• a <br /> W7066787 MAZAK INSTALL•FOUNDATION SKETCHES FOR CALCULATIONS <br /> L= 12.5 Ft <br /> • <br /> B=833Ft <br /> THICKNESS= 18" <br /> FOOTING DIMENSIONS <br /> Ve=966K <br /> W Mazak=47.7 K , <br /> @ 6.84 Ft <br /> above TF <br /> `I• W Ftg=23.4 K <br /> W <br /> 379 PSF PRESSURE ON SOIL 227 PSF PRESURE <br /> 987 SF ON SOIL 113 PSF <br /> SOIL PRESSURE DISTRIBUION•LONGITUDINAL <br /> SOIL PRESSURE DISTRIBUTION <br /> TRANSVERSE <br /> Mu=8.70K-FT W <br /> w(D)=225 PLF(FOR 1 FT STRIP) <br /> w(L)=458 PLF(FOR 1 FT STRIP) <br /> FLEXURAL MOMENT(SHORT DIMENSION) <br /> 0 0 o 0 #6 @ 12"O.C. <br /> EA WAY <br /> o n n n n TOP& BOTTOM <br /> FOOTING REINFORCEMENT <br /> 3/q <br />