Laserfiche WebLink
GENERAL NOTES: ELECTRICAL SYSTEM NOTES : SUPRESS1ON SYSTEMS INC. <br /> LEGEND / PARTS LIST �0ThST"'��.SU'�8p" <br /> 1. ALL DOORS IN THE CLEAN AGENT HAZARD AREA SHALL HAVE DOOR CLOSURES,DOOR SWEEPS AND DOOR SEALS.(BY 1. THE DETECTION AND CONTROLS PORTION OF THE FIRE PROTECTION SYSTEM SHALL BE INSTALLED IN 'RFE'E STREET FIRE SUITE 8 <br /> 263)9213.3306 <br /> OTHERS) ACCORDANCE WITH NFPA 70,72 AND STATE AND LOCAL CODES WHERE APPUCABLE. • eae3sao cN <br /> 2. THE DISCHARGE TIME OF THE SYSTEM SHALL NOT EXCEED 120 SECONDS. THE PROTECTED VOLUME IS TO BE 2. ALL WIRING AND CONDUIT FOR THE FIRE PROTECTION SYSTEM SHALL BE INSTALLED IN MINIMUM OF 1/2° SYMBOL QUAN. PART# DESCRIPTION MANUFACTURER NOTES <br /> FLOODED AT A 46.9%CONCENTRATION FOR CLASS°C ELECTRICAL UP TO 480V,UNI FRR OTHERWISE NOTED ON THE RACEWAY,IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE I CP I 1 77-600000-901 ARIES ADDRESSABLE CONTROL PANEL KIDDE RED ENCLOSURE 6'AFF 400ETSTAMPS <br /> SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS. THE HAZARD AREA SHALL MAINTAIN DESIGN CONCENTRATION (NFPA 70),NATIONAL FIRE ALARM CODE(NFPA 72),CITY,STATE,LOCAL BUILDING CODES,THE AUTHORITY 2 U812120 12.0 Ali BATTERY UPG CONTROL PANEL �, �./ <br /> • FOR A MINIMUM OF 10 MIN. HAVING JURISDICTION,PROJECT SPECIFICATIONS AND THE MANUFACTURES RECOMMENDATIONS. <br /> • a THE CLEAN AGENT CONTROL PANEL SHALL HAVE BATTERY BACK-UP TO PROVIDE 24 HOURS OF STANDBY OPERATION 3. ALL WIRING SHALL BE INSTALLED USING INSULATED INDIVIDUAL CONDUCTORS IN CONDUIT.THERE SHALL I Al I 5 70-610001-001 ADDRESSABLE MONITOR MODULE(WO) NODE 4S BOX OR 2 GANG ° <br /> WITH 5 MINUTES OF ALARM UNLESS NOTED OTHERWISE ON THE DRAWINGS AND THE BATTERY CALCULATIONS. BE NO BUTT SPLICING.ALL WIRE RUNS BETWEEN PANEL AND/OR DEVICES SHALL BE MADE WITH A SINGLE I ILR I 2 06-220023-001 IN-LINE RELEASING CIRCUIT KIDDE AT CYUNDER "`""� <br /> 4. INTERLOCK WIRING AND CONDUIT TO CONNECT TO THE REMOTE FIRE ALARM SYSTEM(IF REQUIRED)SHALL BE LENGTH OF WIRE.CONDUCTORS ARE TO BE COLOR CODED,NUMBER CODED OR BOTH TO IDENTIFY THE <br /> PROVIDED BY OTHERS. SUPPRESSION SYSTEMS INC.WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CIRCUITS AND POLARITY.ALL WIRING SHALL COMPLY WITH ARTICLE 760 OF THE NATIONAL ELECTRICAL 0 1 76-600000-200 MAINTENANCE BYPASS KIDDE 4S BOX OR 2 GANG DEEP /: <br /> s -f i F ._•.. <br /> CONTROL PANEL CODE AND THE MANUFACTURER'S RECOMMENDATIONS. A 1 84-330002-001 ADDRESSABLE MANUAL RELEASE KIDDE SINGLE GANG " <br /> 5. INTERLOCK WIRING AND CONDUIT TO EQUIPMENT SHALL BE PROVIDED BY OTHERS. SUPPRESSION SYSTEMS INC.WILL 4. REFERENCE MOUNTING INSTRUCTION INCLUDED WITH EACH DEVICE. WW1 mum) <br /> © 2 81-486536-000 DISCHARGE PRESSURE SWITCH KIDDE 4S BOX OR 2 GANG DEEP i <br /> PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CONTROL PANEL 5. LOW VOLTAGE CIRCUITS MUST NOT BE COMBINED IN CONDUITS WITH HIGH VOLTAGE(120,240,ETC.VOLT) <br /> 6. THE CLEAN AGENT HAZARD AREA SHALL BE SEALED TO PREVENT LEAKAGE OF THE AGENT.(BY OTHERS)SUPPRESSION AC POWER OR CONTROL CIRCUITS,SUCH AS FAN SHUTDOWN,EQUIPMENT SHUTDOWN,ETC. ®F 4 KS-PS PHOTOELECTRIC SMOKE DETECTOR KIDDE BASE(DS-SB) 'MANUFACTURER LOGO'S <br /> SYSTEMS INC.WILL PROVIDE GUIDANCE AND/OR SUPERVISION. 6. ROUTE NON-POWER LIMITED WIRING AT LEAST 1/4 INCH AWAY FROM ALL POWER LIMITED WIRING.DO NOT 4 DS-SB 4"DETECTOR BASE W/6"TRIM RING KIDDE 3-0 BOX fKidde <br /> 7. THE 120VAC CIRCUIT FOR THE CLEAN AGENT CONTROL PANEL SHALL BE A DEDICATED CIRCUIT WITH A LOCK-OUT ATTACH POWER LIMITED AND NON-POWER LIMITED WIRING TO THE SAME TERMINAL BLOCK.DEVICE ON THE BREAKER SWITCH TO COMPLY WITH NFPA 72 CURRENT ADDITION. 7. MINIMUM CONDUCTORS TYPE AND SIZE REQUIREMENTS: ...inAd 2 4890123 HORN/STROBE-MULTI CANDELA BLUE LENS POTTER 4S BOX OR 2 GANG DEEPFire Systems <br /> a ALL TERMINATIONS IN THE CLEAN AGENT CONTROL PANEL SHALL BE PERFORMED BY SUPPRESSION SYSTEMS INC. 7.1. DETECTION CIRCUITS-16 AWG THHN OR EQUAL 2ctl 1 4890103 STROBE-MULTI CANDELA BLUE LENS POTTER 4S BOX OR 2 GANG DEEP <br /> 9. RETENTION TIME FOR THE PROTECTED SPACE SHALL BE VERIFIED BY A ROOM INTEGRITY TEST PERFORMED IN 7.2. NOTIFICATION APPLIANCE CIRCUITS-16 AWG THHN OR EQUAL O 2 38-428031-100 300 BAR 80 LITER NATURA IGS CYLINDER W/IG-100 KIDDE <br /> ACCORDANCE WITH NFPA 20012018 EDITION. 7.3. RFI FARE CIRCUITS-16 AWG THHN OR EQUAL <br /> 7.4. 24 VDC POWER CIRCUITS-14 AWG THHN OR EQUAL I SOL I 2 38-400001-003 300 BAR RELEASE UNIT KIDDE CYLINDER VALVE 0.75A <br /> 7.5. 120/240 AC POWER CIRCUITS-14 AWG THHN OR EQUAL 2 38 g000prr105 FEMALE QUICK CONNECTOR NODE RELEASE UNIT <br /> CLEAN AGENT PIPING SYSTEM NOTES : 7.6. ALL CONDUCTORS MUST MEET THE MINIMUM RATING OF 600 VOLTS AT 90°C. <br /> 1. REFER TO SYSTEM DRAWINGS AND CALCULATIONS FOR THE LOCATION AND LAYOUT OF THE CLEAN AGENT 8. ELECTRICAL EQUIPMENT/SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH GOOD COMMERCIAL 2 38-401110-500 19.68"ACTUATION HOSE STRAIGHT TO STRAIGHT KIDDE RELEASE UNIT TO VALVE FIFE PR0TECRON ENGREERS Shur <br /> DISTRIBUTION PIPING SYSTEM. EXAMINE THE CONFIGURATION OF THE PIPING SYSTEM TO ENSURE THE PIPING AND PRACTICE.CARE SHALL BE TAKEN TO AVOID INCORRECT WIRING,CONNECTIONS,FAULTY FABRICATION 2 38-400007-001 PILOT LINE BLEED VALVE KIDDE CYLINDER VALVE <br /> DISCHARGE NOZZLES DO NOT INTERFERE WITH ANY ON SITE PHYSICAL OBSTRUCTIONS WITHIN THE CLEAN AGENT AND/OR IMPROPER INSTALLATIONS.ALL CONDUIT SHALL BE RIGIDLY SECURED. <br /> HAZARD AREA BEFORE THE PIPING INSTALLATION BEGINS. SHOULD ANY CONFLICTS OCCUR NOTIFY SUPPRESSION <br /> 9. AC AND DC CURRENT SHALL BE RUN IN SEPARATE CONDUIT AND BOXES. 2 38-400330-410 DISCHARGE HOSE 90°TO 90° KIDDE CYLINDER VALVE 16.1" <br /> SYSTEMS INC.TO MAKE THE REQUIRED ADJUSTMENTS TO THE SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS 10.PAINT ALL J-BOXES AND COVERS RED TO IDENTIFY FIRE PROTECTION SYSTEM. 2 01-8131-0000 MOUNTING STRAP FOR A 80 L CYLINDER KIDDE CYLINDER <br /> PRIOR TO BEGINNING PIPING INSTALLATION.ANY DEVIATIONS IN THE ROUTING OF 11.IDENTIFY EACH COVER WITH POWER LIMITED FIRE ALARM CKT. <br /> THE PIPE NETWORK SHALL BE 2 38-407500-055 180°NATURA IG-100 NOZZLE 1/2" KIDDE NOZZLE AREA 0.0368 <br /> VERIFIED AND APPROVED BY SUPPRESSION SYSTEMS INC. 12,MAINTAIN 1"SEPARATION BETWEEN ALL POWER LIMITED AND NON POWER LIMITED CIRCUITS. <br /> 2. CLEAN AGENT SUPPRESSION SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 2001 CURRENT 13.CONTROL SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 72,AS WELL AS ALL 2 SSI SIGN#1 CLEAN AGENT DOOR SIGN SSI/CW SIZE 9"X 12' <br /> ADDITION,AS WELL AS ALL APPLICABLE LOCAL CODES.DO NOT HYDROSTATIC TEST.PNEUMATIC PRESSURE TEST APPLICABLE LOCAL CODES. 2 SSI SIGN#2A CLEAN AGENT HORN/STROBE SIGN SSI/CW SIZE 5"X 8" <br /> WITH AIR OR N2 TO 40 PSI FOR 10 MINUTES.AT THE END OF 10 MINUTES SHALL NOT DROP BELOW 20%OF THE iAg 2 SSI SIGN#3 CLEAN AGENT DISCHARGE STROBE SIGN SSI 1 CW SIZE 5°X 8' COMPUANCE <br /> TEST PRESSURE. EXCLUSIONS. DATE <br /> suaMllT�us <br /> 3. PIPING MATERIAL MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001,CURRENT EDITION.SCHEDULE 40 ..WORK LISTED BELOW SHALL BE PROVIDED BY OTHERS OR UNDER OTHER SECTIONS OF THE PROJECT.** 100%SUBMITTAL 06/09/22 <br /> OR SCHEDULE 80 PIPE(BLACK OR GALVANIZED)MUST CONFORM TO ASTM A53 OR A106. ORDINARY CAST IRON PIPE" 1. 120 VAC POWER SUPPLY TO THE CLEAN AGENT CONTROL PANEL <br /> STEEL PIPE CONFORMING TO ASTM-120,OR NONMETALLIC PIPE SHALL NOT BE PERMITTED TO BE USED. 2. INTERLOCK WIRING AND CONDUIT FOR SHUTDOWN OF HVAC,DAMPERS AND/OR ELECTRIC POWER <br /> 4. PIPE FITTINGS MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001,CURRENT EDITION. MALLEABLE IRON SUPPLIES,RELAYS,SHUNT TRIP BREAKERS OR OTHER DEVICES. Permit#: FA2206-004 <br /> REV DESCRIPTION DATEFITTINGS(BLACK OR GALVANIZED)SHALL BE 300 LB.CLASS THAT CONFORM TO ASTM SPECIFICATION A-197. 150 LB. 3. CONNECTION TO LOCAL OR REMOTE FIRE ALARM SYSTEMS OR LISTED CENTRAL ALARM STATION. <br /> EA 1 CLASS FITTINGS AND ORDINARY CAST IRON FITTINGS ARE NOT PERMITTED. ONLY LISTED GROOVED,THREADED, Site Address: 590123RD D R W#1 OWNER 06/14/22 <br /> • WELDED OR FLANGED FITTINGS MAY BE USED,PROVIDED THEY CONFORM TO THE ABOVE REQUIREMENTS. HOLE CUT 4. ALL MATERIALS AND LABOR TO ENSURE THE RESPONSIBILITY <br /> OF THE PROTECTED SPACE(S)AND COMMENTS <br /> FITTINGS MAY NOT BE USED. RESPONSIBILITY FOR THE INTEGRITY OF THE CLEAN AGENT PROTECTED SPACE TO SATISFY THE Owner: SEAWAY CORPORATE LOT 3C Q <br /> REQUIREMENTS FOR THE TEN(10)MINUTE RETENTION TIME.SUPPRESSION SYSTEMS INC. MAY PROVIDE <br /> 5. ALL PIPE JOINING METHODS SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION.TEFLON TAPE IS ASSISTANCE,BY MEANS OF INSPECTION OF THE SPACE AND MAKING RECOMMENDATIONS ON REMEDIAL Tenant: ZAP ENERGY <br /> RECOMMENDED AND SHALL BE USED WITH ALL THREADED PIPING CONNECTIONS.THREADED PIPE AND FITTINGS ACTIONS THAT MAY BE REQUIRED TO ENSURE ROOM INTEGRITY. App.Date: 6/29/2022 <br /> " SHALL BE TAPERED IN CONFORMANCE WITH ANSI SPECIFICATION B-20.1.ALL GROOVED PIPING CONNECTIONS SHALL Proposed Use: COMMERCIAL <br /> BE BE LUBRICATED PER MANUFACTURERS SPECIFICATIONS. PROJECT STANDARDS <br /> 6. ALL PIPING MUST BE RIGIDLY SUPPORTED BY A COMBINATION OF PIPE HANGERS AND RIGID SUPPORT BRACKETS. PIPE Description: FIRE ALARM FOR CLEAN AGENT FIRE <br /> HANGERS ARE USED TO SUPPORT THE'DEAD LOAD'OF THE PIPING SYSTEM AND SHALL BE SPACED AT INTERVALS NOT APPLICABLE CODES: SUPPRESS 10 N SYSTEMS W/LV Z <br /> EXCEEDING 15 FEET. RIGID SUPPORTS ARE REQUIRED TO SUPPORT THE"LIVE LOAD"OF THE PIPING SYSTEM DURING NFPA 2001 2018 Q <br /> DISCHARGE. RIGID BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE-90°ELBOW,TEE AND NOZZLE.ALL 180° NFPA 70 2017 <br /> ' NOZZLES REQUIRE BACK-BRACING IN THE OPPOSITE DIRECTION OF THE DISCHARGE PATTERN. EARTHQUAKE BRACING NFPA 72 2019 V <br /> SHALL BE USED WHERE REQUIRED BY LOCAL CODE. REFER TO ANSI B31.1 FOR BRACING REQUIREMENTS. INTERNATIONAL FIRE CODE 2018 ®� LU <br /> 7. REDUCTIONS IN PIPE SIZE SHALL BE DIRECTLY AFTER A TEE WITH THE TEE BEING THE SAME PIPE SIZE AS THE INLET INTERNATIONAL BUILDING CODE 2018 Reviewed BY: • <br /> LU <br /> LINE TO THE TEE. REDUCTIONS IN PIPE SIZE MAY ALSO BE MADE USING A CONCENTRIC BELL REDUCER AFTER A CO <br /> UNION, PROVIDED THE NEXT CHANGE IN DIRECTION(TEE)IS LOCATED A MINIMUM OF 10 PIPE DIAMETERS Office Set Job Site Set Fire/Planning Set 0 cv <br /> SCOPE OF WORK <br /> DOWNSTREAM OF THE CONCENTRIC BELL REDUCER. CONCENTRIC BELL REDUCERS OR CONCENTRIC REDUCING Q_ co O) <br /> PROVIDE A SINGLE ZONE CLEAN AGENT FIRE SUPPRESSION WITH ADDRESSABLE DETECTION AND CONTROLS W Z <br /> COUPLINGS SHALL BE USED TO MAKE ALL REDUCTIONS IN PIPE SIZE. REDUCING BUSHINGS,WELDA LETS AND HOLE TO PROTECT 2 CONEX ENCLOSURES.THE UNITS MEASURE 8'-0'X 20-0"X T 6`AND WILL BE STACKED.THE >- LLI6 <br /> CUT FITTINGS SHALL NOT BE PERMITTED. SYSTEM IS DESIGN TO CLASS C.THE HAZARD EQUIPMENT AT DISCHARGE SHALL NOT EXCEED 480V. W <br /> 8. THE SYSTEM SHALL BE INSTALLED IN A PROFESSIONAL MANNER WITH"GOOD COMMERCIAL PRACTICE".ALL PIPING CC it -CD <br /> AND FITTINGS MUST BE REAMED,BLOWN CLEAN AND SWABBED WITH A CLEANING SOLVENT TO REMOVE DIRT,RUST Z O= <br /> AND OIL OWNER / SITE DATA : a <br /> ^9. PIPE REDUCTIONS MADE DIRECTLY AFTER A CHANGE IN DIRECTION,WITH THE FITTING BEING THE SAME PIPE SIZE AS ZAP ENERGY `\ E <br /> B W CL Z a <br /> THE INLET,SHALL BE MADE USING A COMMON CONCENTRIC BELL REDUCER. REDUCING BUSHINGS ARE NOT 5901 23RD DRIVE WEST �./1 afi Q Z NACCEPTABLE(UNLESS OTHERWISE NOTED).A MINIMUM OF 10 PIPE DIAMETERS MUST BE MAINTAINED FROM THE EVERETT,WASHINGTON 98203 N U r <br /> CENTER OF THE FITTING TO THE CENTER OF THE NEXT CHANGE IN DIRECTION. <br /> 10.WHEN BRACING THE PIPING CARE SHOULD BE TAKEN TO INSURE THE NOZZLE LOCATIONS ARE WITHIN ONE FOOT OF - c W <br /> THE LOCATIONS SHOWN ON THE SYSTEM PLANS.CORRECT NOZZLES SHALL BE INSTALLED EXACTLY IN ACCORDANCE AUTHORITY HAVING JURISDICTION : JUL 13 2022 <br /> WITH THE SYSTEM PLANS.NOZZLES SHALL BE INSTALLED PERPENDICULAR TO THE CEILING FOR PROPER CITY OF EVERETT 1."-- W <br /> DISTRIBUTION PATTERNS. 180°NOZZLES SHALL BE ALIGNED WITH THE ORIFICE HOLES ORIENTED PARALLEL TO THE 3200 CEDAR STREET g X <br /> CITY <br /> ADJACENT WALL$SO NO DIRECT WALL IMPINGEMENT OF THE AGENT OCCURS. EVERETT,WA 98201 F <br /> 11.FINAL INSTALLATION ACCEPTANCE SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION. PHONE:425-257-8810 pF b <br /> E�'ERETT CM <br /> Pefmit Services E x <br /> PARCEL NUMBER:2984965 1 <br /> bo <br /> DESIGNED SY:NMR SCALE: <br /> NDT TO <br /> owlNNsr: NMR SORE <br /> CHEaKEDsY:ZST utEse <br /> Norm <br /> DRAWING INDEX JOB NURSER:2241 °^ <br /> FP-01 NOTES,LEGEND,PARTS LIST AND DRAWING INDEX SHEET TRUE <br /> FIRE PROTECTION DRAWINGS <br /> FP-02 GENERAL ELEVATION,MAPS&SEQUENCE OF OPERATIONS <br /> _ NOTES,LEGEND,PARTS LIST, <br /> FP-03 FLOOR PLANS _ AND DRAWING INDEX <br /> FP-04 SINGLE LINE WIRING DETAIL AND ISOMETRICS <br /> b FP-05 ELECTRICAL MULTI-LINE WIRING DIAGRAM SHEET NUMBER: <br /> FP-06 ELECTRICAL AND MECHANICAL DETAILS FP-01 of 06 <br />