Laserfiche WebLink
An IL Degenkolb <br /> 3. Comment 3: Framers neglected to double the rafters at each side of the chimney. Is the <br /> existing single rafter each side acceptable? <br /> Response 3: This is acceptable, structurally. <br /> 4. Comment 4: Are the seated/notched rafters at deck overhang roof ridge acceptable? <br /> Response 4: This is acceptable, structurally. <br /> 5. Comment S: Clarification of call-out note on plans S2.2 "CS16 STRAP x 1'--6"LONG <br /> CONNECTING FROM HIP RAFTER TO STUD PACK BELOW, TYP(4) <br /> PLACES" This connection exists outside the exterior walls of the building and there is no <br /> stud pack below. What needs to happen here or can this note be eliminated? <br /> Response 5: Provide the straps on either side of the hip rafter to the beam below. <br /> Please feel free to contact us should you have any questions. <br /> Very truly yours, <br /> DEGEN'KOLLB ENGINEERS <br /> Michael Bramhall <br /> i <br /> �pjvREWe <br /> SOON A L�•. <br />