Command Centers Installation, Warranty, and Training
<br /> System command centers shall be Radionics D1255 Installation of the system, wiring of initiating devices and
<br /> Command Center, D1256 Fire Command Center, and signaling circuits shall be the responsibility of the
<br /> D1257 Fire Annunciator. Each of these shall be equipped installing company.
<br /> with a 16-character alphanumeric display, distinct fire and
<br /> burglary tones, and backlighted multi-key touchpad. Warranty on all components shall be for one year, subject
<br /> to manufacturer's limitations. Training in the complete
<br /> The D1255, D1256, and D1257 shall have the ability to operation of the system shall be furnished by the
<br /> display the following for each detection point: alarm, installing company upon completion of the installation.
<br /> trouble, service,faulted, and custom text. In addition,
<br /> expanded, addressable point displays shall include Listings and Approvals
<br /> missing and extra, point information. System wide
<br /> displays shall include: local system test, sensor reset, Fire
<br /> fire test mode, and user programming prompts. UL: Central Station, Local, Auxiliary, Remote Station, and
<br /> Remote Diagnostics and Controls Household Fire Warning.
<br /> Remote control through the use of the Remote Account CFSM,FM and NYC-MEA approved.
<br /> Manager software shall include: reset of audible signals,
<br /> activation/deactivation of D8129 relays, interrogation of Burglary
<br /> battery, point and armed status, the enabling or disabling UL: Central Station, Local, Police Connect, Bank Safe and
<br /> of reporting functions, and the shunting of reporting points Vault, Mercantile Safe and Vault, and Grade A Household
<br /> during servicing. systems.
<br /> System Test DOD: Approved for installations in Sensitive Compart-
<br /> The Fire Test mode shall support single person mented Information Facilities (SCIF).
<br /> operation. All reports to the central station shall be
<br /> suppressed while the fire test is being conducted. The
<br /> Fire Test mode shall be activated by entering a user
<br /> passcode at the D1255R. All testing data shall be visible
<br /> on command center and annunciator displays during
<br /> testing.
<br /> Hardware
<br /> The D9112 shall provide up to 246 individually identified
<br /> addresses. Each shall accommodate normally open and/
<br /> or normally closed devices with End-Of-Line resistor
<br /> supervision. Each point shall be programmable for fire,
<br /> fire supervisory or burglary applications. Also, silent or
<br /> steady and/or pulsed audible, and local or remote
<br /> reporting to a receiver.
<br /> External Hardware
<br /> The D9112 shall allow the use of up to three on-site
<br /> parallel printers using Radionics D9131A Printer Interface
<br /> Modules. Events shall print as they are stored in logger.
<br /> The printer shall print the time, date, account number,
<br /> event,point ID,point text and user text.
<br /> Radionics'
<br /> © 1997 Radionics,Inc.,Salinas,CA, USA.All rights reserved. ISO 9002
<br /> Ell
<br /> nA The Radionics logo is a registered trademark of Radionics, Inc.,Salinas,CA. CERTIFICATE NO.3946
<br /> L772 P/N 32236C (10/97) Radionics, Inc., 1800 Abbott Street, L772 P/N 32236C
<br /> Salinas,CA,93901, U.S.A.
<br /> 38
<br />
|