- --- --- --- - - --- - - 24 ANTEC CONTROLS/PRICE VENTURI VALVE <br /> RAV-7-2 NON-HD BUFFER 114 VV GEV - 1230 0.4/L NIA --- --- --- --- --- - - --- - - 24 ANTEC CONTROLS/PRICE VENTURI VALVE KP Project No: CAP020407 <br /> HOK Project No: 19.05002.03 <br /> RAV-7-3 PHARM REC,CIRC 112 VV GEV --- 800 0.5/L N/A --- --- --- --- --- - - --- - - 22 ANTEC CONTROLS/PRICE VENTURI VALVE Sheet Title: <br /> NOTES: EQUIPMENT <br /> 1.PROVIDE HOT WATER REHEAT COIL AS INDICATED.PROVIDE TRANSITION BETWEEN VALVE AND REHEAT COIL. SCHEDULES <br /> 2.PROVIDE 2-WAY CONTROL VALVES FOR ALL REHEAT COILS. <br /> 3.PROVIDE INSULATION FOR CAV VALVES. <br /> 3/15/2021 <br /> IN <br /> or�elnal Ie ao x a2.oo not eoaio ooncente or use a.aw�ns <br /> Sheet Number <br /> M016 <br />