Laserfiche WebLink
10/26/2023 ENGINEERING QC INSPECTION FORM Page 1 of 2 <br /> Inspection PROJECT TITLE: Boeing 40-03 &40-03 Rack Relocation BUILDING # <br /> Layout 40-03 <br /> 30% REVIEWED BY: Robert. A. Marmaduke PE, PEng <br /> 60% <br /> 90% DISCIPLINE Arch. Struct. x Civil Due back date: <br /> Final X Mech. Elect. Other N/A <br /> Dwg./pars. No. COMMENTS ACTION TAKEN <br /> S700 Detail 1 Reid Middleton calls min (4) 3/8"D. Hilti KB-TZ2 Anchors each post baseplate <br /> Calcs Pg 14 with 3" nominal embedment <br /> 250CT23 Observed drilling, hole cleaning, (4) 1/2"D. x 3-3/4" anchor bolt insertion and Performed to specs <br /> torquing at post base. <br /> - VEHICULAR I <br /> - `- TRAFFIC I <br /> w ,001, ! - <br /> 6�fi Kv <br /> 20x N&TZ2 <br /> 12210250 <br />