Laserfiche WebLink
Flow Summary - NFPA 2007 <br /> A-PEX Design Services Inc. Page 4 <br /> BENTON SQUARE BLDG A PLAN C GL-Two Head Calculation (H.11 & H.7) Date 1/30/2024 <br /> SUPPLY ANALYSIS <br /> Node at Static Residual Available <br /> Source Pressure Pressure Flow Pressure Total Demand Required Pressure <br /> STR 43.0 20 500.0 42.951 18.0 31.683 <br /> NODE ANALYSIS <br /> Pressure Discharge <br /> Node Tag Elevation Node Type at Node at Node Notes <br /> H.11 124.0 3 9.0 9.0 0.05 144 <br /> H.13 124.0 9.45 <br /> T.33 124.0 9.66 <br /> T.34 124.0 9.82 <br /> T.35 116.0 14.16 <br /> T.36 116.0 14.2 <br /> H.17 116.0 14.22 <br /> T.32 116.0 14.29 <br /> T.30 108.0 18.64 <br /> T.21 108.0 19.15 <br /> T.22 108.0 19.18 <br /> S.1 104.0 21.92 <br /> MTR 100.0 27.99 <br /> STR 100.0 31.68 <br /> H.7 124.0 3 9.01 9.0 0.05 144 <br /> T.19 124.0 9.51 <br /> T.20 116.0 14.06 <br /> T.24 116.0 14.18 <br /> T.28 116.0 14.21 <br /> T.29 116.0 14.23 <br /> T.26 108.0 18.63 <br /> H.3 124.0 9.63 <br /> T.18 124.0 9.7 <br /> HA 124.0 9.76 <br /> H.8 124.0 9.86 <br /> T.25 124.0 9.92 <br /> T.27 116.0 14.24 <br /> T.23 116.0 14.34 <br /> H.16 124.0 9.83 <br /> T.31 124.0 9.86 <br /> H.12 124.0 9.89 <br /> H.6 116.0 14.07 <br /> H.2 116.0 14.15 <br /> H.1 116.0 14.22 <br /> H.5 116.0 14.3 <br /> H.14 116.0 14.19 <br /> H.9 116.0 14.19 <br /> H.10 116.0 14.25 <br /> H.15 108.0 18.64 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />