Laserfiche WebLink
Seismic Load Calculation for Components and System <br /> (Reference: 2018 IBC Section 1613&ASCE 7-16 Section 13.3) <br /> Seismic Force: <br /> 0.2s Spectral Response Acceleration,Site Class B,S, = 1.349 (ASCE 7,Figure 22-1 thru 22-8) <br /> 1.Os Spectral Response Acceleration,Site Class B,Si = 0.478 (ASCE 7,Figure 22-1 thru 22-8) <br /> D(assumed/ <br /> Site Class = default) (ASCE 7,Section 11.4.3) <br /> Seismic Design Category = D (ASCE 7,Tables 11.6-1&11.6-2) <br /> Site Coefficient per S,&Site Class,F, = 1.20 (ASCE 7,Table 11.4-1) <br /> Site Coefficient per Si&Site Class,F, = 1.82 (ASCE 7,Table 11.4-2) <br /> SMs=F,S, = 1.619 (ASCE 7,Section 11.4.4) <br /> SMs=F0S1 = 0.871 (ASCE 7,Section 11.4.4) <br /> SDs=2/3 SMs = 1.079 (ASCE 7,Section 11.4.5) <br /> Su,=2/3 SMs = 0.581 (ASCE 7,Section 11.4.5) <br /> (Per ASCE 7-16,13.3) <br /> Component Amplification Factor,ap = 1.0 (ASCE 7,Table 13.6-1) <br /> Component Response Modification Factor,Rp = 2.5 (ASCE 7,Table 13.6-1) <br /> Overstrength Factor,no = 2.0 (ASCE 7,Table 13.6-1) <br /> Component Importance Factor,Ip = 1.0 (ASCE 7,Table 1.5-2) <br /> Component Operating Weight,Wp = Wp (lb) <br /> Height in structure at lowest point of attachment of component,z1 = 28.5 (ft) <br /> Height in structure at highest point of attachment of component,z2 = 28.5 (ft) <br /> Average Roof Height of Structure,h = 28.5 (ft) <br /> Seismic design force,Fp = O.4aPSDSWp (1+2z/h) <br /> Rp/Ip (Eq.13.3-1) <br /> Max.seismic design force,Fp,,,,,t = 1.6S,„si0Wp (Eq.13.3-2) <br /> Min.seismic design force,Fpnp„ = 0.3SmIpWp (Eq.13.3-3) <br /> Seismic design force at lowest point,Fpl = 0.518 Wp <br /> Fp(AVM.' 0.518 <br /> Seismic design force at highest point,FP2 = 0.518 Wp <br /> Min.seismic design force,Fp,„,„ = 0.324 We <br /> Max.seismic design force,Fp,,,, = 1.727 Wp <br /> Seismic design force,Fp(ASD) = 0.370 Wp <br /> Description By Date <br /> 1DM 1/27/2023 <br /> ENGINEERING Checked DateSeismic Loads For Components&Systems <br /> Project Scale Sheet No. <br /> N.T.S. <br /> 250 4th Ave.South SN17 Eastmont <br /> Suite 200 Job No. <br /> Edmonds,WA 98020 23007.128 <br /> 12 <br />