Laserfiche WebLink
NEUDORFER <br />ENGINEERS <br />Supply Air Terminal Unit Test Data <br />Project No. <br />2023-0139 <br />Project I.D. <br />Snohomish County Court House <br />Test Date <br />9-4-2024 <br />Tested By <br />Dwight Hammack <br />Area Served <br />Jury Room <br />Equipment I.D. <br />TU-3-26 <br />Terminal Unit Data <br />Flow Spec I + 10% 10% <br />Manufacturer <br />Nailor <br />Model Number <br />D3230 <br />Terminal Unit Type <br />Dual -Duct <br />Calibration Method <br />Sum of GRID Readings <br />Unit Inlet Size <br />6"/6" <br />K Factor <br />2.173(0.99) <br />Control Address <br />18.00 <br />Application Number <br />Johnson Controls <br />Terminal Unit Airflow Test Data <br />Airflow Setting (CFM) <br />Specified / Actual <br />Airflow Setting (CFM) <br />Specified / Actual <br />Cooling Maximum Airflow <br />400 / 425 <br />Cooling Minimum Airflow <br />0 / 0 <br />Heating Maximum Airflow <br />100 / 105 <br />Heating Minimum Airflow <br />0 / 0 <br />Grille, Register, Diffuser Test Data <br />Supply Outlet Summary Instrument Used Flowhood Flow Spec + 10% - 10% <br />GRID <br />No. <br />Area Served <br />Type <br />Size <br />AK <br />Design Airflow <br />Initial Airflow <br />Final Airflow <br />Notes <br />FPM <br />CFM <br />CFM <br />% <br />FPM <br />CFM <br />I % <br />1 <br />Jury Room <br />CD <br />10x10 <br />1.00 <br />175 <br />185 <br />106% <br />195 <br />111% <br />2 <br />Jury Room <br />CD <br />10x10 <br />1.00 <br />175 <br />165 <br />94% <br />175 <br />100% <br />1 <br />3 <br />Hallway <br />CD <br />6x6 <br />1.00 <br />50 <br />75 <br />150% <br />55 <br />110% <br />Total Supply Airflow <br />400 <br />425 <br />106% <br />425 <br />106% <br />General Notes <br />�No_te(l) I The balancing damper is full open. <br />Project 2023-0139 Page 8 of 25 <br />