Laserfiche WebLink
NEUDORFER <br />ENGINEERS <br />Supply Air Terminal Unit Test Data <br />Project No. <br />2023-0139 <br />Project I.D. <br />Snohomish County Court House <br />Test Date <br />9-4-2024 <br />Tested By <br />Dwight Hammack <br />Area Served <br />Trial Courtroom <br />Equipment I.D. <br />TU-3-7 <br />Terminal Unit Data <br />Flow Spec I + 10% 10% <br />Manufacturer <br />Nailor <br />Model Number <br />D3230 <br />Terminal Unit Type <br />Dual -Duct <br />Calibration Method <br />Sum of GRID Readings <br />Unit Inlet Size <br />12"/10" <br />K Factor <br />1.659(2.213) <br />Control Address <br />8.00 <br />Application Number <br />Johnson Controls <br />Terminal Unit Airflow Test Data <br />Airflow Setting (CFM) <br />Specified / Actual <br />Airflow Setting (CFM) <br />Specified / Actual <br />Cooling Maximum Airflow <br />1260 / 1210 <br />Cooling Minimum Airflow <br />0 / 0 <br />Heating Maximum Airflow <br />720 / 740 <br />Heating Minimum Airflow <br />0 / 0 <br />Grille, Register, Diffuser Test Data <br />Cold Deck Outlet Summary Instrument Used Flowhood Flow Spec + 10% - 10% <br />GRID <br />No. <br />Area Served <br />Type <br />Size <br />AK <br />Design Airflow <br />Initial Airflow <br />Final Airflow <br />Notes <br />FPM <br />CFM <br />CFM <br />% <br />FPM <br />CFM <br />I % <br />1 <br />Court Room <br />SG <br />4'-2" <br />1.00 <br />210 <br />185 <br />88% <br />210 <br />100% <br />2 <br />Court Room <br />SG <br />4'-2" <br />1.00 <br />210 <br />165 <br />79% <br />220 <br />105% <br />3 <br />Court Room <br />SG <br />4'-2" <br />1.00 <br />210 <br />235 <br />112% <br />200 <br />95% <br />4 <br />Court Room <br />SG <br />4'-2" <br />1.00 <br />210 <br />300 <br />143% <br />195 <br />93% <br />5 <br />Court Room <br />SG <br />4'-2" <br />1.00 <br />210 <br />335 <br />160% <br />195 <br />93% <br />6 <br />Court Room <br />SG <br />4'-2" <br />1.00 <br />210 <br />310 <br />148% <br />190 <br />90% <br />Total Cold Deck Supply Airflow <br />1260—T <br />1530 <br />1 121 % <br />1210 <br />1 96% <br />Project 2023-0139 Page 6 of 25 <br />