2 3 4 5 6 <br /> -COFFMAN <br /> FLAG NOTES: ENGINEERS <br /> 1101 2nd Avenue, <br /> D PROVIDE NEW 2-INCH DOMESTIC WATER LINE FROM EXISTING 2-INCH DOMESTIC Suite 400 <br /> WATER PIPE TO SERVE ULTA TENANT SPACE.OWNER TO VERIFY THAT EXISTING Seattle,WA 98101 <br /> DOMESTIC WATER SERVICE CAN SUPPORT A NEW CONNECTION TO THE ULTA TENANT <br /> SPACE OF AT LEAST 35 PSI AND 50 TO 60 GPM MINIMUM FLOW.PRV TO BE ph 206.623.0717 <br /> PROVIDED AT NEW TENANT SPACE IF WATER PRESSURE EXCEEDS 80 PSI.CAP <br /> DOMESTIC WATER PIPE IN TENANT SPACE FOR FUTURE TENANT CONNECTION. <br /> 2D PROVIDE NEW DOMESTIC WATER SUB-METER AND RPBP ASSEMBLY IN TENANT SPACE. www.COffman.com <br /> PROVIDE FUNNEL DRAIN BELOW RPBP ASSEMBLY AND ROUTE RPBP DRAIN TO IT. <br /> PROVIDE REQUIRED CLEARANCES FOR MAINTENANCE AND SERVICE. <br /> D PROVIDE NEW RPBP AND VALVE ASSEMBLY AT EXISTING DOMESTIC WATER MAIN RISER. <br /> E PROVIDE NEW FUNNEL DRAIN BELOW RPBP AND ROUTE RPBP DRAINAGE TO IT. E XIAD NA <br /> MAINTAIN ALL CLEARANCES FOR MAINTENANCE AND SERVICE. <br /> ®PROVIDE NEW GAS SUB-METER FOR ULNA TENANT SPACE SIZED FOR A MINIMUM OF <br /> 1,100 MBH CAPACITY. �SN' <br /> 5 PROVIDE NEW 10-INCH COMBUSTION AIR INTAKE UP THROUGH ROOF.EXTEND INTAKE Q� G <br /> O <br /> D DOWN BELOW ROOF DECK TO TERMINATE AT LEAST 14-FEET A.F.F. NOS � <br /> ©PROVIDE NEW VENT THRU ROOF.EXTEND AT LEAST 24-INCHES BELOW ROOF DECK <br /> AND CAP FOR FUTURE TENANT CONNECTION. 7022 <br /> D PROVIDE NEW WATER HEATER VENT THRU ROOF.EXTEND AT LEAST 24-INCHES BELOW <br /> ROOF DECK AND CAP FOR FUTURE TENANT CONNECTION. <br /> D PROVIDE NEW DRYER EXHAUST VENT THRU ROOF.TERMINATE AT 6-FOOT A.F.F.FOR <br /> FUTURE TENANT CONNECTION. <br /> D D <br /> 22 21 20 —719 18 17 16 15 13 12 11 10 9 7 6 �t <br /> 4 2 1 <br /> (E)WALL HYDRANT (E)WALL H D NT <br /> FIRE <br /> (E)1-1/2"CW RISER <br /> (E)1-1/2"cw EVERETT MALL <br /> RENOVATION <br /> PHASE 1 <br /> (E)1 1/2"CW <br /> HYDRANT <br /> PALLETS TRASH/RECYCLE <br /> C )WALL HYDRANT <br /> (E)2"C <br /> p 1402 SE EVERETT <br /> MALL WAY <br /> EVERETT, WA 98208 <br /> HYD ANT 1 <br /> ENAN 1 LOADING DOCK (E)WALL HYDRANT <br /> 83,400 SF TENAN 2 <br /> 13,230 S <br /> C <br /> E) 1 'CW <br /> HYD ANT <br /> (E)2"C <br /> B BD4' R B <br /> EX ST <br /> (E)1-1/2"CW TH F <br /> 0 <br /> 0 <br /> 28,_ „ <br /> (E)1-1/2"CyY 07/08/22 50%DD SET <br /> 5 REV DATE DESCRIPTION <br /> 2-CW <br /> TENANT 3 PROD.NO. 221522 <br /> h �p,� DRAWN CEI <br /> 6°TYPE B� ,�f, S r <br /> 3 0 > WATER HEA �J J Jr CHECKED ON <br /> S VENT THRU R00� (E)WALL HYDRANT <br /> DATE 06/27/22 <br /> c5 ©to*AIR COMBUSTION �Q <br /> SWIT H GEAR AIR INTAKE THRU J RPBP <br /> A, ROOF ©COFFMAN ENGINEERS INC. <br /> SUB METER <br /> (E)3 C 2 <br /> (E)1 1/2"CW <br /> LTA 86-2 1/4.. 2° (E)1-1/2"CW SHEET TITLE: <br /> c / R MEET RS VAUL 0 4 R HOUS F <br /> E EL ./ (E)1-1/2"Cw PLUMBING FLOOR <br /> NTRY MPOE <br /> PLAN <br /> (E)ADJ ENT AS M ERS <br /> A (E)WALL HYDRANT TENANT AS <br /> 0 1-1/2C UP (E)WALL HYDRANT <br /> RISER A <br /> a <br /> 'o <br /> rE <br /> SHEET NO: <br /> ® PLUMBING FLOOR PLAN P201 <br /> o SCALE: 1/16"= 1'-0" <br /> a <br /> a SHEET X OF xxx <br /> 1 2 3 4 5 6 <br />