4. Record Pressures - Record static pressure, then flow both valves simultaneously <br />for 30 seconds and record residual pressure while flowing. <br />Static Pressure Residual Pressure <br />5. Amount of Water - Measure the amount of water flowed into a calibrated 55El El El <br />- <br />gallon drums. <br />Drum #1 Gallons Drum #2 Gallons <br />6. Calculate GPM - Verify flow rates meet or exceed required hydraulically calculated El El El <br />gpm. <br />Total Gallons Flowed X2 = > Required gpm. <br />Final Inspection: <br />PASS FAIL N/A <br />7. Schedule - A final inspection should be performed when the house is complete, El El El <br />or nearly complete. <br />8. <br />Approved Plans - Approved plans on site? And all work completed per plans? <br />El El El <br />9. <br />Head Inspection - All sprinkler heads shall be uncovered, with escutcheons or trim <br />El El El <br />rings in place. For concealed heads, the cover plates shall be off. <br />10. <br />Obstructions - Verify that no architectural features have been constructed or <br />El El El <br />installed that will obstruct the coverage from the sprinkler discharge or result in a <br />change of sprinkler coverage. <br />11. <br />Protective Covers - Check to see that all protective coverings are removed for <br />El El El <br />sprinklers heads. <br />12. <br />Painted Heads - Ensure that sprinklers or cover plates on concealed sprinklers <br />El El El <br />have not been painted by anyone other than the sprinkler manufacturer. <br />13. <br />Verify Pressure Gauges - Verify that the pressure gauge provided on the riser is at <br />El El El <br />the minimum required pressure and ensure that the system is fully operational. <br />14. <br />NFPA 13D Report - The installer shall complete and sign the contractor's material <br />El El El <br />and test certificate prior to final approval of the system. <br />15. <br />Address - Verify that the address to the building is posted and in compliance with <br />El El El <br />the requirement for the City of Everett. <br />16. <br />Fire Department Access - Ensure that fire department access is posted and meets <br />El El El <br />the requirements for the City of Everett. <br />Fire Marshal's Office 425.257.8100 1 everettwa.gov/fire I INFORMATION HANDOUT C-7 4.20.2020 1 Page 6 <br />