• • <br /> 11. It appears that the existing wall coverings are being removed from the wall surfaces, which may also <br /> include the interior walls. The removal and replacement of the wall covers from all walls and ceilings <br /> should be specified. Details should be provided as needed. See Section R106.1.1. INDICATED ON <br /> SHT. A-8.0,"TYP. BLDG. SECTION". <br /> 12. Continuing with the previous comment, the south exterior wall of the building appears to be located <br /> within 5 feet of the south property line, resulting in a fire separation distance (FSD) of less than 5 <br /> feet. If the interior wall covering is removed, a minimum 5/8-inch Type"X"GWB is required to <br /> comply with Table R302.1(1). INDICATED ON SHT. A-7.0 FLOOR PLANS. <br /> 13.The reframed lower roof in Section C/S2 appears to have a slope of less than 2:12. Asphalt shingles <br /> are not permitted. See Section R905.2. NOTES ON SHT. A-11.0. ROOFING TO BE THERMOSET <br /> SINGLE-PLY ROOFING, APPLIED PER MANUFACTURER'S INSTRUCTIONS. <br /> Structural <br /> 1. The submitted drawings do not provide sufficient documentation for the proposed structural <br /> modifications to the existing building. Revised structural drawings should be submitted <br /> providing additional clarification of the proposed construction in the impacted areas, <br /> including but not limited to framing plans, sections, details, construction schedules, fastening <br /> schedules, materials requirements, general notes, special inspection requirements, etc. The <br /> drawings should substantiate compliance with the prescriptive requirements of the IRC. <br /> Additional comments are provided below. See IRC Sections R106.1.1 and R301.1. <br /> 2. The project appears to involve structural modifications that do not comply with the <br /> prescriptive limitations of the IRC. Structural calculations substantiating the design should <br /> be submitted for review. See Section R301.1.3. SEE SHT. A-7.0, A-8.0, &A-9.0 AND <br /> SUBMITTED STRUCTURAL CALCULATIONS. <br /> 3. The reconstruction of the stairway requires modifications to the low roof, second floor framing, and <br /> the north exterior second-story wall. See Sections R106.1.1 and R301.1. The following comments <br /> should be addressed: <br /> a. Construction for the load bearing wall adjacent to the stairs should be specified. The wall should <br /> have a PT-sill plate per Section R317 and bear on a foundation complying with Section R403. <br /> The wall should be positively connected at the top and bottom to the supporting structure. <br /> ORIGINAL WALL NOT MODIFIED. <br /> b. Additional framing requirements for the new 4x8 beam, including but not limited to supporting <br /> vertical framing, foundations, and connections. SEE SHT A-11.0. <br /> c. The portion of the exterior wall over the stairway has not been refrained to provide a new load <br /> path. NO CHANGES REQUIRED. <br /> d. The proposed modifications to the low roof appear to be shown schematically only. The framing <br /> should be clarified, including providing sections and details. DETAILS SHOWN ON SHT. A-11.0 <br /> 4. Details for the construction of the new walls should be included. The details should specify <br /> connections for the top and bottom framing plates to the existing structure. See IRC <br /> Sections R106.1.1 and R301.1. <br /> Alex Dariotis,CPM WOODWAY HOMES.INC. Dean Dariotis,AIA <br /> PHONE 425-773-4356 PHONE 425 772-3167 <br /> Li ) 5 <br />