February 19,2004 DN-3783•A-105
<br /> 8 NOTIFIER® AFP-200
<br /> Analog Fire Panel
<br /> Section: Intelligent Fire Alarm Control Panels
<br /> GENERAL (11 l California
<br /> , State Fire
<br /> II5
<br /> The AFP-200 is a compact,cost-effective,intelligent fire alarm o.•'.:,
<br /> Marshal
<br /> control with a capacity of 198 individually identified and con- �:-` ':5'
<br /> trolled points and an extensive list of powerful features. The •`' 7165 0028:164
<br /> �F
<br /> AFP-200 provides capabilities that exceed most large intelli- LISTED CS118 IIT
<br /> gent systems, at a cost comparable to conventional control S635 (AFP-200C,
<br /> panels. AFP-200RC)
<br /> FEATURES M EA U.S. Coast Guard APPROVED
<br /> • 198 intelligent device capacity(99 analog detectors and 99 161.002/23/3
<br /> monitor/control modules). Style 4,6,or 7. 104-93-E Vol.XI
<br /> • Overall 301 point capability (198 intelligent points, 4 pro- The AFP-200
<br /> grammable NAC circuits, 99 programmable relays).
<br /> • Network ready(reference NOTI•FIRE•NETT"" and NAM- ,Lloyds
<br /> 232 data sheets for more information). master 6
<br /> • Intelligent features: AFP-200
<br /> V Manual sensitivity adjustment. °^mow..^^E°VE°^°N MID
<br /> •w11.15,5,°
<br /> V Day/Night automatic sensitivity adjustment. TYPE
<br /> APPROVED
<br /> ✓ Drift compensation (U.S. Patent Pending) meets UL
<br /> requirements as a calibrated test instrument. 94/60004(E2) AARE,
<br /> V Auto detector test(meets NFPA 72). City of 0®Eg o
<br /> I., Maintenance alert(two separate algorithms), Iasi 0
<br /> V Pre-alarm(AWACST"' U.S. Patent Pending). Chicago 0®Ma0
<br /> ✓ Activate local sounder base on pre-alarm. CLASS 1: owns®O
<br /> V LED blink control for sleeping areas. 1928E
<br /> V Automatic device type check.
<br /> • Releasing features: City and
<br /> V Four independent hazards. County of
<br /> ✓ Sophisticated cross-zone(three options) DENVER Q)NOTIFIER
<br /> V Delay timer and Discharge timers(adjustable).
<br /> V Abort(four options).
<br /> • Optional DACT,with AC fail delay. 3783afp2.wmf
<br /> • LCD-80 remote display/control. • Two-Stage option for notification circuits(Canada).
<br /> • ACS annunciators(EIA-485), including LDM custom. • Tornado Warning activates different notification circuit code.
<br /> • Printer interface(80-column and 40-column printers). • Non-alarm points for lower priority functions.
<br /> • 5.0 A usable regulated output power, plus 6.0 A expander • Remote Silence/Reset/Evacuate via monitor modules.
<br /> (maximum 8.0 A to panel circuits). • Automatic time control functions,with holiday exceptions.
<br /> • 80-character LCD display, backlit. • Rapid poll algorithm for manual stations. Responds in <2
<br /> • Real-time clock,with European format option. seconds.
<br /> • History file with 650-event capacity in nonvolatile memory. • Operates with untwisted, unshielded wire (up to 1,000 ft./
<br /> Includes non-erasable shadow history. 304.8 m)for retrofit applications(U.S. Patent 5,210,523).
<br /> • Waterflow or supervisory selection per point. • UL Listed for Fire Signaling per Standard 864&NFPA 72.
<br /> • Alarm Verification selection per point,with tally. • UL Listed for Burglary applications per Standard 1076.
<br /> • Walk Test reports two devices set to same address. • UL Listed for Releasing Service. Complies with NFPA 12,
<br /> • Positive Alarm Sequence(PAS)Presignal per NFPA 72. 12A,12B,13,15,16,17,17A,2001 Standardswhen installed
<br /> • Silence inhibit and Auto Silence timer options. in accordance with appropriate NFPA standard.
<br /> • March time/temporal/California code for bell circuits. • Approved forAgent Release and Preaction/Deluge by CSFM,
<br /> • Field-programmable on panel or on PC, with user-defined City and County of Denver, FM, MEA,and ULC.
<br /> passwords, plus Autoprogram feature. • Approved for marine applications by U.S. Coast Guard and
<br /> • UL-Listed modem interface allows remote/off-site system Lloyd's Register of shipping.
<br /> integration. AGENCY LISTINGS AND APPROVALS
<br /> • FZM-1 two-wire detector interface provides compatibility with Listing agencies and file numbers displayed above.These list-
<br /> many non-NOTIFIER detectors for retrofit applications(con- ings and approvals apply to the basic AFP-200 control panel.
<br /> suit factory for latest compatibility listings). In some cases, certain modules may not be listed by certain
<br /> • Dual-rate charger for up to 90 hours of standby power. approval agencies, or listing may be in process. Consult fac-
<br /> tory for latest listing status.
<br /> 1 NOTI•FIRE•NETTm is a trademark of NOTIFIER, 1994.
<br /> NThis
<br /> document
<br /> is a Honeywell company. ISO 9001 •
<br /> This document is not intended to be used for installation purposes. We try to keep our •: ='•,.
<br /> product information up-to-date and accurate. We cannot cover all specific applications `'-::�
<br /> or anticipate all requirements. All specifications are subject to change without notice. C E R T I F I E �_
<br /> For more information,contact NOTIFIER. Phone:(203)484-7161 FAX:(203)484-7118 ENGINEERING$MANUFACTURING
<br /> 0 NOT 1 Fl ERA 12 Clintonville Road, Northford, Connecticut 06472 QUALITY SYSTEMS Made in the U.S.A.
<br /> DN-3783•02/19/04 — Page 1 of 4
<br />
|