Laserfiche WebLink
11■41116TI <br /> Hilti PROFIS Engineering 3.0.40 <br /> • www.hilti.com <br /> Company: Page: 3 <br /> Address: Specifier. <br /> Phone I Fax: I E-Mail: <br /> Design: Work Shed column A2 Date: 4/3/2019 <br /> Fastening point: <br /> 3.2 Pullout Strength <br /> No =W,p Ni, ACI 318-14 Eq.(17.4.3.1) <br /> Np =8 A. f. ACI 318-14 Eq.(17.4.3.4) <br /> 4 Np,t t N„a ACI 318-14 Table 17.3.1.1 <br /> Variables z� <br /> 4/eo A (in.I X e fc(psq <br /> 1.000 0.65 1.000 4.500 <br /> Calculations <br /> Ni,[lb] <br /> 23,544 <br /> Results <br /> Np (lb] Sconcrete +Win* Snondutal 0 NPn I!bL N"`11b1 <br /> 23,544 0.700 0.750 1.000 12,361 2,000 <br /> III <br /> III <br /> Input data and results must be checked for conformity with the existing conditions and for plausibility! <br /> PROFIS Engineering(c)20034009 Had AG.FL•9494 Schoen Had 4 a registered Trademark of Had AG,Schaan <br /> 3 <br /> 04/05/19 Boeing Flightline Stall 113 Page 91 <br />