GENERAL NOTES Otak <br /> 1. CONTRACTOR SHALL VERIFY STATIC WATER PRESSURE OF 88 PSI %A <br /> ' AT EXISTING WATER METER/ DOUBLE CHECK VALVE ASSEMBLY. <br /> NOTIFY OWNER OF ANY DISCREPANCIES PRIOR TO COMMENCING <br /> WITH INSTALLATION. Otak Architects,Inc. <br /> 2. AN EXISTING IRRIGATION SYSTEM EXISTS ON SITE. SALVAGEABLE 808 SW Third Avenue,Suite 300 <br /> PORTIONS OF THE EXISTING MAINLINE AND LATERAL LINES MAY Portland,OR 97204 <br /> BE USED BY THE CONTRACTOR WHEN POSSIBLE. main 503.287.6825 <br /> 3. EXISTING IRRIGATION STATIONS MAY BE UTILIZED AS LONG AS www.otak.com <br /> REPAIRS ARE MADE AND THE SYSTEM IS FULLY OPERATIONAL <br /> 4. IRRIGATION CONTROLLER SHALL BE LOCATED IN MECHANICAL OF WAS , <br /> ���'� SENSOR AND CAN UTILIZE EXISTING WIRE SLEEVE AND RAIN Q2P,NM3AY�ysch4'aCA <br /> "�-r 5. SYSTEM OPERATING PRESSURE 30-40 PSI. q a '��I�JQJ✓ll� Z <br /> �f 6. LATERAL PIPE SIZING SHALL BE S" FOR FLOWN UNDER 10 GPM. m ��%� • <br /> LATERAL PIPE SIZING FOR FLOWS GREATER THAN 10 GPM IS _L <br /> /..- LABELED ON PLANS. CONTRACTOR SHALL VERIFY LATERAL PIPE G�/ '-- 'I <br /> 'ti-<, ' I • SIZING REQUIREMENTS IN FIELD PER THE PVC PIPE SCHEDULE <br /> / SHOWN ON IRRIGATION LEGEND. •wy. -- {,��j. <br /> y �o 011 tP.�= <br /> „,...\ IRRIGATION NOTES �'`DSCA� <br /> \ (�� •,� STAMP <br /> • <br /> �' 1 WALL MOUNT IRRIGATION CONTROLLER <br /> / \ \ O &WIRING, SEE DETAIL SHEET L3.10 <br /> _ �<� \ \\ p II <br /> O CONTROL VALVE ASSEMBLY, <br /> -_"� �� SEE DETAIL SHEET L3.10 <br /> 11 <br /> \ O QUICK COUPLER, <br /> SEE DETAIL SHEET L3.11 <br /> O BALL VALVE, <br /> e ;I SEE DETAIL SHEET L3.11 <br /> • 1 <br /> // %� O TYPICAL TRENCHING- SEE DETAIL EET 1 LANDSCAPE, CONSULTANT <br /> kill 4 <br /> DIRECT BORE ALL IRRIGATION <br /> 1*0 0 r� 6O TYPICAL TRENCHING UNDER PAVEMENT, Cr)v <br /> SLEEVES TO PARKING AREA 1" SEE DETAIL SHEET L3.11 <br /> PLANTERS(TYP) Z <br /> ......_........_....-- a .._- O POP-UP HEL SHEET <br /> SEE DECAH L3.11 CW <br /> 111 <br /> \ - O MANUAL DRAIN VALVE, G <br /> - • <br /> \ \ _-- SEE DETAIL SHEET L3.11 <br /> /, " -- --- , SLEEVE FOR IRRIGATION PIPE&WIRE <br /> O <br /> -\ r( SEE DETAIL SHEET L3.11 O <br /> ri EQUIPMENT LEGEND Ce <br /> -- <br /> - -- HUNTER MP800SR-90 ROTARY SPRAY r <br /> \ \ \\ I�' 1" 11' 0 NOZZLE 6'-16' ON PRO-SPRAY PRS30 6" <br /> \ ----- "-- <br /> II Op POP-UP BODY(0.23-0.42 GPM) <br /> \ 1-114 <br /> ,- a 11 HUNTER MP800SR-360 ROTARY SPRAY 11 <br /> i - ------- C '•,I POPNOZ LE P BODY(0.78 GPM)PRO-SPRAY PRS30 6" V <br /> 11 <br /> al HUNTER MPSS530 SIDE STRIP ROTARY <br /> Z <br /> / \\ _/ • SPRAY NOZZLE ON PRO-SPRAY PRS30 Q <br /> \ v - ---. D _ RE ALL IRRIGATION ,, <br /> SLEEVES DIRECT OTO PARKINGAREA--J\ 6"POP-UP BODY(0.44 GPM) <br /> /7. jam \ I PLANTERS(TYP) li\ HUNTER MPLCS515 LEFT CORNER STRIP <br /> \\ \ II • C ROTARY SPRAY NOZZLE ON PRO-SPRAY PRS30 <br /> ' <br /> - li-- --- \ V 6"POP-UP BODY(0.22 GPM) <br /> 4" <br /> \ HUNTER MPRCS515 RIGHT CORNER STRIP <br /> \ ; <br /> _..... _._... -.... _. ROTARY SPRAY NOZZLE ON PRO-SPRAY PRS30 <br /> • <br /> \ • <br /> O ' ll\ 6"POP-UP BODY(0.22 GPM) Z <br /> \ _...._.._... .. ....-_.-- \ • HUNTER MSBN-10H MULTI-STREAM <br /> . BUBBLER NOZZLE ON PRO-SRAY <br /> iI - PRS30 6"POP UP BODY(1.OP PM) Q <br /> ll\ HUNTER MSBN-50H MULTI-STREAM Q <br /> O 0 • _._ \ BUBBLER NOZZLE ON PRO-SPRAY <br /> PRS30 6"POP-UP BODY(0.5 GPM) <br /> 1 • <br /> �8 --- -- --------- DISLEEVES-TO PARKING T BORE ALL IRRIGATION <br /> IN III <br /> • NG AREA - -� --- \ r� POINT OF CONNECTION: <br /> O AT EXISTING WATER METER/ W Z <br /> 9 PLANTERS(TYP) <br /> Q <br /> ,i ,z„ r ® (� 0 -._) \ DOUBLE CHECK VALVE ASSEMBLY �/ Q <br /> •, INSTALL IRRIGATION VALVES _ • ---o a __. ,al• PROVIDE MASTER VALVE: BUCKNEN)SUPERIOR Lim 0 co <br /> `•^ 1i• 0 `pV/ t V� - -- - -, O\ MODEL 3100150 (NORMALLY OPEN) U <br /> \ � - \ PROVIDE FLOW SENSOR: RAIN BIRD Z GO <br /> � O�j �, ., // ? ���I MODEL F51508 O rn Z <br /> OUTSIDE OF R-TANK STORMWATER- Una - <br /> - DETENTION SYSTEM FOOTPRINT. IRRIGATION CONTROLLER: 16 STATIONS <br /> .. \ 1-1/a" • (WALL MOUNT) WITH RAIN SENSOR re 0 G' �' <br /> z / DIRECTORE ALL IRRIGATION �•0 C-2 INSTALL IRRIGATION HEADS AND 14.0 C-3 -- 16.0 C+-4------ 14,� _5 C----- --G-B <br /> RAIN BIRD ESPLXMSM12 WITH ADDITIONAL Q <br /> o S EEVES'TO PARKING AREA LATERAL LINE IN SOIL ABOVE <br /> • 4 STATION MODULE =W <br /> 4 PLANTERS(TYP) GPM �• R-TANK STORMWATER DETENTION GPM 1' c GPM 1` GPM 1` GPM 1• • D MANUAL DRAIN VALVE: LLJp W <br /> tY <br /> \ \ FOOTPRINT 1-- <br /> 0 <br /> C > <br /> J /; 1-1/4•:_ I• • �- - lie <br /> r-- CHAMPION 100RS-150Y(1-1/2" G I�W <br /> c //� \ INSTALL IRF�iGATI N NLINEIAT I -,/ "' a ® ISOLATION BALL VALVE: <br /> 12'OFF BA K OF URB <br /> ,� U ,�y 1-1/2"(PVC) TrLE <br /> b \-\ 1 1-112' - 1 Qb RAIN BIRD PEB CONTROL VALVE <br /> ci / \ ,-. -!� _.-.. _.. - _-_-._.-_ - _ ______ __ b a . _ __ ASSEMBLY V DATE DESCRIPTION <br /> / / _-._ ���� _- <br /> ' _l�=�.1 ; • -• • • / _r.l .:,.,.-..Q -� 0 - RAIN BIRD 44-LRC 6030921 PERMIT <br /> /7 ',.,.,1 •I a "� _---. --_- - _�: . ��i •r -14" __ -�,� O QUICK COUPLER ASSEMBLY <br /> 1 / Per. -- - - / / / i 1/21/2022 BID ISSUE <br /> O • O 0. O O O O O O O___ z _- ��,-.___ -. 180 -7 SCHEDULE 40 IRRIGATION SLEEVING <br /> o / 1.va A <br /> So (_____:: <br /> •` • �> INSTALL IRRIGATION HEADS AT - I I � • _ GPM C1• SCHEDULE 40 MANUNE(1.5") <br /> o J BACK SIDE OF ELECTRIC VEHICLE a R--�-o, I f • O -- •.'1 `-. ` e- SCHEDULE 40 LATERAL LINES <br /> ti -� CHARGING STSTIONS(TYP.) s t I 8 - -- - T'� - ��. <br /> C p <br /> / • , . 1 • I I• SLEEVES AT EXISTI ISIDEWALK a 111111111 // 1-1/4" <br /> �_ I' 'I -° ® *' I IRRIGATION PIPE SIZING <br /> S SEE SHEET L3.02 FOR CONTINUATION P.V.C.PIPE SCHEDULE <br /> REVISIONS <br /> m PIPES ARE TO BE SIZED ACCORDING TO G.P.M. <br /> a (GALLONS PER MINUTE) DEMAND DOWN UNE. DR,8S,AL,EH COC <br /> HE <br /> DRAWN BY CHECK BY <br /> FLOW VELOCITIES ARE NOT TO EXCEED 5' PER BID ISSUE <br /> SECOND. STATUS <br /> 'w <br /> 20 0 20 40 SCHEDULE 40 P.V.C. MAINLINE& LATERALS. 1/21/2022 <br /> HORZ DATE <br /> E <br /> m �� SCALE IN FEET <br /> NG.P.M. PIPE SIZE 32880J <br /> F I PROJECT NUMBER <br /> 0-8 3/4" <br /> RI <br /> L3.01 <br /> 9 - 11 ,,, <br /> 2- 22 , i/4" <br /> g 23- 30 1 1/2"Know what's below. 0 2021 OTAK,INC. <br /> t Call before you dig. 31 - SD 2 Il this drawing is not24.x 36-.it has been <br /> reduced/enlarged.Scale accordingly. <br /> EL <br />