" ° `TI Fli System Power Requirements <br /> by Honeywen <br /> Notifier NFS-320 Fire Alarm Control Panel <br /> Protected Premises: ZAP ENERGY Date: 6/29/21 <br /> Address: 5901 23RD DRIVE WEST SUITE 100-101 <br /> City: EVERETT State: WASHINGTON Zip: 98203 <br /> Prepared By: SSI Phone: <br /> Address: Email: <br /> City: State: Zip: <br /> AC Branch Current Requirements 5.00 AMPS @ 120 VAC <br /> Current required by source to power the fire <br /> alarm system. <br /> Primary Standby Load 0.44 Amps <br /> Current load on the primary power supply during <br /> non-alarm conditions. <br /> Primary Alarm Load 4.03 Amps <br /> Current load on the primary power supply during <br /> alarm conditions. <br /> Secondary Load Requirements 14.29 Amp Hours <br /> Total Secondary Load from the calculation table below. <br /> Current Draw I I Time (hours) I Total (AH) <br /> Secondary Standby Load Required Standby Time <br /> 0.482 A 24 hours 11.56 <br /> Secondary Alarm Load Required Alarm Time(hours) <br /> 4.066 A x 0.084 hours 0.34 <br /> Total Secondary Load 11.91 <br /> Derating factor x 1.2 <br /> Secondary Load Requirements(Amp Hours) 14.29 AH <br /> Page 1 of 1 <br />