Laserfiche WebLink
NI`T1 <br /> Hilti PROFIS Engineering 3.0.93 <br /> www.hilti.com <br /> Company: Page: 3 <br /> Address: Specifier: <br /> Phone I Fax: I E-Mail: <br /> Design: Boeing NL-Emergency Generator Anchorage Date: 4/5/2024 <br /> Fastening point: <br /> 2 Proof I Utilization (Governing Cases) <br /> Design values[lb] Utilization <br /> Loading Proof Load Capacity PN/Itv[%] Status <br /> Tension Concrete Breakout Failure 1,613 4,193 39/- OK <br /> Shear Steel Strength 1,704 6,668 -/26 OK <br /> Loading PN Pv Utilization(3N,v[%] Status <br /> Combined tension and shear loads 0.385 0.256 5/3 31 OK <br /> 3 Warnings <br /> • Please consider all details and hints/warnings given in the detailed report! <br /> Fastening meets the design criteria! <br /> Input data and results must be checked for conformity with the existing conditions and for plausibility! III <br /> PROFIS Engineering(c)2003-2024 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan <br /> 93 <br /> lot Zo <br />