Permit#: FA2402-008 <br /> Site Address: 3915 Colby Ave <br /> Applicant: Dave Pontnak <br /> Application Date:Fire Alarm eo nve rg j nta <br /> Description: Fire Alarm Retrofit <br /> conver nt® Review Date: 02I15I2024 <br /> I 450 Shattuck Avenue South,Renton,Washington 98057 <br /> L Phone:425-272-2250 Fax:425-251-0949 <br /> EVERETT <br /> Everett Fire Dept.Permit Review This dooumentand the information/depicb.ns mntainedlshown <br /> is the exclusive property MCon-mint Technologies LLC and shall <br /> Status:Approved be handled as pnapneWry and wnfld.nti.1 information and must be <br /> Reviewed By:KBrown retum.d upon request.This dowmenl cannot be reproduced by any <br /> means without the Tften authorization of Convergint Technologies LLC. <br /> CASCADIAN PLACE <br /> 02/15/2024 2:4056 <br /> PM <br /> PANEL REPLACEMENT <br /> 3914 COLBY AVE N, EVERETT, WA 98201 <br /> SYMBOL LEGEND SCOPE OF WORK WIRE LEGEND MOUNTING HEIGHTS <br /> SYM DESCRIPTION MODEL# MANUFACTURER BACK BOX THIS SCOPE OF WORK INCLUDES: ALL WIRING AND INSTALLATION METHODS SHALL BE IN COMPLIANCE WITH CURRENT RELEVANT <br /> REPLACEMENT OF AN EXISTING FACP WITH NEW 101000G FIRE ALARM PANEL.EXISTING SLC NATIONAL AND LOCAL ELECTRICAL CODE ARTICLES AND RELATED SECTION CODE REQUIREMENTS. AIC SUPPLY DIFFUSER <br /> FACPv FIRE ALARM CONTROL PANEL 101000 EST INCLUDED-SEE PANEL DETAILS FOR DEVICES WILL BE REPLACED ON A ONE FOR ONE BASIS.EXISTING WIRING WILL REMAIN AND BE <br /> DIMENSIONS REUSED.NEW POWER SUPPLIES WILL BE INSTALLED TO POWER EXISTING NOTIFICATION DEVICES. WIRING INSTALLATION NOTES: CEILING MOUNTED FLUORESCENT LIGHT <br /> EXISTING NOTIFICATION WILL REMAIN AS IS.A NEW RADIO DIALER WILL BE INSTALLED FOR OFFSITE •LABEL ALL ZONE WIRES WITH ZONE NUMBER TAG AND DESCRIPTION. SMOKEIHEAT <br /> NACxx NAC POWER SUPPLY-GA EBPS6A EST INCLUDED-17"H X 13"W X 3.5"D NOTIFICATION. 'LABEL ALL SIGNAL CIRCUIT WIRES WITH SIGNAL CIRCUIT NUMBER TAG AND DESCRIPTION. DETECTOR TYP. 3'(MIN) <br /> 'LABEL ALL NETWORK,ANNUNCIATOR AND 1/0 CONTROL CIRCUIT WIRING WITH CIRCUIT NUMBER NOTE:DIMENSIONS SHOWN <br /> ARE TO THE CLOSEST <br /> Q INPUT MODULE - N/A - DESIGN CRITERIA APPLICABLE STANDARDS AND GUIDANCE: TAG AND DESCRIPTION. CEILING � EocE OF THEDErECTOR <br /> NFPA 72,2016 EDITION •VERIFY WITH OWNER AND GENERAL CONTRACTOR THAT OPEN CABLE IS ALLOWED ON SPECIFIC <br /> SINGLE ACTION PULL STATION 20181NTERNATIONAL FIRE CODE WITH SITE.(FPL,FPLP,RISER,OR 2 HOUR RATED) <br /> ❑F STANDARD SIGA-270 EST SINGLE GANG,2-1/2"DEEP 'WHERE REQUIRED,OUR DRAWINGS WILL NOTE WIRE OR PATHWAY REQUIRING SURVIVABILITY. <br /> OCCUPANCY/USE CLASSIFICATIONS: SUBSTITUTE THE RELEVANT CABLE WITH AN EQUIVALENT CABLE COMPATIBLE WITH THE MEANS OF 3' <br /> Q CONTROL RELAY MODULE SIGA-CR EST 4"SQUARE BOX,1-1/2"DEEP,SINGLE GANG R2-RESIDENTIAL SURVIVABILITY.THIS OFTEN INCLUDES;CI-C OR Cl CABLE(CIRCUIT INTEGRITY),CONCRETE ONLYAUDI DEVICES <br /> &VISUAL MAX <br /> COVER ENCASEMENT OR OTHER MEANS AS APPROVED BY THE AHJ.REFER TO NFPA 72 FOR FURTHER ONLY DEVICES <br /> 5' <br /> SINGLE INPUT MODULE SIGA-C71 EST 4"SQUARE BOX,1-1/2"DEEP,SINGLE GANG DOCUMENTATION AVAILABLE TO CONVERGINT TECHNOLOGIES INFORMATION. <br /> FIRE ALARM REMOTE MANUAL PULL <br /> COVER ATRIA CASCADIAN PLACE-FA MARKUPS-03-22-23 <br /> O 4"SQUARE BOX,1-1/2"DEEP,SINGLE GANG NON PLENUM: SINGLE COND.: PLENUM RATED: FIRE ALARM ANNUNCIATOR STATION <br /> DUAL INPUT MODULE SIGA-CT2 EST COVER CIRCUIT DESCRIPTION (FPLR,FPL) (THHN,TFFN) (FPLP) CONTROL PANEL <br /> H z ADDRESSABLE ROR HEAT SIGA-HRD EST 4"OCTAGON BOX,1-1/2"DEEP A ZONE/INPUT CIRCUIT BELDEN 5220UL (2)#16 AWG BELDEN 6220UL <br /> w F SIGA-SB4-STANDARD BASE 2 COND.16 AWG [3.850][24pF/FT] [3.850][37pF/F7] 80"MIN.TO BOTTOM <br /> STANDARD ADDRESSABLE SMOKE OFLENS <br /> 05 SIGA-OSD EST 4"OCTAGON BOX,1-1/2"DEEP C NAC CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 6120UL OR �+ <br /> SIGA-SB4-STANDARD BASE p <br /> 2 COND.14 AWG [2.43D][23pF/FT] [2.43D][37pF/Fl] 96'MAX.TO TOP <br /> F 10"BELL-WALL MOUNT 439D-10AW-R EST INDOOR FLUSH:4"SQUARE,OUTDOOR OF LENS 72"AFF ® r=n <br /> COLOR:RED SURFACE:EST MODEL"449" D MASS.NOTIFICATION NAC CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OUL 60"AFF <br /> 2 COND.14 AWG [2.43D][23pF/FT] [2.430][37pF/FT] 48"MAX(ADA) LL <br /> vs TAMPER SWITCH BY OTHERS BY OTHERS - <br /> E DOOR HOLDER/CONTROL CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OUL <br /> 2COND.I4 AWG [2.43D][23pF/FT] [2.43D][37pF/FT] <br /> F WATER FLOW SWITCH BY OTHERS BY OTHERS CONTACT INFORMATION FINISHED FLOOR <br /> F FAN/HVAC SHUTDOWN BELDEN 5120UL (2)#14 AWG BELDEN 6120UL <br /> PROJECT MANAGER FIRE ALARM DESIGNER 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] 'DEVICES SHOWN DEPICT DEVICE TYPES ONLY. <br /> DAVE PONTNAK HARLAN KIND <br /> (425)272-2250 (512)632-0219 G FUTURE ADA NAC BELDEN 5120UL (2)#14 AWG BELDEN 6120UL <br /> DAVE.PONTNAK@CONVERGINT.COM HARLAN.KIND@GMAIL.COM CIRCUIT COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] <br /> SALES REPRESENTATIVE H PHONE CIRCUIT BELDEN 5220FL N/A BELDEN 6220FL /p <br /> LARRY ONEAL 2 COND.16 AWG SHIELDED [3.9D][65.5pF/FT] [3.85D][77pF/FT] <br /> (425)760-4301 J SPEAKER CIRCUIT BELDEN 5220UL (2)#16 AWG BELDEN 6220UL <br /> LARRY.ONEAL@CONVERGINT.COM 2 COND.16 AWG [3.850][24pF/FT] [3.85Q][37pF/FT] 38th St <br /> L ELEVATOR CONTROL BELDEN 5120UL (2)#14AWG BELDEN 612OUL <br /> GENERAL NOTES 2COND.14 AWG [2.430][23pF/FT] [2.430][37pF/Fr] <br /> M AUDIO RISER BELDEN 5220FL N/A BELDEN 6220FL <br /> 2 COND.16 AWG SHIELDED [3.94][65.5pF/FT] [3.850][77pF/FT] <br /> THE FOLLOWING NOTES ARE INTENDED TO BE GENERAL IN NATURE AND ARE NOT SPECIFIC TO EACH N NETWORK COMMUNICATIONS BELDEN 5220UL (2)#16 AWG BELDEN 6220UL <br /> PROJECT.THESE NOTES ARE TO BE FOLLOWED WHERE APPLICABLE TO INDIVIDUAL PROJECTS AND 2 COND.16 AWG [3.850][24pF/FT] [3.850][37pF/F7] <br /> SHOULD NOT BE TAKEN AS SCOPE OR DIRECTION WHERE THEY CONFLICT WITH INFORMATION FOUND <br /> ELSEWHERE IN THIS DRAWING SET. P 24VDC AUX.POWER BELDEN 5120UL (2)#14 AWG BELDEN 6120UL <br /> 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/FT] 3.9th St <br /> 1. ALL WIRE AND CONDUIT SHALL BE INSTALLED IN ACCORDANCE WITH PLANS AND 0 VESDA NET BELDEN9841 N/A BELDEN89841 Everrtt Memorial <_ <br /> SPECIFICATIONS AND SHALL MEET ALL APPLICABLE CODES. 2 COND.22 AWG [240][12.SpF/FT] [24D][12pF/FT] <br /> 2. ALL WIRE AND CABLE SHALL BE RATED FOR FIRE ALARM USE PER THE LATEST REVISIONS OF R REMOTE LED CIRCUIT BELDEN 5220UL (2)#16 AWG BELDEN 6220UL Z 3C <br /> THE NATIONAL ELECTRICAL CODE(NEC)SECTION 760.THIS IS A POWER LIMITED FIRE ALARM 2 COND.16 AWG [3.850][24pF/FT] [3.85Q][37pF/FT] <br /> SYSTEM.ALL CABLE MUST BE MARKED FPL,FPLP,FPLR OR Cl.FURTHER NEC,REQUIRES ALL <br /> WIRE BE RATED FOR THE ENVIRONMENT FOR WHICH IT IS INSTALLED.ANY REFERENCES TO S ADDRESSABLE DATA SLC LOOP BELDEN 5220UL (2)#16 AWG BELDEN 6220UL _ <br /> WIRE DESIGNATIONS ASSUME ELECTRICAL CONTRACTOR WILL SUBSTITUTE APPROPRIATE 2 COND.16 AWG [3.850][24pF/FT] [3.85Q][37pF/FT] <br /> WIRE TO MEET CODE. T1 ANALOG TWO-WAY COMM.CABLE N/A RATH RP66010001 <br /> 3. ALL CONDUCTORS SHALL TEST FREE OF GROUNDS AND SHORTS BEFORE MAKING ANY 2 COND.18 AWG N/A [2-HOUR CIC] I 40th St _- <br /> CONNECTION TO THE FIRE ALARM CONTROL PANEL. T2 ANALOG TWO-WAY COMM.CABLE RATH 66120 N/A N/A <br /> 4. TO RETAIN WARRANTY,THE FIRE ALARM EQUIPMENT MUST BE POWERED UP UNDER THE 2 COND.18 AWG [2-HOUR] <br /> SUPERVISION OF A QUALIFIED MANUFACTURERS TECHNICIAN. TP ANALOG TWO-WAY POWER CABLE N/A RATH R66010001 DESIGNER OF RECORD <br /> 2 COND.18 AWG N/A [2-HOUR CIC] <br /> 5. THE INSTALLING ELECTRICAL CONTRACTOR SHALL COORDINATE ALL FIELD CHANGES WITH THE <br /> FIRE ALARM CONTRACTOR.THIS INCLUDES CHANGES IN DEVICES,WIRE,CONDUIT RUNS AND U SUPPRESSION RELEASING CIRCUIT BELDEN 5120UL (2)#14 AWG BELDEN 612OULIV <br /> OPERATION OF THE SYSTEM.FIRE ALARM CONTRACTOR SHALL NOT BE HELD RESPONSIBLE 2 COND.14 AWG [2.430][23pF/FT] [2.430][37pF/Fl] A,St S� FlaeAURM sysTems <br /> FOR UNDOCUMENTED CHANGES OR THE RESULTS OF THOSE CHANGES. - - �-- <br /> W SINGLE MODE FIBER NETWORK BUDGET DUPLEX <br /> SC 15/25 dBm L _� _ <br /> 6. FIRE ALARM NOTIFICATION DEVICES SHALL BE AUDIBLE THROUGHOUT THE SPACE AND SHALL 8.3p SM CONNECTOR:DUPLEX SC SC --- Ir FOR vewFlcAnoe vLEASE VISIT www Nicer oac <br /> HAVE A SOUND PRESSURE LEVEL NOT LESS THAN 15db ABOVE THE AVERAGE AMBIENT SOUND X MULTIMODE FIBER NETWORK BUDGET MMXVR:10 dB. C 2023 Microsoft Corporation®2023 TomTomr MEto� <br /> y,r <br /> LEVEL. 5db ABOVE THE MAXIMUM SOUND LEVEL,MEASURED AT 5'0"ABOVE THE FINISHED 50/125P'62.5/125p OR 100/140p MM CONNECTOR:ST <br /> FLOOR. `¢- <br /> Y TWO-WAY COMMUNICATIONS BELDEN 1583A N/A BELDEN 1585A VICINITY MAP <br /> 7. MAIN BUILDING FIRE ALARM&SUPPRESSION SYSTEMS SHALL BE CLASS"B"WIRING. CAT5E-(4)PAIR 22 AWG N <br /> PRE-ACTION&DELUGE ALARM SYSTEMS SHALL BE CLASS"A"WIRING.CLASS"A"APPLICATIONS rq FIRE/SMOKE DAMPER INTERFACE BELDEN 5120UL (2)#14 AWG BELDEN 6120UL conve rg j nt"SHALL MAINTAIN A MINIMUM SEPARATION OF 48 INCHES HORIZONTALLY&12 INCHES 2 COND.14 AWG [2.430][23pF/FT] [2.43D][37pF/FT] <br /> VERTICALLY BETWEEN OUTGOING AND RETURN CIRCUITS. <br /> NOTE:ALL LISTED RESISTANCE AND CAPACITANCE ARE CONDUCTOR TO CONDUCTOR.ALL <br /> 8. ALL PULL STATIONS AND NOTIFICATION DEVICES SHALL BE MOUNTED AT HEIGHTSSPECIFIED RESISTANCE VALUES ARE PER 1000 FEET. ABBREVIATIONS <br /> PER NFPA 72 AND ADA REQUIREMENTS. <br /> 9. ALL DETECTOR SPACING SHALL BE PER NFPA 72&LOCAL CODES. AC-ABOVE CEILING FSD-FIRE SMOKE DAMPER(THIRD PARTY) <br /> AFF-ABOVE FINISHED FLOOR HVAC-HEATING,VENTILATION,AND AIR <br /> 10. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL ROUGH-IN LOCATIONS WITH OTHER Sheet List Table ADA-A THORI N DISABILITIES ACT CONDITIONING(THIRD PARTY) <br /> AHJ-AUHORITY HAVING JURISDICTION LA-LOW AIR(THIRD PARTY) <br /> TRADES. Sheet Number Sheet Title AHU-AIR HANDLING UNIT(THIRD PARTY) N/A-NOT APPLICABLE <br /> 11. ALL FIRE ALARM DEVICES SHALL BE SECURELY FASTENED TO WALLS OR CEILINGS. FA-0-1 COVER SHEET ASO-ASPIRATION SMOKE DETECTION NAC-NOTIFICATION APPLIANCE CIRCUIT <br /> FA-0-2 NOTES CD-CANDELA(EX.15CD) NFPA-NATIONAL FIRE PROTECTION ASSOCIATION <br /> 12. SMOKE DETECTORS SHALL NOT BE LOCATED CLOSER THAN 36"TO ANY AIR REGISTER OR FA-1-1 LOWER BUILDING BASEMENT&1ST FLOOR CIS-COMMON INTELLIGIBILITY SCALE NIC-NOT IN CONTRACT <br /> DH-DOOR HOLDER(THIRD PARTY UNO) NTS-NOT TO SCALE <br /> DIFFUSER. FA-1-2 LOWER BUILDING 2ND FLOOR EF-EXHAUST FAN(THIRD PARTY) PS-POWER SUPPLY <br /> 13. HEAT DETECTORS SHALL NOT BE LOCATED CLOSER THAN 36"TO ANY AIR REGISTER OR FA-1-3 LOWER BUILDING 3RD FLOOR ELEV-ELEVATOR(THIRD PARTY) RTU-ROOF TOP UNIT(THIRD PARTY) <br /> FA-1-4 UPPER BUILDING BASEMENT EOL-END OF LINE SLC SIGNALING LINE CIRCUIT <br /> DIFFUSER. FA-1-5 UPPER BUILDING IST FLOOR EPF-ELEVATOR PRESSURIZATION FAN(THIRD PARTY) SPF-STAIR PRESSURIZATION FAN(THIRD PARTY) <br /> 14. PER NFPA 72,CHAPTER 17;SMOKE DETECTORS INSTALLED PRIOR TO FINAL CLEAN MUST BE FA-1-6 UPPER BULDING 2ND FLOOR FA-FIRE ALARM STI-SPEECH TRANSMISSION INDEX <br /> CLEANED AND VERIFIED TO BE OPERATING IN ACCORDANCE WITH THE LISTED SENSITIVITY,OR FA-1-7 UPPER BUILDING 3RD FLOOR FAA-FIRE ALARM ANNUNCIATOR TYP-TYPICAL <br /> THEY SHALL BE REPLACED PRIOR TO THE FINAL COMMISSIONING OF THE SYSTEM. FA-2-1 TYPICAL RISER FACP-FIRE ALARM CONTROL PANEL UNO-UNLESS NOTED OTHERWISE <br /> FACU-FIRE ALARM CONTROL UNIT VAV-VARIABLE AIR VOLUME(THIRD PARTY) <br /> CONVERGINT BEARS NO RESPONSIBILITY FOR LABOR OR MATERIAL ASSOCIATED WITH FA-3-1 FACP DETAILS FA7C-FIRE ALARM TERMINAL CABINET VFD-VARIABLE FREQUENCY DRIVE(THIRD PARTY) <br /> CLEANING,SENSITIVITY TESTING OR REPLACEMENT OF SMOKE DETECTORS INSTALLED PRIOR FA-4-1 DEVICE DETAILS FBO-FURNISHED BY OTHERS W/-WITH <br /> TO FINAL CLEANING. FA-5-1 I CALCULATIONS FCU-FAN COIL UNIT(THIRD PARTY) W-WATT(EX.1/2W) <br /> 15. HEAT DETECTORS SHALL NOT BE LOCATED CLOSER THAN 36"TO ANY HEAT GENERATING FFT-FIREFIGHTER'S TELEPHONE WP-WEATHERPROOF <br /> DEVICE(FUSES,BOILERS,WATER HEATERS,ETC.)IN MECHANICAL ROOMS. FM-FACTORY MUTUAL XP-EXPLOSION PROOF <br /> Ref JOBR-DESCRIPTION DALE <br /> 16. HEAT DETECTORS SHALL NOT BE LOCATED CLOSER THAN 18"TO ANY PART OF ANY LIGHT FLOOR PLAN KEY a ISSUEDFORPERMIT 12ASNM. XN <br /> FIXTURE. <br /> DEVICE ADDRESS KEY DETAIL BUBBLE KEY <br /> 17. HEAT DETECTORS SHALL BE MOUNTED WITHIN 24"OF A SPRINKLER HEAD WHEN USED FOR <br /> ELEVATOR SHUNT TRIP IN ELEVATOR MACHINE ROOMS&SHAFTS. // DETAIL NUMBER <br /> FIRE ALARM PANEL# <br /> 18. INITIATING AND SIGNALING CIRCUITS MAY BE RUN IN SAME CONDUIT. O // DEVICE ADDRESS 4DETAIL <br /> 19. ALL CONDUCTORS SHALL BE LABELED BY ZONE OR SLC LOOP NUMBER. z-x-xxzz-x LOCATION I- SAME SHEET) <br /> p 20. THESE DRAWINGS ARE INTENDED TO SHOW PROJECT SPECIFIC PANELS,DEVICES AND WIRING DATACARD, _ISOLATED <br /> REDBRANCH <br /> U DEPICTED DIAGRAMMATICALLY.WIRING SHOWN IS NOT INTENDED TO DEPICT RACEWAY OR LOGICAL ADDRESS (A ) NAI u. <br /> p PATHWAY LOCATIONS.DEVICE AND PANEL LOCATIONS SHALL BE COORDINATED BY INSTALLING PROJECT DESIGNER: <br /> JCONTRACTOR AS PART OF THE CONSTRUCTION PROCESS. MR: DAVE, <br /> Q NOTIFICATION DEVICE CIRCUIT KEY DRAWING SHEET INDEX KEY ­212117 <br /> U 21. ALL REFERENCES TO INTERNATIONAL BUILDING CODE(IBC)ARE FROM THE 2015 EDITION.ALL wN DATE: tzta�oz <br /> U REFERENCES TO NFPA 72 ARE FROM THE 2013 EDITION AS CURRENTLY ADOPTED BY IBC.THE SPEAKER CIRCUIT NUMBER FIRE ALARM �LEVEUFLOOR/ARFA <br /> Q ADOPTED VERSION FOR THE PROJECT JURISDICTION MAY BE DIFFERENT AND UPON REQUEST CIRCUIT <br /> In CONVERGINT WILL PROVIDE UPDATED REFERENCE SECTIONS TO MATCH ADOPTED VERSION. CIRCUIT NUMBER SIP X FA-X.XX CASCADIAN PLACE <br /> W <br /> � THE SCOPE SECTION OF OUR DRAWINGS WILL PROVIDE THE VERSION REFERENCED FOR THE POWER SUPPLY PANEL REPLACEMENT <br /> SUFFIX Eel! � <br /> FIRE ALARM DESIGN. � 0=COVER SHEET 3915 COLBY AVE N <br /> 7 XX-MX.X 1=FLOOR PLANS <br /> x 22. AS THE FIRE ALARM VENDOR UTILIZED FOR THIS BUILDING,NFPA 72 REQUIRES WE KEEP `\ 2-RISER DIAGRAMS EVERETT,WA 98201 <br /> ACCURATE RECORD DRAWING INFORMATION.AS SUCH,IT IS NECESSARY THAT WE DEPICT LOGICAL DEVICE NUMBER 3=FIRE PANEL DETAILS <br /> EXISTING DEVICES AND WIRING IN ADDITION TO THOSE COMPONENTS ASSOCIATED WITH YOUR 4 5-DEVICE DETAILS <br /> =CALCULATIONS <br /> � SCOPE WHERE APPLICABLE.UNLESS OTHERWISE NOTED,IT IS ASSUMED EXISTING 6=2-WAY COMMUNICATION <br /> 0 COMPONENTS WILL REMAIN UN-DISTURBED BY YOUR OFAID IN IDENTIFYING <br /> Z NEW S.EXSTNG,WE WILL TURN EXISTING CO PONEN SPTOALIGHTERSHADE.REMOVAL F COVER SHEET <br /> U THE EXISTING DEVICES AND WIRING MAY OTHERWISE IMPACT THE CONTEXT OF THE <br /> COMPLETE,CODE REQUIRED FIRE ALARM SYSTEM,THEREFORE THEY CANNOT BE OMITTED <br /> Z FROM OUR DRAWNG PACKAGE. FIRE ALARM SYSTEM <br /> WING. <br /> o FA-0-1 <br /> tL <br />