• • <br /> Mr. Matt Prevost <br /> Mr. Racks, LLC <br /> Plan Check Number: B2103-021, First Building Review <br /> March 16, 2019 <br /> Architectural <br /> 1. The plan on Sheet 3 shows egress routes to a single exit that has a sliding door. The total area <br /> of the tenant space is 6,600 SF per Sheet 1, and includes both storage and office areas. Based <br /> on an occupant factor of 500 SF/person for storage per IBC Table 1004.5, the minimum <br /> occupant load exceeds 10; this will increase based on the area designated for office use. The <br /> space requires a side-hinged exit door. See IBC Section 101.1.2. <br /> 2. The new racks will cause a visual obstruction for the exit sign shown on Sheet 2. An additional <br /> exit sign with a direction arrow should be provided at least six feet from the east exterior wall, <br /> but not less than required to be visible from the north and south ends of the space when <br /> standing along the racks. See IBC Section 1013.1. <br /> 3. Continuing with the previous comment, both exit signs should specify a minimum 90-minute <br /> back-up power supply. The type of power should be specified in the drawings. See IBC Section <br /> 1013.6.3. <br /> Structural <br /> 1. The structural design has been performed per ASCE 7-10 Section 15.5.3, which references a <br /> response modification factor of R=4. However, the design also considers a higher factor of R=6 <br /> for the moment frame direction. This is only permitted if documentation is submitted per <br /> Section 15.5.3.5 substantiating the use of a higher value. Note that these type of racks are <br /> typically not designed to perform better than ordinary moment frames, which are limited to a <br /> factor of R=3.5. The details do not comply with the requirements for special moment frames <br /> per AISC 341-10. The response factor should be reduced to R=4 for both directions. See IBC <br /> Sections 1613.1 and 1901.2. <br /> 2. Continuing with the previous comment, the increased response modification factor will increase <br /> the anchor design loads by 50% for one direction. Page 1 of the structural calculations <br /> indicates a demand-to-capacity ratio for the base anchors of DCR=1.09/1.2=0.91 (i.e., anchor <br /> is 91% utililized, only 9% reserve capacity). The anchors will be overstress by a 50% increase. <br /> The design should be revised. See IBC Section 1604.1. <br /> 3. Continuing with the previous two comments, the anchor design considers an overstrength <br /> factor of c2=2.0, as required by ACI 318-14 Sections 17.2.3.4.3(d) and 17.2.3.5.3(c). However, <br /> the factor for both special and ordinary moment frames is 5n=3.0, increasing the load by 50%. <br /> The design should be revised. See IBC Section 1604.1. <br /> 4. The calculations of the anchor capacities in page 1 of the structural calculations is not clear, <br /> appears to be the base values from the ICC Evaluation Report ESR-3037. It is not clear if the <br /> capacities all reduction factors. Calculations substantiating the values should be submitted <br /> submitted for review. The use of the free proprietary software"Anchor Designer"by Simpson <br /> Strong-Tie is recommended. See IBC Section 1604.1. <br /> v 3200 Cedar Street 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 3 <br />