Laserfiche WebLink
Final Calculations : Hazen-Williams <br /> A-PEX Design Services Inc. Page 9 <br /> BENTON SQUARE BLDG A PLAN B GL-Two Head Calculation (H.6 & H.2) Date 1/30/2024 <br /> Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt <br /> to or Ftngs Pe ******* Notes ****** <br /> Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf <br /> H.12 116 0.0 0.75 Utb 17.0 3.000 150 14.786 <br /> to 17.000 0.0 <br /> T.32 116 0.5 0.671 20.000 0.0008 0.017 Vel = 0.45 <br /> 0.0 <br /> T.32 0.50 14.803 K Factor= 0.13 <br /> T.34 116 2.07 1 Utr 2.0 2.000 150 14.919 <br /> to 2.000 0.0 <br /> H.15 116 2.07 0.862 4.000 0.0032 0.013 Vel = 1.14 <br /> H.15 116 0.0 1 Utr 2.0 13.000 150 14.932 <br /> to 2.000 0.0 <br /> H.20 116 2.07 0.862 15.000 0.0034 0.051 Vel = 1.14 <br /> H.20 116 0.0 1 Utr 2.0 7.000 150 14.983 <br /> to 2.000 0.0 <br /> T.40 116 2.07 0.862 9.000 0.0033 0.030 Vel = 1.14 <br /> 0.0 <br /> T.40 2.07 15.013 K Factor= 0.53 <br /> T.39 116 2.24 1 Utr 2.0 5.000 150 14.964 <br /> to 2.000 0.0 <br /> T.37 116 2.24 0.862 7.000 0.0039 0.027 Vel = 1.23 <br /> 0.0 <br /> T.37 2.24 14.991 K Factor= 0.58 <br /> T.35 108 0.99 1 2.000 150 19.422 <br /> to 0.0 <br /> T.36 108 0.99 0.862 2.000 0.0010 0.002 Vel = 0.54 <br /> 0.0 <br /> T.36 0.99 19.424 K Factor= 0.22 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />