Laserfiche WebLink
Static city water pressure 69 psi <br />Churn suction pressure 66 psi Churn discharge pressure 149 psi <br />Was 300 GPM flow conducted? Yes ® No ❑ <br />Hose size: 2.5 inch Tip size: 2.5 inch Hose length: 25 ft <br />Pitot reading: 9/9/9 GPM: 1524 <br />Was pump run for 10 minutes flowing? Yes ® No ❑ <br />Were all fire pumps tested? Yes ® No ❑ <br />Flow Chart <br />NO. & SIZE OF <br />NOZZELS <br />PUMP PRESSURE <br />PITOT <br />PRESSURE <br />FLOW <br />RPM <br />VOLTS <br />AMPS <br />COMMENTS <br />DISCHG. <br />SUCT. <br />NET <br />Churn <br />149 <br />66 <br />83 <br />- <br />0 <br />1770 <br />3 — 21/Z" HM <br />137 <br />64 <br />73 <br />9/9/9 <br />1524 <br />1769 <br />4 — 2 Y2" HM <br />111 <br />59 <br />52 <br />12/12/11/11 <br />2246 <br />1770 <br />Problems found: <br />Corrections made: <br />Date corrections made: By: <br />THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY <br />TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED <br />IN THIS REPORT; IS CONSISTANT WITH MANUFACTURER'S REQUIREMENTS; <br />AND ALL CORRECTIONS ARE TO BE MADE BY OWNER. <br />Signature of Tester: <br />Agency: Capitol Pump Resources Phone: (360) 493-1830 <br />Witnessed By: <br />HC; kw templates <br />