LL <br /> N <br /> v LL 0 <br /> EMOP III SUITE 110 <br /> Y U <br /> U � <br /> r � <br /> m <br /> FIRE ALARM SYSTEM OPERATIONAL MATRIX GENERAL NOTES <br /> ALARM TROUBLE SUPERVISORY MISCELLANEOUS 1.FACTORY RECOMMENDED MINIMUM WIRING SIZES,TYPE AND 7.PARALLEL BRANCHING OF WIRE TO ALL NOTIFICATION APPLIANCE Q <br /> CONSTRUCTION AS NOTED ON THE DRAWINGS MUST BE STRICTLY CIRCUITS SHALL NOT BE PERMITTED. o <br /> FOLLOWED.ANYONE WILLING TO MAKE CHANGES WILL DO SO AT <br /> O 1"SSO THEIR OWN RISM 8.PARALLEL BRANCHING OF WIRE TO ADDRESSABLE INITIATING DEVICE <br /> CIRCUITS IS PERMISSIBLE. w <br /> 2.THE CIRCUIT ROUTING AND WIRING COUNTS ON THE FLOOR PLAN Cn <br /> z w DRAWINGS ARE SHOWN DIAGRAMMATIC BASED ON CONTINUOUS AND 9.PER NFPA 72,SECTION 29.8.3.4(7):SMOKE ALARMS AND SMOKE U <br /> Qp p 4i4 ��w SHORTEST POSSIBLE ROUTING FROM THE CONTROL PANEL AND DETECTORS SHALL NOT BE INSTALLED WITHIN A 361N.(910MM) ( �I <br /> p4 {U5 G 5� 5 BETWEEN CONNECTED FIELD DEVICES WITH NO PHYSICAL HORIZONTAL PATH FROM THE SUPPLY REGISTERS OF A FORCED AIR > o <br /> c�S l�ti �yG�Sw PG4�S1�44 y� OBSTRUCTIONS.THE WIRING OR CIRCUIT COUNTS(IF SHOWN)ARE HEATING OR COOLING SYSTEM AND SHALL BE INSTALLED OUTSIDE OF <br /> PROVIDED AS A CONVENIENCE ONLY AND AS MEANS TO HASTEN THE DIRECT AIRFLOW FROM THOSE REGISTERS. o <br /> INSTALLATION OR TO DETERMINE WIRING ROUTES. <br /> 10.SMOKE ALARMS AND CO-DETECTION WILL BE INSTALLED BY <br /> 3.WIRE SHOWN IN THIS DRAWING SET IS PERMITTED IN RACEWAYS ELECTRICAL CONTRACTOR. <br /> LEADING TO FIRE PROTECTION EQUIPMENT.OTHER WIRE SHALL NOT BE o <br /> 4 P P 4v4v4v 4�4�4� <br /> PERMITTED. 11.THE AUDIBLE ALARM NOTIFICATION APPLIANCES SHALL PROVIDE A <br /> CAUSE Q�Q� �¢�¢�¢O y�y�y�4 �.��.�y�$ REMARKS SOUND PRESSURE LEVEL OF I5 DECIBELS(dBA)ABOVE THE AVERAGE <br /> 4.PER NFPA 72,SECTION 17.7.1.11.3:WHERE DETECTION IS NOT AMBIENT SOUND LEVEL OR 5 dBA ABOVE THE MAXIMUM SOUND LEVEL <br /> SMOKE HEAT DETECTORS • • • • • REQUIRED DURING CONSTRUCTION,DETECTORS SHALL NOT BE HAVING A DURATION OF NOT LESS THAN 60 SECONDS,WHICHEVER IS <br /> MANUAL PULL STATION • • • • • INSTALLED UNTIL AFTER ALL OTHER CONSTRUCTION TRADES HAVE GREATER,IN EVERY OCCUPIABLE SPACE WITHIN THE BUILDING.IN <br /> SYSTEM RESET • COMPLETED CLEANUP. COMPLIANCE WITH CURRENT IFC AND NFPA 72 CODES. <br /> SIGNAL SILENCE t <br /> • 5.FIRE ALARM SYSTEM INSTALLATION SHALL CONFORM WITH THE <br /> AC POWER FAILURE • • • LATEST U.L.,N.E.C.,N.F.P.A.,W.A.C.,AND OTHER STANDARDS AS <br /> FIRE ALARM TROUBLE(OPEN, APPLICABLE TO THE CITY STANDARDS. Z <br /> SHORTS,OR GROUNDS)ON • • • w LL <br /> INITIATION OR SIGNALING CIRCUITS 6.WHEN NECESSARY,DUE TO CHANGING DESIGN REQUIREMENTS, <br /> TAMPER SWITCHES • • • FACTORY AVAILABILITY,ETC.WE RESERVE THE RIGHT TO SUBSTITUTE z_ _ <br /> WATERFLOW SWITCH 1111• • • • • EQUIPMENT HEREIN MENTIONED OR SPECIFIED,WITH EQUIPMENT OF - - <br /> EQUAL OR BETTER QUALITY,FUNCTION AND DESIGN. 3 <br /> F 3 5 <br /> SCOPE OF WORK: o <br /> - <br /> 0 <br /> -ADD FIRE ALARM A/V NOTIFICATION TO SUITE <br /> -ADD FIRE ALARM ADDRESSABLE INITIATING TO SUITE <br /> FIRE ALARM DEVICE LEGEND <br /> SYMBOL QTY I DESCRIPTION MODEL NUMBER MANUFACTURER BACKBOX MOUNTING HEIGHT Z <br /> AC EX FIRE ALARM CONTROL PANEL 101000 EST EX EX J <br /> NAC# EX NOTIFICATION CKT POWER BOOSTER EBPS6A EST EX EX d <br /> cc <br /> 4 HORN STROBE-CEILING MOUNT EGCF-HDVM EST 4S BOX CEILING Q <br /> LLI <br /> 1 STROBE-CEILING MOUNT EGCF-VM EST 4S BOX CEILING Cn <br /> OH e 1 HEAT DETECTOR PSDA EST 4S BOX CEILING J <br /> c°xtl US PHOTO SMOKE SIGA-PS EST 4S BOX CEILING C Z <br /> T 0 Q <br /> J <br /> � w a <br /> °x D °C Lu <br /> a � <br /> " cn > � cc <br /> = w F <br /> d W W a <br /> nACI CCKT #1 0 0 W w <br /> e ee sea NAC CIRCUIT) � Ir <br /> REa aRh, Accentuate with Ash w a> w LL <br /> POWER <br /> SI;PPLY NAC# D OOU p Fy elapax at <br /> f <br /> FRCP A,_,P1ebeFS Gnil Ba-. <br /> o,000 B Evergreen <br /> Fconi oM ,� a 9 n Beauty College V <br /> PANEL fWf <br /> .� <br /> 120 VAC JULES MAYER,SET ` <br /> 20 AMP DEDICATED CIRCUIT NICET#130993 C ° o <br /> v Modern Home Fumiture United Seattle FIRE ALARM SYSTEMS.LEVEL IV 0 U o 2 "4 <br /> Furniture store 4.0 <br /> FIRE ALARM RISER <br /> Everett Vet Center Q �.o <br /> Metal Supermarkets r�.1 0 I <br /> Everett <br /> THE CIRCUIT ROUTING AND WIRING COUNTS [IN THE <br /> FLOOR PLAN DRAWINGS ARE SHOWN DIAGRAMMATIC <br /> BASED ON CONTINUOUS AND SHORTEST POSSIBLE <br /> ROUTING FROM THE CONTROL PANEL AND BETWEEN <br /> VICINITY MAP CONNECTED FIELD DEVICES WITH ND PHYSICAL 44 <br /> ❑BSTRUCTIONS. THE WIRING OR CIRCUIT COUNTS <br /> (IF SHOWN) ARE PROVIDED AS A CONVENIENCE <br /> ONLY AND AS MEANS TO HASTEN INSTALLATION <br /> OR TD DETERMINE WIRING ROUTS. ALL FIRE ALARM <br /> WIRING CAN BE RAN IN SAME CONDUIT. <br />