Laserfiche WebLink
Final Calculations : Hazen-Williams <br /> A-PEX Design Services Inc. Page 9 <br /> BENTON SQUARE BLDG A PLAN B GL- One Head Calculation (H.8) Date 1/30/2024 <br /> Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt <br /> to or Ftngs Pe ******* Notes ****** <br /> Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf <br /> 0.0 <br /> T.32 0.35 11.747 K Factor= 0.10 <br /> T.34 116 1.61 1 Utr 2.0 2.000 150 11.794 <br /> to 2.000 0.0 <br /> H.15 116 1.61 0.862 4.000 0.0020 0.008 Vel = 0.89 <br /> H.15 116 0.0 1 Utr 2.0 13.000 150 11.802 <br /> to 2.000 0.0 <br /> H.20 116 1.61 0.862 15.000 0.0021 0.032 Vel = 0.89 <br /> H.20 116 0.0 1 Utr 2.0 7.000 150 11.834 <br /> to 2.000 0.0 <br /> T.40 116 1.61 0.862 9.000 0.0021 0.019 Vel = 0.89 <br /> 0.0 <br /> T.40 1.61 11.853 K Factor= 0.47 <br /> T.39 116 1.68 1 Utr 2.0 5.000 150 11.828 <br /> to 2.000 0.0 <br /> T.37 116 1.68 0.862 7.000 0.0023 0.016 Vel = 0.92 <br /> 0.0 <br /> T.37 1.68 11.844 K Factor= 0.49 <br /> T.35 108 0.73 1 2.000 150 15.834 <br /> to 0.0 <br /> T.36 108 0.73 0.862 2.000 0.0005 0.001 Vel = 0.40 <br /> 0.0 <br /> T.36 0.73 15.835 K Factor= 0.18 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />