Laserfiche WebLink
Flow Summary - NFPA 2007 <br /> A-PEX Design Services Inc. Page 4 <br /> BENTON SQUARE BLDG A PLAN B GL- One Head Calculation (H.8) Date 1/30/2024 <br /> SUPPLY ANALYSIS <br /> Node at Static Residual Available <br /> Source Pressure Pressure Flow Pressure Total Demand Required Pressure <br /> STR 43.0 20 500.0 42.973 13.0 26.226 <br /> NODE ANALYSIS <br /> Pressure Discharge <br /> Node Tag Elevation Node Type at Node at Node Notes <br /> H.8 124.0 4.9 7.04 13.0 0.05 256 <br /> T.27 124.0 7.39 <br /> T.28 124.0 7.52 <br /> T.31 116.0 11.67 <br /> T.34 116.0 11.79 <br /> T.33 108.0 15.94 <br /> T.26 108.0 16.57 <br /> S.1 104.0 18.74 <br /> MTR 100.0 24.2 <br /> STR 100.0 26.23 <br /> H.6 124.0 7.2 <br /> H.2 124.0 7.36 <br /> H.1 124.0 7.54 <br /> T.23 124.0 7.69 <br /> H.5 124.0 7.74 <br /> T.24 124.0 7.81 <br /> T.25 116.0 11.64 <br /> H.10 116.0 11.67 <br /> T.29 116.0 11.73 <br /> T.32 116.0 11.75 <br /> H.17 116.0 11.82 <br /> T.37 116.0 11.84 <br /> T.36 108.0 15.84 <br /> H.16 108.0 15.93 <br /> T.30 124.0 7.54 <br /> H.14 124.0 7.58 <br /> H.19 124.0 7.68 <br /> H.22 124.0 7.76 <br /> H.21 124.0 7.83 <br /> T.38 124.0 7.86 <br /> T.39 116.0 11.83 <br /> T.41 116.0 11.85 <br /> T.40 116.0 11.85 <br /> T.35 108.0 15.83 <br /> H.7 124.0 7.82 <br /> H.11 124.0 7.83 <br /> H.13 124.0 7.84 <br /> H.18 124.0 7.85 <br /> HA 116.0 11.65 <br /> H.3 116.0 11.66 <br /> H.9 116.0 11.66 <br /> H.12 116.0 11.74 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />