GENERAL NOTES: ELECTRICAL SYSTEM NOTES : 1 t.SUPIKESSION SYSTEMS INC.
<br /> S PEG W.HAZARDS RED PROTECTION
<br /> I .077 20TH STREET EAST.SURE 8
<br /> 1. ALL DOORS IN THE CLEAN AGENT HAZARD AREA SHALL HAVE DOOR CLOSURES,DOOR SWEEPS AND DOOR SEALS.(BY 1. THE DETECTION AND CONTROLS PORTION OF THE FIRE PROTECTION SYSTEM SHALL BE INSTALLED IN MD waaew a
<br /> OTHERS) ACCORDANCE WITH NFPA 70,72 AND STATE AND LOCAL CODES WHERE APPLICABLE. (DDE)` "'T"%°2:$0°""P
<br /> 2. THE DISCHARGE TIME OF THE SYSTEM SHALL NOT EXCEED 120 SECONDS.THE PROTECTED VOLUME IS TO BE 2. ALL WIRING AND CONDUIT FOR THE ARE PROTECTION SYSTEM SHALL BE INSTALLED IN MINIMUM OF 1/2'
<br /> lA
<br /> FLOODED AT A 46.9%CONCENTRATION FOR CLASS"C'ELECTRICAL UP TO 480V,UNLESS OTHERWISE NOTED ON THE RACEWAY,IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE n FACET STAMPS
<br /> CC
<br /> SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS. THE HAZARD AREA SHALL MAINTAIN DESIGN CONCENTRATION (NFPA 70),NATIONAL FIRE ALARM CODE(NFPA 72),CITY,STATE,LOCAL BUILDING CODES,THE AUTHORITY 0 '
<br /> FOR A MINIMUM OF 10 MIN. HAVING JURISDICTION,PROJECT SPECIFICATIONS AND THE MANUFACTURES RECOMMENDATIONS. ` e..i'. /L-
<br /> 3. THE CLEAN AGENT CONTROL PANEL SHALL HAVE BATTERY BACK-UP TO PROVIDE 24 HOURS OF STANDBY OPERATION 3. ALL WIRING SHALL BE INSTALLED USING INSULATED INDIVIDUAL CONDUCTORS IN CONDUIT.THERE SHALL 2 Z I
<br /> WITH 5 MINUTES OF ALARM UNLESS NOTED OTHERWISE ON THE DRAWINGS AND THE BATTERY CALCULATIONS. BE NO BUTT SPLICING.ALL WIRE RUNS BETWEEN PANEL AND/OR DEVICES SHALL BE MADE WITH A SINGLE 0 0 %I a omr• =uvus
<br /> • MA
<br /> 0
<br /> 4. INTERLOCK WIRING AND CONDUIT TO CONNECT TO THE REMOTE FIRE ALARM SYSTEM OF REQUIRED)SHALL BE LENGTH OF WIRE.CONDUCTORS ARE TO BE COLOR CODED,NUMBER CODED OR BOTH TO IDENTIFY THE cC N 2 , �. /,
<br /> PROVIDED BY OTHERS. SUPPRESSION SYSTEMS INC.WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CIRCUITS AND POLARITY.ALL WIRING SHALL COMPLY WITH ARTICLE 760 OF THE NATIONAL ELECTRICAL CC cc 0
<br /> Itr- ,._
<br /> +,
<br /> CONTROL PANEL CODE AND THE MANUFACTURERS RECOMMENDATIONS. 0 - 0 a n " ,
<br /> 5. INTERLOCK WIRING AND CONDUIT TO EQUIPMENT SHALL BE PROVIDED BY OTHERS.SUPPRESSION SYSTEMS INC.WILL 4. REFERENCE MOUNTING INSTRUCTION INCLUDED WITH EACH DEVICE 0- LW ° 0O
<br /> PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CONTROL PANEL 5. LOW VOLTAGE CIRCUITS MUST NOT BE COMBINED IN CONDUITS WITH HIGH VOLTAGE(120,240,ETC.VOLT) a N 06. THE CLEAN AGENT HAZARD AREA SHALL BE SEALED TO PREVENT LEAKAGE OF THE AGENT.(BY OTHERS)SUPPRESSION AC POWER OR CONTROL CIRCUITS,SUCH AS FAN SHUTDOWN,EQUIPMENT SHUTDOWN,ETC. Q 2 a MANUFACTURER LOGOS
<br /> SYSTEMS INC.WILL PROVIDE GUIDANCE AND/OR SUPERVISION. 6. ROUTE NON-POWER LIMITED WIRING AT I FAST 1/4 INCH AWAY FROM ALL POWER UMITED WIRING.DO NOT U ° } U- 0 I �,�'Kidde
<br /> 7. THE 120VAC CIRCUIT FOR THE CLEAN AGENT CONTROL PANEL SHALL BE A DEDICATED CIRCUIT WITH A LOCK-OUT ATTACH POWER LIMITED AND NON-POWER LIMITED WIRING TO THE SAME TERMINAL BLOCK. cn in I
<br /> DEVICE ON THE BREAKER SWITCH TO COMPLY WITH NFPA 72 CURRENT ADDITION. 7. MINIMUM CONDUCTORS TYPE AND SIZE REQUIREMENTS: C CD tr H Lu Ir \`I +� Fire Systems
<br /> 8. ALL TERMINATION'S IN THE CLEAN AGENT CONTROL PANEL SHALL BE PERFORMED BY SUPPRESSION SYSTEMS INC. 7.1, DETECTION CIRCUITS-16 AWG THHN OR EQUAL g0. cc CC CD N d Q V' O i!� cn
<br /> 9. RETENTION TIME FOR THE PROTECTED SPACE SHALL BE VERIFIED BY A ROOM INTEGRITY TEST PERFORMED IN 7.2. NOTIFICATION APPLIANCE CIRCUITS-18 AWG THHN OR EQUAL 1 N Z Z cN ,Z z L.) \ill 4)ACCORDANCE WITH NFPA 2001 2018 EDITION. 7.3, RELEASE CIRCUITS-16 AWG THHN OR EQUAL Oe-ILu LLI N 7.4. 24 VDC POWER CIRCUITS-14 AWG THHN OR EQUAL N 0 e0�[- asa ` c = J Q `1 O
<br /> 7,5. 120/240 AC POWER CIRCUITS-14 AWG THHN OR EQUAL Y Lf) rJ N m U U U U
<br /> CLEAN AG ENT PIPING SYSTEM NOTES : 7.6. ALL CONDUCTORS MUST MEET THE MINIMUM RATING OF 600 VOLTS AT 90°C.
<br /> 1. REFER TO SYSTEM DRAWINGS AND CALCULATIONS FOR THE LOCATION AND LAYOUT OF THE CLEAN AGENT 8. ELECTRICAL EQUIPMENT/SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH GOOD COMMERCIAL uj 5.- FIRE PROTECTION ENGINEERS STAMP
<br /> DISTRIBUTION PIPING SYSTEM. EXAMINE THE CONFIGURATION OF THE PIPING SYSTEM TO ENSURE THE PIPING AND PRACTICE.CARE SHALL BE TAKEN TO AVOID INCORRECT WIRING,CONNECTIONS,FAULTY FABRICATION N CI.; 2 CO
<br /> DISCHARGE NO771 FS DO NOT INTERFERE WITH ANY ON SITE PHYSICAL OBSTRUCTIONS WITHIN THE CLEAN AGENT AND/OR IMPROPER INSTALLATIONS.ALL CONDUIT SHALL BE RIGIDLY SECURED. i F N a)
<br /> HAZARD AREA BEFORE THE PIPING INSTALLATION BEGINS.SHOULD ANY CONFLICTS OCCUR NOTIFY SUPPRESSION 9. AC AND DC CURRENT 10.PAINT ALL J-BOXES ANDFCOVERS REDLL BE RUN IN TO DENT FY FIRE PTE UIT AND ROTECTIONXSYSTEM. E Q c E -
<br /> SYSTEMS INC.TO MAKE THE REQUIRED ADJUSTMENTS TO THE SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS
<br /> 11.IDENTIFY EACH COVER WITH POWER LIMBED FIRE ALARM CKT. v . 3 N I? N Lan) N
<br /> PRIOR TO BEGINNING PIPING INSTALLATION,ANY DEVIATIONS IN THE ROUTING OF THE PIPE NETWORK SHALL BE n O Q N 0 K
<br /> VERIFIED AND APPROVED BY SUPPRESSION SYSTEMS INC. 12.MAINTAIN 1"SEPARATION BETWEEN ALL POWER UMITED AND NON POWER UMITED CIRCUITS.
<br /> 2. CLEAN AGENT SUPPRESSION SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 2001 CURRENT 13.CONTROL SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 72,AS WELL AS ALL
<br /> ADDITION,AS WELL AS ALL APPLICABLE LOCAL CODES.DO NOT HYDROSTATIC TEST.PNEUMATIC PRESSURE TEST APPUCABLE LOCAL CODES.
<br /> WITH AIR OR N2 TO 40 PSI FOR 10 MINUTES.AT THE END OF 10 MINUTES SHALL NOT DROP BELOW 20%OF THE
<br /> TEST PRESSURE. EXCLUSIONS : COMPLIANCE DATE
<br /> SUBMITTALS
<br /> 3. PIPING MATERIAL MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001,CURRENT EDITION.SCHEDULE 40 **WORK LISTED BELOW SHALL BE PROVIDED BY OTHERS OR UNDER OTHER SECTIONS OF THE PROJECT.** 100%SUBMITTAL 02/08/23
<br /> OR SCHEDULE 80 PIPE(BLACK OR GALVANIZED)MUST CONFORM TO ASTM A53 OR A106.ORDINARY CAST IRON PIPE, 1. 120 VAC POWER SUPPLY TO THE CLEAN AGENT CONTROL PANEL
<br /> STEEL PIPE CONFORMING TO ASTM-120,OR NONMETALLIC PIPE SHALL NOT BE PERMITTED TO BE USED. 2. INTERLOCK WIRING AND CONDUIT FOR SHUTDOWN OF HVAC,DAMPERS AND/OR ELECTRIC POWER _ JJ
<br /> 4. PIPE FITTINGS MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001,CURRENT EDITION. MALLEABLE IRONSUPPLIES,RELAYS,SHUNT TRIP BREAKERS OR OTHER DEVICES.FITTINGS(BLACK OR GALVANIZED)SHALL BE 300 LB.CLASS THAT CONFORM TO ASTM SPECIFICATION A-197. 150 LB. 1E1REV DESCRIPTION DATECLASS FITTINGS AND ORDINARY CAST IRON FITTINGS ARE NOT PERMITTED.ONLY LISTED GROOVD,THREADED, 3. CONNECTION TO LOCAL OR REMOTE FIRE ALARM SYSTEMS OR LISTED CENTRAL ALARM STATION, ) REVIEW02/17/23
<br /> 4. ALL MATERIA S AND LABOR TO ENSURE THE"AIR-TIGHTNESS'OF THE PROTECTED SPACE(S)AND COMMENTS
<br /> WELDED OR FLANGED FITTINGS MAYBE USED,PROVIDED THEY CONFORM TO THE ABOVE REQUIREMENTS. HOLE CUT RESPONSIBILITY FOR THE INTEGRITY OF THE CLEAN AGENT PROTECTED SPACE TO SATISFY THE0
<br /> FITTINGS MAY NOT BE USED. REQUIREMENTS FOR THE TEN(10)MINUTE RETENTION TIME.SUPPRESSION SYSTEMS INC. MAY PROVIDE / 25. ALL PIPE JOINING METHODS SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION. TEFLON TAPE IS ASSISTANCE,BY MEANS OF INSPECTION OF THE SPACE AND MAKING RECOMMENDATIONS ON REMEDIAL `w' A("` 0-7 2023 QS
<br /> RECOMMENDED AND SHALL BE USED WITH ALL THREADED PIPING CONNECTIONS.THREADED PIPE AND FITTINGS ACTIONS THAT MAY BE REQUIRED TO ENSURE ROOM INTEGRITY.
<br /> SHALL BE TAPERED IN CONFORMANCE WITH ANSI SPECIFICATION B-20.1.ALL GROOVED PIPING CONNECTIONS SHALL ,_, Q
<br /> BE BE LUBRICATED PER MANUFACTURERS SPECIFICATIONS.
<br /> 6. ALL PIPING MUST BE RIGIDLY SUPPORTED BY A COMBINATION OF PIPE HANGERS AND RIGID SUPPORT BRACKETS. PIPE PROJECT STANDARDS : CITY OF EVERETT
<br /> HANGERS ARE USED TO SUPPORT THE'DEAD LOAD°OF THE PIPING SYSTEM AND SHALL BE SPACED AT INTERVALS NOT APPUCABLE CODES: Permit Services z N
<br /> EXCEEDING 15 FEET.RIGID SUPPORTS ARE REQUIRED TO SUPPORT THE'LIVE LOAD'OF THE PIPING SYSTEM DURING NFPA 2001 2018 W
<br /> DISCHARGE. RIGID BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE-90°ELBOW,TEE AND NOZZLE. ALL 180° NFPA 70 2017 G O)
<br /> N0771 FS REQUIRE BACK-BRACING IN THE OPPOSITE DIRECTION OF THE DISCHARGE PATTERN. EARTHQUAKE BRACING NFPA 72 2019 J LU
<br /> C.)SHALL BE USED WHERE REQUIRED BY LOCAL CODE REFER TO ANSI B31.1 FOR BRACING REQUIREMENTS. INTERNATIONAL FIRE CODE 2018
<br /> 7. REDUCTIONS IN PIPE SIZE SHALL BE DIRECTLY AFTER A TEE WITH THE TEE BEING THE SAME PIPE SIZE AS THE INLET INTERNATIONAL BUILDING CODE 2018 L
<br /> LINE TO THE TEE. REDUCTIONS IN PIPE SIZE MAY ALSO BE MADE USING A CONCENTRIC BELL REDUCER AFTER A O Cr)
<br /> UNION, PROVIDED THE NEXT CHANGE IN DIRECTION(TEE)IS LOCATED A MINIMUM OF 10 PIPE DIAMETERS SCOPE OF WORK : cc
<br /> 0 Z W
<br /> DOWNSTREAM OF THE CONCENTRIC BELL REDUCER.CONCENTRIC BELL REDUCERS OR CONCENTRIC REDUCING
<br /> COUPLINGS SHALL BE USED TO MAKE ALL REDUCTIONS IN PIPE SIZE. REDUCING BUSHINGS,WELDA-LETS AND HOLE PROVIDE A SINGLE ZONE CLEAN AGENT pG-100 INERT GAS)FIRE SUPPRESSION WITH ADDRESSABLE Q
<br /> CUT FlTI7NGS SHALL NOT BE PERMUTED. DETECTION AND CONTROLS TO PROTECT CAPACITOR ROOM.THE MEASURE 20'-0'X 24'-0"X 9'-9"WITH A 1'-4" CCV) d
<br /> 8. THE SYSTEM SHALL BE INSTALLED IN A PROFESSIONAL MANNER WITH"GOOD COMMERCIAL PRACTICE'.ALL PIPING SUB-FLOOR THE SYSTEM IS DESIGN TO PROTECT A CLASS"C"FIRE HAZARD. STANDARD DETECTOR SPACED IQ
<br /> ECE
<br /> OVE
<br /> Q V)AND FITTINGS MUST BE REAMED,BLOWN CLEAN AND SWABBED WITH A CLEANING SOLVENT TO REMOVE DIRT,RUST AT 250 SQ.FT.SHALL RELEASE THE SYSTEM.ALARM,TROUBLE AND SUPERVISORY TO BUILDING FACP BYSSI.
<br /> la-
<br /> AND OIL CL
<br /> 9. PIPE REDUCTIONS MADE DIRECTLY AFTER A CHANGE IN DIRECTION,WITH THE FITTING BEING THE SAME PIPE SIZE AS OWNER / SITE DATA : MAR t 7 2023 a 0_ cn
<br /> THE INLET,SHALL BE MADE USING A COMMON CONCENTRIC BELL REDUCER. REDUCING BUSHINGS ARE NOT ZAP ENERGY Q = 1-
<br /> ACCEPTABLE(UNLESS OTHERWISE NOTED).A MINIMUM OF 10 PIPE DIAMETERS MUST BE MAINTAINED FROM THE 5901 23RD DRIVE WEST co
<br /> CENTER OF THE FITTING TO THE CENTER OF THE NEXT CHANGE IN DIRECTION. EVERETT,WASHINGTON 98203 C i TY OF EVERETT v LUILI
<br /> 10.WHEN BRACING THE PIPING CARE SHOULD BE TAKEN TO INSURE THE NOZZLE LOCATIONS ARE WITHIN ONE FOOT OF } CC
<br /> THE LOCATIONS SHOWN ON THE SYSTEM PLANS. CORRECT NOZZLES SHALL BE INSTALLED EXACTLY IN ACCORDANCE Permit r m i# Services 0
<br /> cc Er-
<br /> DISTRIBUTIOWITH THE STEMPLANS.N RNS. 180°SSFCSHA BEAUGNDWITHLL BE INSTALLED DD FOR EHO THE
<br /> LESONGFOR
<br /> PNTED ARALLELTOTHE PER AUTHORITY HAVING JURISDICTION :CITY OF EVERETT Z LU I- o
<br /> ADJACENT WALLS SO NO DIRECT WALL IMPINGEMENT OF THE AGENT OCCURS. 3200 CEDAR STREET Z
<br /> Z p
<br /> 11.FINAL INSTALLATION ACCEPTANCE SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION. EVERETT,WA 98201 2 a 0 RI
<br /> PHONE:425-257-8810 3
<br /> PARCEL NUMBER:2964965 Q 8
<br /> DESIGNED BY:NMB SCALE:
<br /> TO
<br /> DRAWING INDEX DRAWN BY: NMB "SCALE
<br /> OT
<br /> CHECKED BY:ZST UNtESS
<br /> NOTED
<br /> FP-01 NOTES AND DRAWING INDEX JOB NUMBER:2306 °THEMES
<br /> FP-02 GENERAL ELEVATION AND MAPS SHEET TITLE:
<br /> FIRE PROTECTION DRAWINGS
<br /> FP-03 PARTS LIST AND SEQUENCE OF OPERATIONS NOTES AND
<br /> FP-04 FLOOR PLANS AND ISOMETRICS DRAWING INDEX
<br /> FP-05 ELECTRICAL MULTI-LINE WIRING DIAGRAM
<br /> FP-06 ELECTRICAL DETAILS AND SINGLE LINE DIAGRAM SHEET NUMBER:
<br /> t FP-07 MECHANICAL DETAILS FP-01 of 07