SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 <br />DATE: 5/17/2024\CALCULATIONS\HYDRAULIC CALC'S\40-22 TORIT BOOTH CALCS.SDF <br />JOB TITLE: 40-22 Torit Booth <br />Pipe Tag K-fac Add F1 Add F1 To Fit: L C (Pt) <br />Frm Node E1 (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) <br />To Node E1 (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) <br />Pipe: 96 0.0 0.0 Fire Pump Rating Avail. Req'd. <br />VF -11.6 0.1 405.7 VD gpm: 1500.0 405.9 405.9 <br />VE -11.6 25.8 405.7 psi: 75.0 80.3 25.7 <br />User Defined Five Point Pump Curve: <br />gpm: 83.0 73.0 68.0 61.0 52.0 <br />psi: 83.0 73.0 68.0 61.0 52.0 <br />Pipe: 97 Source 0.0 1.00 140 0.0 <br />SOURCE -11.6 0.1 405.7 VE 8.000 ---- 0.00 -0.0 <br />VF -11.6 0.1 405.7 7.981 1.00 0.001 0.0 <br />NOTES (HASS): <br />(1) Calculations were performed by the HASS 2023 D computer program <br />in accordance with NFPA (2020) <br />under license no. 65689119 granted by <br />HRS Systems, Inc. <br />208 Southside Square <br />Petersburg, TN 37144 <br />(931) 659-9760 <br />(2) The system has been calculated to provide an average <br />imbalance at each node of 0.011 gpm and a maximum <br />imbalance at any node of 0.146 gpm. <br />(3) Total pressure at each node is used in balancing the system. <br />Maximum water velocity is 10.4 ft/sec at pipe 30. <br />(4) The Minimum pump suction pressure under maximum calculated demand is 0.10 (psi) <br />(5) Items listed in bold print on the cover sheet <br />are automatically transferred from the calculation report. <br />(6) Available pressure at source node SOURCE under full flow conditions is <br />65.16 psi with a flow of 713.92 gpm. <br />(7) PIPE FITTINGS TABLE <br />HASS Pipe Table Name: standard <br />