SCOPE OF WORK:
<br /> TO INSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC EQUIPMENT SUMMARY GOVERNING CODES SYSTEM RATING
<br /> SYSTEM AT THE OWNER RESIDENCE LOCATED AT 717 24 HANWHA Q CELL(Q.PEAK DUO-G8+340W) MODULES 2018 INTERNATIONAL RESIDENTIAL CODE 8.16 KWDC
<br /> LAUREL DR EVERETT, WA 98201. 2018 INTERNATIONAL BUILDING CODE
<br /> THE POWER GENERATED BY THE PV SYSTEM WILL BE 24 ENPHASE IQ7-60-2-US(240V) MICROINVERTERS 2018 INTERNATIONAL FIRE CODE 6.00 KWAC
<br /> INTERCONNECTED WITH THE UTILITY GRID THROUGH 2O20 NATIONAL ELECTRICAL CODE
<br /> THE EXISTING ELECTRICAL SERVICE EQUIPMENT. WASHINGTON ADMINISTRATIVE CODE (WAC) SHEET INDEX
<br /> THE PV SYSTEM DOES NOT INCLUDE STORAGE PV-0 COVER PAGE
<br /> BATTERIES PV-1 SITE PLAN
<br /> PV-2 ROOF PLAN&MODULES
<br /> PV-2A STRING LAYOUT&BOM
<br /> GENERAL NOTES: PV-3 ATTACHMENT DETAIL
<br /> • THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND WIRING AND CONDUIT NOTES: PV-3A ATTACHMENT DETAIL
<br /> OTHER INFORMATION AVAILABLE AT THE TIME.ACTUAL FIELD CONDITIONS MAY REQUIRE • ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PV-4 ELECTRICAL LINE DIAGRAM&CALCS. SYSTEM INFO.
<br /> MODIFICATIONS IN CONSTRUCTION DETAILS. PURPOSE AND APPROVED FOR THE SITE APPLICATIONS PV 4A SPECIFICATIONS&CALCULATION (24)HANWHA Q CELL
<br /> • ALL PV CABLES AND HOMERUN WIRES BE#10AWG *USE-2, PV (Q.PEAK DUO-G8+340W)
<br /> • ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR WIRE, OR PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, PV-5 SIGNAGE (24)ENPHASEIQ7-60-2-US(24ov)
<br /> INSTALLATION OF ANY EQUIPMENT AT SITE. PV-6+ EQUIPMENT SPECIFICATIONS DC SYSTEM SIZE:8A 6 KWDC
<br /> • BOXES
<br /> CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER
<br /> OXES AS REQUIRED AC sysrEM size 6.00 Kwnc
<br /> PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION. . ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED PROJECT SITE REVISIONS
<br /> • CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS ACCORDING TO [NEC 690.8 (A)(1)&(B)(1)], [NEC 240] [NEC ! ' -
<br /> AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER DESCRIPTION DATE REV
<br /> BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION P FOR MULTIPLE CONDUCTORS
<br /> ALL
<br /> • ALL
<br /> AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE
<br /> CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL SHALLLL BEE DERATED ACCORDING TO [NEC TABLE 310.15
<br /> CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT
<br /> (B)(2)(C)] BLACK ONLY" Signature with Seal
<br /> COMPENSATION. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C
<br /> • DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL, RATED, WET AND UV RESISTANT, AND UL LISTED RATED FOR
<br /> FLOORS, ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST. 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT
<br /> • THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND WIRE FROM SHARP EDGES
<br /> COMPLETION OF THE WORK WITH APPROVED MATERIALS.
<br /> • 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH DATE:08/10/2021
<br /> THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR
<br /> • NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE IDENTIFIED BY OTHER EFFECTIVE MEANS PROJECT NAME&ADDRESS
<br /> ARCHITECT. . ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE
<br /> • CONTRACTOR SHALL OBTAIN BUILDING PERMIT. NO WORK TO START UNLESS BUILDING CIRCUIT PROTECTION
<br /> PERMIT IS PROPERLY DISPLAYED. . VOLTAGE DROP LIMITED TO 2%
<br /> • ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE . NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE `
<br /> WITH THE REQUIREMENTS OF THE WA BUILDING CODE, THE DEPARTMENT OF
<br /> ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES. COLOR CODED AS FOLLOWS: DC POSITIVE- RED (OR MARKED 4 C)RED), DC NEGATIVE-GREY(OR MARKED GREY) _ C)• IT IS ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL i �
<br /> _
<br /> PARTIES AND WITH MINIMUM INTERFERENCE TO THE OCCUPANTS WITHIN THE BUILDING. • POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR i w W O
<br /> THE OWNER'S DIRECTIONS IN THIS REGARD SHALL BE FULLY COMPLIED WITH. CODED: DC POSITIVE- GREY(OR MARKED GREY), DC J LLI � CNp o
<br /> NEGATIVE- BLACK(OR MARKED BLACK) Pv-o HOUSE PHOTO scALE:Nrs J U 0 p-)
<br /> • ALL EXPOSED PLUMBING, HVAC, ELECTRICAL DUCTWORK, PIPING AND CONDUITS ARE TO • AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE O z W Q C)
<br /> BE PAINTED BY GENERAL CONTRACTOR. A OR L1- BLACK, PHASE B OR L2- RED, PHASE C OR L3- BLUE, of LU
<br /> • THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE NEUTRAL-WHITE/GRAY CD 0
<br /> c�
<br /> LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE. PROJECT SITE IUD
<br /> • THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS, z U) Q I j o
<br /> CERTIFICATIONS, ETC.AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES. Q W ti (]� '
<br /> it
<br /> • CONTRACTORS SHALL OBTAIN FIRE CERTIF. UPON COMPLETION OF WORK. D ti � Z
<br /> ELECTRICAL NOTES: I U) W d
<br /> THE EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE INSTALLED ONLY BY QUALIFIED PEOPLE. A QUALIFIED PERSON IS Q
<br /> • ONE WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT AND INSTALLATIONS
<br /> AND HAS RECEIVED SAFETY TRAINING TO RECOGNIZE AND AVOID THE HAZARDS INVOLVED. (NEC 690.4(C), NEC 2017) 717 Laurel Dr, Everett,
<br /> • LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. FOR A LINE SIDE TAP
<br /> CONNECTION, UTILITY NEEDS TO BE NOTIFIED WELL IN ADVANCE TO COORDINATE BUILDING ELECTRICAL SHUT OFF. WA 98201, USA
<br /> • NEW CONDUIT ROUTING SHOWN IS ESSENTIALLY SCHEMATIC. SUBCONTRACTOR SHALL LAY OUT RUNS TO SUIT FIELD CONDITIONS AND THE PORT GARDNER
<br /> COORDINATION REQUIREMENTS OF OTHER TRADES. SHEET NAME
<br /> • ARRAY WIRING SHOULD NOT BE READILY ACCESSIBLE EXCEPT TO QUALIFIED PERSONNEL. COVER PAGE
<br /> • ALL EXTERIOR CONDUIT, FITTINGS,AND BOXES SHALL BE WATERTIGHT AND APPROVED FOR USE IN WET LOCATIONS. (NEC 690), NEC 2017.
<br /> • WIRING METHODS FOR PV SYSTEM CONDUCTORS AREN'T PERMITTED WITHIN 10 IN. OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE LOCATED
<br /> DIRECTLY BELOW THE ROOF SURFACE THAT'S COVERED BY PV MODULES AND ASSOCIATED EQUIPMENT WIRING i SHEET SIZE
<br /> • BACK-FED BREAKER MUST BE AT THE OPPOSITE END OF BUS BAR FROM THE MAIN BREAKER OR MAIN LUG SUPPLYING CURRENT FROM THE UTILITIES. ANSI B
<br /> • ALL CONDUCTORS AND WIRE TIES EXPOSED TO SUNLIGHT ARE LISTED AS UV RESISTANT.
<br /> • CONTRACTOR SHALL FOLLOW ALL ELECTRICAL EQUIPMENT LABELING REQUIREMENTS IN NEC 690 11" X 17"
<br /> • PV SOURCE, OUTPUT AND INVERTER CIRCUITS SHALL BE IDENTIFIED AT ALL POINTS OF TERMINATION, CONNECTION, AND SPLICES. THE MEANS OF ID SHEET NUMBER
<br /> CAN BE SEPARATE COLOR CODING, MARKING TAPE, TAGGING ETC. (NEC 690.4), NEC 2017. PV-o VICINITY MAP SCALE:NTs
<br /> • MEASURE THE LINE-TO-LINE AND LINE-TO-NEUTRAL VOLTAGE OF ALL SERVICE ENTRANCE CONDUCTORS PRIOR TO INSTALLING ANY SOLAR �\V�_0
<br /> EQUIPMENT. THE VOLTAGES FOR THE 240VAC RATED.