MODULE SPECIFICATIONS REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS <br /> RATED POWER(STC) 420 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 11.8 A AC <br /> MODULE VOC 59.4 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 14.7 A AC <br /> MODULE VMP 50 V DC CITY EVERETT CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG BLUE RAVEN <br /> MODULE IMP 8.4 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A <br /> MODULE ISC 8.88 A DC ASHRAE EXTREME LOW TEMP(°C) -5 AMB.TEMP.AMP.CORRECTION= 1 <br /> VOC CORRECTION -0.24 %/'C ASHRAE 2%AVG. HIGH TEMP(-C) 26 ADJUSTED AMP_= 30 > 14.7 1403 N. Research Way <br /> VMP CORRECTION -0.24%/'C JUNCTION BOX TO MAX.SHORT CIRCUITCURRRENT(ISC)= 11.8 A AC Orem, UT 84097 <br /> SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR I CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 14.7 A AC 800.377.4480 <br /> W W W.BLU ERAVENSOLAR.COM <br /> ADJ. MODULE VOC @ ASHRAE LOW TEMP 63.7 V DC NUMBER OF MODULES PER MPPT 9 9 CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG <br /> CONFIDENTIAL-THE INFORMATION <br /> ADJ,MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 46.0 V DC DC POWER RATING PER CIRCUIT(STC) 3780 3780 CONDUCTOR RATING= 35 A HEREIN CONTAINED SHALL NOT BE <br /> TOTAL MODULE NUMBER 18 CONDUIT FILL DERATE= 1 USED FOR THE BENEFIT OF ANYONE <br /> EXCEPT BLUE RAVEN SOLAR NOR <br /> MICROINVERTER SPECIFICATIONS Enphase IQ7X Microinverters STC RATING OF ARRAY 7560 AMB.TEMP,AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR <br /> ----- - IN PART TO OTHERS OUTSIDE <br /> POWER POINT TRACKING(MPPT)MIN/MAX 53 - 64 V DC AC CURRENT @ MAX POWER POINT(IMP 11.8 11.8 ADJUSTED AMP.= 35 > 14.7 RECIPIENTS ORGANIZATION,EXCEPT <br /> MAXIMUM INPUT VOLTAGE 79.5VDC MAX.CURRENT(IMP X 1,25) 14.7375 14.7375 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 11.8AAC IN CONNECTION WITH THE SALE AND <br /> USE OF THE RESPECTIVE EQUIPMENT, <br /> MAXIMUM DC SHORT CIRCUITCURRENT 10 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 14.7 A AC WITHOUT THE WRITTEN PERMISSION <br /> MAXIMUM USABLE DC INPUT POWER 460 W MAX.COMB.ARRAY AC CURRENT(IMP) 23.6 CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG OF BLUE RAVEN SOLAR LLC. <br /> MAXIMUM OUTPUT CURRENT 1.31 A AC MAX.ARRAY AC POWER 5670W AC CONDUCTOR RATING= 35 A <br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 0.8 NABCEP <br /> MAXIMUM OUTPUT POWER 315 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. JRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED <br /> CEC WEIGHTED EFFICIENCY 9750% VRISE SEC. 1(MICRO TO JBOX) 32.4 12 Cu. 1.18 241.18 0.49% ADJUSTED AMP.= 28 > 14.7 <br /> VRISE SEC.2()BOX TO COMBINER BOX) 85 10 Cu. 2,55 242.55 1.06% COMBINER BOX TO INVERTER RATED AMPS= 23.6 A AC PV INSTALLATION <br /> AC PHOTOVOLTTIC MODULE MARKING(NEC 690.52) VRISE SEC_3(COMBINER BOX TO POI) 5 10 Cu. 0.30 240.30 0.12% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 29.48 A AC PROFESSIONAL <br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 4.02 244.02 1-68% CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG Scott Gurney <br /> #PV-011719-015866 <br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A <br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL NEC 690.54 CONDUIT FILL DERATE= 1 CONTRACTOR: <br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 23.6 A AC AMB.TEMP.AMP.CORRECTION= 1 BRS FIELD OPS <br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 29.5 800-377-4480 <br /> U U <br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z 00 Q <br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE _0 N <br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. OD <br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE M 1,-- CO <br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). QCC C (q LSD <br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G O L0 [-- <br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED <br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF Q b C LU W <br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. ILL. N N <br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z Y N <br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. -�e O C <br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND i O G C <br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS LLJ N z LL1 LLJ <br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. CC <br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE G _ I <br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O O LJJ W (j) <br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/81,ABOVE ��W W. � U >. >. <br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE 1� WAS f/� ~ U Of Vll U) <br /> INSTALLATION A ALL BE PROPER Y R PREP ED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF (OOF PV DC CONDUCTORS y ORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL 8.ENCLOSURES SHALL BE pf y�NC��� = N Cf) > V V <br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP A L �� C) gt W Q o <br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. r <br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHNrrHWN-2 INSULATED, 90°C RATED, <br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY: <br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND <br /> �p k S4072 <br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. �,o FG'/� R� '� Brendan FIIImOre <br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION F•Sq ,;1� <br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS �O1 I V <br /> PLOT DATE: <br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC <br /> GREEN <br /> F 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY <br /> R MARKED <br /> ICONDU T BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15 POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COOLOR CODED:GREY) <br /> 3.ALL R August 11, 2023 <br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) 2023 .08. 11 1 <br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER: <br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY <br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE 828444 <br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE <br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. • <br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, 16:35 :22 <br /> SHEET NAME: <br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING <br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151. E L EC CALLS <br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC 0 / 'O O' <br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. _ /V <br /> REVISION: PAGE NUMBER: <br /> 0 PV6 <br />